Honeywell NOTIFIER FMM-1 Installation And Maintenance Instructions
Honeywell NOTIFIER FMM-1 Installation And Maintenance Instructions

Honeywell NOTIFIER FMM-1 Installation And Maintenance Instructions

Monitor module

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
FMM-1 Monitor Module
SPECIFICATIONS
Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current:
EOL Resistance:
Maximum IDC Wiring Resistance:
Maximum IDC Voltage:
Maximum IDC Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Listed to: UL 864 and UL 2610
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the appropriate Notifier control panel installation manual for detailed system
information. If the modules will be installed in an existing operational system,
inform the operator and local authority that the system will be temporarily
out of service. Disconnect power to the control panel before installing the
modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The FMM-1 Monitor Module is intended for use in intelligent, two-wire sys-
tems, where the individual address of each module is selected using the built-
in rotary switches. It provides either a 2-wire or 4-wire fault tolerant initiating
device circuit (IDC) for normally open contact fire alarm and supervisory de-
vices, or either normally open or normally closed security devices. The mod-
ule has a panel controlled LED indicator. The FMM-1 can be used to replace
an MMX-1 module in existing systems. FMM-1 is also UL Listed as a com-
mercial proprietary burglar alarm accessory and a commercial central station
burglar alarm accessory.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
NOTIFIER system control panel (list available from NOTIFIER).
FIGURE 1. CONTROLS AND INDICATORS
15 to 32 VDC
5.0 mA (LED on)
375 µA (group poll); 350 µA (direct poll); 600 µA Max. (Communicating, IDC Shorted)
47K Ohms
1,500 Ohms
11 Volts
450µA
32°F to 120°F (0°C to 49°C)
10% to 93% Non-condensing
4
1
˝ H x 4˝ W x 1
1
˝ D (Mounts to a 4˝ square by 2
2
4
SMB500 Series Electrical Box
C1067-00
1
˝ deep box.)
8
MOUNTING
The FMM-1 mounts directly to 4-inch square electrical boxes. (See Figure
2). The box must have a minimum depth of 2
mounted electrical boxes (SMB500-WH) are available from NOTIFIER.
FIGURE 2. MODULE MOUNTING
NOTE: For UL Listed security installations, the FMM-1 must be mounted
within the control panel enclosure.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Set the address on the module per job drawings.
3.
Secure module to electrical box (supplied by installer). See Figure 2.
NOTE: All references to power limited represent "Power Limited (Class 2)".
NOTE: Dispose electronic waste following national and/or local regulations.
1
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161
1
/
inches (54 mm). Surface
8
ISOLATED
QUADRANT
C1066-00
I56-3506-005
5/23/2022

Advertisement

loading

Summary of Contents for Honeywell NOTIFIER FMM-1

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS 12 Clintonville Road FMM-1 Monitor Module Northford, CT 06472-1653 Phone: 203.484.7161 SPECIFICATIONS Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 5.0 mA (LED on) Average Operating Current: 375 µA (group poll); 350 µA (direct poll); 600 µA Max. (Communicating, IDC Shorted) EOL Resistance: 47K Ohms Maximum IDC Wiring Resistance:...
  • Page 2 Testing should be performed annually, as per NFPA72. The installer should be familiar with and follow the best practices set forth within ANSI/SIA CP-01 for troubleshooting and reduction in dispatch calls. NOTIFIER ® and Honeywell ® are registered trademarks of Honeywell International, Inc. I56-3506-005 ©2022 NOTIFIER. 5/23/2022...