JADE™ Economizer Module
(MODEL W7220)

PRODUCT DESCRIPTION

The JADE™ Economizer System is an expandable
economizer control system, which includes a W7220
Economizer Module (controller) with an LCD and keypad. The
W7220 can be configured with optional sensors.
The W7220 Economizer Module can be used as a stand-
alone economizer module wired directly to a commercial set
back space thermostat and sensors to provide Outdoor Air
dry-bulb economizer control.
The W7220 Economizer Module can be connected to optional
Sylk Bus sensors for single or differential economizer control.
The W7220 Economizer Module provides power and
communications on the Sylk Bus for the Sylk Bus sensors.
The W7220 Economizer Module automatically detects
sensors by polling the Sylk Bus to determine which sensors
are present. If a sensor loses communications after it has
been detected, the W7220 Economizer indicates a device fail
error on its LCD.
System Components
The JADE™ Economizer System includes an Economizer
Module, 20k mixed air sensor, damper actuator, an optional
CO
sensor, and either a 20k outdoor air temperature sensor
2
or Sylk Bus sensors for measuring Outdoor Air and return air
enthalpy, temperature, and humidity.
Economizer Module
This is the core of the JADE™ Economizer System and
includes the user interface for the system. The W7220
Economizer Module provides the basic inputs and outputs to
provide simple economizer control. When used with the
optional Sylk Bus sensors, the Economizer Module provides
more advanced economizer functionality.
Sylk Bus Sensors (optional)
The Sylk Bus Sensor is a combination temperature and
humidity sensor which is powered by and communicates on
the Sylk Bus. Up to three sensors may be configured with the
JADE™ Economizer Module.
CO
Sensor (optional)
2
A CO
sensor (non-communicating or non-Sylk Bus) can be
2
added for Demand Control Ventilation (DCV).
Product Description ..........................................................
Specifications ...................................................................
Before Installation .............................................................
Installation and Setup .......................................................
Mounting ...........................................................................
Wiring ...............................................................................
Wiring Application Examples ............................................
Interface Overview ............................................................ 12
Setup and Configuration ................................................... 17
Checkout .......................................................................... 22
Troubleshooting ................................................................ 24
E4436
PRODUCT DATA
Contents
1
2
3
3
3
4
7
63-2700-05

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell JADE W7220

  • Page 1: Table Of Contents

    JADE™ Economizer Module (MODEL W7220) PRODUCT DATA The W7220 Economizer Module automatically detects sensors by polling the Sylk Bus to determine which sensors are present. If a sensor loses communications after it has been detected, the W7220 Economizer indicates a device fail error on its LCD.
  • Page 2: Specifications

    W7220A Economizer Module 2k ohm; Sylkbus two-wire output for Honeywell Sylkbus communicating actuators. The module is designed for use with any Honeywell 2 to 10 Vdc or Honeywell Sylkbus communicating actuator. The Exhaust fan, Y1, Y2 and AUX1 O: module includes terminals for a CO...
  • Page 3: Before Installation

    JADE™ ECONOMIZER MODULE BEFORE INSTALLATION MOUNTING Review the “Specifications” on page 2 before installing the The This section describes the mounting procedures for the JADE™ Economizer System. JADE™ Economizer module and the sensors. When Installing This Product Economizer Module Location and Mounting 1.
  • Page 4: Wiring

    JADE™ ECONOMIZER MODULE WIRING Sensor Mounting The sensors can be mounted directly on to the sheet metal of unit or can be mounted in the air stream using the duct All wiring must comply with applicable electrical codes and mounting kit (order separately). ordinances, or as specified on installation wiring diagrams.
  • Page 5 JADE™ ECONOMIZER MODULE Table 1. Economizer Module - Left hand terminal blocks. 1. STRIP 1/2 IN. (13 MM) FROM WIRES TO Label Type Description BE ATTACHED AT 1/2 (13) ONE TERMINAL. Top Left Terminal Block 20k NTC Mixed Air Temperature Sensor (polarity insensitive connection) 2.
  • Page 6 JADE™ ECONOMIZER MODULE Sylk Bus Sensor Wiring NOTE: When using the Sylkbus sensors there will be a slight delay while the Jade controller and the sen- Use Fig. 6 and Table 3 to locate the wiring terminals for each sor communicate. Analog sensors do not commu- Sylk Bus sensor.
  • Page 7: Wiring Application Examples

    JADE™ ECONOMIZER MODULE WIRING APPLICATION Stand-alone Economizer EXAMPLES The most basic configuration is the stand-alone Economizer (see Fig. 7 and Fig. 9). This section describes the wiring configurations for the JADE™ A stand-alone Economizer is directly wired to sensors, Economizer system. The configurations are: actuators, thermostat, and mechanical controls in the roof top —...
  • Page 8 MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W. WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C. M32564B Fig. 9. Stand-alone dry-bulb Economizer configuration with Honeywell MS7503 or MS7505 Direct Coupled Actuator. ROOF TOP UNIT MA TEMP...
  • Page 9 THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W. WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C. M32565B Fig. 11. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black motor. 63-2700—05...
  • Page 10 MAY BE LABELED W. WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C. M32566B Fig. 12. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7503 or MS7505 Direct Coupled Actuator. 63-2700—05...
  • Page 11 SYLKBUS SENSOR WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C. M32653B Fig. 13. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS3103J or MS3105J communicating actuators. NOT USED AUX2-1...
  • Page 12: Interface Overview

    JADE™ ECONOMIZER MODULE INTERFACE OVERVIEW Using the Keypad with Settings and Parameters This section describes how to use the Economizer’s user To use the keypad when working with Setpoints, System and interface for: Advanced Settings, Checkout tests, and Alarms: • Keypad and menu navigation •...
  • Page 13 JADE™ ECONOMIZER MODULE Table 5. Menu Structure Parameter Parameter Range and Default Menu Parameter Value Increment Notes STATUS YES = economizing available; the system can use Outdoor Air for free ECON AVAIL YES/NO cooling when required. ECONOMIZING YES/NO YES = Outdoor Air being used for 1 stage cooling.
  • Page 14 JADE™ ECONOMIZER MODULE Table 5. Menu Structure . (Continued) Parameter Parameter Range and Default Menu Parameter Value Increment Notes Setpoint determines where the economizer will modulate the OA damper to SETPOINTS MAT SET 53ºF 38 to 70 ºF; maintain the mixed air temperature. increment by 1 Setpoint determines outdoor temperature when the mechanical cooling LOW T LOCK...
  • Page 15 JADE™ ECONOMIZER MODULE Table 5. Menu Structure . (Continued) Parameter Parameter Range and Default Menu Parameter Value Increment Notes Display order = MM/DD/YY SYSTEM INSTALL 01/01/11 Setting order = DD, MM, then YY. SETUP Sets economizer controller in degrees Fahrenheit or Celsius. UNITS DEG ºF ºF or ºC...
  • Page 16 JADE™ ECONOMIZER MODULE Table 5. Menu Structure . (Continued) Parameter Parameter Range and Default Menu Parameter Value Increment Notes Temp to activate Freeze Protection (close damper and alarm if temp falls ADVANCED MA LO SET 45ºF 35 to 55 ºF; below setup value) SETUP increment by 1º...
  • Page 17: Setup And Configuration

    Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu. When used with Honeywell communicating actuator the damper out is reported in XX.X% open versus XX.X Vd. After 10 minutes without a command or mode change, the controller will change to normal operation.
  • Page 18 JADE™ ECONOMIZER MODULE ECONOMIXING DUAL ENTHALPY AVAILABLE HIGH LIMIT NOT AVAILABLE SINGLE ENTHALPY P2 (T,RH) (T,RH) TEMPERATURE M32286A Fig. 16. Single Enthalpy curve and boundaries. Table 6. Single Enthalpy and Dual Enthalpy High Limit Curves. Point P1 Point P2 Enthalpy Temp.
  • Page 19 JADE™ ECONOMIZER MODULE Table 7. Setup and Setpoint Menus. Parameter Default Parameter Menu Parameter Value Range and Increment Notes Display order = MM/DD/YY SYSTEM SETUP INSTALL 01/01/11 Setting order = DD, MM, then YY. Sets economizer controller in degrees Fahrenheit or UNITS DEG ºF ºF or ºC...
  • Page 20 JADE™ ECONOMIZER MODULE Table 7. Setup and Setpoint Menus. (Continued) Parameter Default Parameter Menu Parameter Value Range and Increment Notes Temp to activate Freeze Protection (close damper ADVANCED SETUP MA LO SET 45ºF 35 to 55 ºF; and alarm if temp falls below setup value) increment by 1º...
  • Page 21 JADE™ ECONOMIZER MODULE Table 7. Setup and Setpoint Menus. (Continued) Parameter Default Parameter Menu Parameter Value Range and Increment Notes Setpoint determines where the economizer will SETPOINTS MAT SET 53ºF 38 to 70 ºF; modulate the OA damper to maintain the mixed air increment by 1 temperature.
  • Page 22: Checkout

    Initial Menu Display For checkout, review the Status of each configured parameter On initial start up, Honeywell displays on the first line and and perform the Checkout tests. Economizer W7220 on the second line. After a brief pause, NOTE: See “Interface Overview” on page 12. for...
  • Page 23 W (HEAT IN) ON/OFF n/a = not applicable *1 When used with Honeywell communicating actuator the damper out is in XX.X% versus XX.X Vd. Checkout Tests Table 9. Checkout Menu. Use the Checkout menu (Table 9) to test the damper operation...
  • Page 24: Troubleshooting

    All settings are stored in non-volatile flash memory. Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North ® U.S. Registered Trademark Golden Valley, MN 55422 © 2012 Honeywell International Inc. 63-2700—05 M.S. Rev. 02-12 customer.honeywell.com Printed in United States...

Table of Contents