CLCM1H,6H,6T
Digital Wall Modules
FUNCTIONAL OVERVIEW
Table 1. Functional overview
model
sensor
CLCM1H112
temp. / humidity
CLCM6H212
temp. / humidity
CLCM6T21N
temperature
BEFORE INSTALLATION
All wiring must comply with local electrical codes and
ordinances or as specified on installation wiring diagrams.
Digital Wall Module (DWM) wiring can be sized from 1.5 to
2
0.34 mm
, depending on the application. The maximum
length of wire from a device to a DWM is 50 m. Twisted pair
wire is recommended for wire runs longer than 30.5 m.
CAUTION
EMI Noise Introduction. Risk of erratic system
operation.
Keep wiring at least 300 mm away from large induc-
tive loads such as motors, line starters, lighting
ballasts and large power distribution panels. During
installations, try to avoid areas of high EMI noise.
Run DWM wiring separately from 50 Vac or greater
power wiring.
WARNING / CAUTION
Risk of electric shock or equipment damage!
►
Do not touch any live parts inside the DWM housing.
►
Disconnect the power supply before making connections
to or removing connections from the DWM's terminals.
►
Do not reconnect the power supply until you have com-
pleted the installation.
►
If the DWM is powered via terminal 8 and connected to
earth ground, then the cable must be shielded.
►
Observe precautions for handling electrostatic sensitive
devices.
Copyright © 2016 Honeywell GmbH ● All Rights Reserved
Installation Instructions
suitable controllers
PANTHER
PANTHER
PANTHER + SERVAL
Cover Disassembly/Assembly
The DWM comes packed with a sub-base that mounts
separately for ease of installation; to disassemble the cover
and the sub-base, see Fig. 1. When re-attaching, make sure
that the latch on the underside of the DWM engages
properly.
LIFT
2
1
PRESS
Fig. 1. Cover disassembly / assembly
INSTALLATION
NOTE:
Maintain a mounting clearance of approx. 10 cm on
both sides of the DWM in order to allow a free airflow
for the temperature sensor and accessibility of the
setpoint dial.
Do not mount the DWM on an outside wall, on a wall
containing water pipes, or near air ducts. Avoid
locations exposed to discharge air from registers or
radiation from lights, appliances, or the sun.
The wall modules can be mounted on a 60-mm wall outlet
box using 3.5-mm screws or on a wall (see Fig. 2). When
mounting directly on a wall, use the type of screws
appropriate for the wall material.
See Fig. 5 for bore-holes and mounting dimensions
(dimensions are the same for all models).
sub-base
cover
screw
Fig. 2. Mounting of DWM (CLCM6H,6T shown)
screw