hit counter script
Download Print this page

Advertisement

Quick Links

FDCI183 Transponder
Product Manual
Characteristic
Application
From a functional perspective, we distinguish between the primary side and the secondary side of the transponder.
The primary side is the connection to the FD18-BUS. The secondary side is the connection to the collective
detection line.
Compatible detector list
Type
HI520/OP520
DO1101A-EX/DT1101A-EX
DF1101-EX
FDL241-9-CN/DF1191/DF1192
FDO181C/FDT181C
Communication
The communication with the control panel is performed via the FD18-BUS. The configuration is performed on
the control unit or commissioning tool.
Power Supply
Power supply of the primary side (FD18-BUS) is always ensured via the detector line FD18-BUS. Power
supply of the secondary side must always be ensured via an external 24VDC supply unit. The primary and
the secondary side are galvanically isolated.
Operating modes
The transponder can be in either of the following operating modes:
Fulfill Chinese Standard of GB16806-2006 "Interlocking Control System";
1 monitored inputs as collective detector connection;
LED display of alarm and fault status;
External 24VDC power supply;
Microprocessor-controlled signal evaluation;
Earth fault monitoring;
With the Zener diode barrier, it is also possible to connect intrinsically safe detectors;
Applicable in dry, dusty and humid areas in protection box.
Max. detector per line
32
25
5
1
32

Advertisement

loading

Summary of Contents for Siemens FDCI183

  • Page 1 FDCI183 Transponder Product Manual Characteristic Fulfill Chinese Standard of GB16806-2006 “Interlocking Control System”; 1 monitored inputs as collective detector connection; LED display of alarm and fault status; External 24VDC power supply; Microprocessor-controlled signal evaluation; Earth fault monitoring; With the Zener diode barrier, it is also possible to connect intrinsically safe detectors;...
  • Page 2 Normal operation Localization Normal operation The transponder is in the intended operating mode. Inputs are monitored and assessed. Localization For an unambiguous identification, the transponder can be set in localization mode from the control unit. The localization mode is indicated by the LED. Earth fault monitoring The earth fault monitoring function can be switched off with a jumper.
  • Page 3 Fig. 3 Fig. 4 Fig. 2 Fig. 5 Fig. 6 Fig. 7 FDCI183 Fig. 9 Detector line with safety barrier Fig. 8 Detection line connection t he earth fault monitoring must be switched off) Preparation Procedure with installation in the housing 1.
  • Page 4 100211529 End of Line Transient Diode 20V 1.5KE20CA(EOL) A5Q00015836 100967645 Beijing Siemens Cerberus Electronics Limited No.1,Fengzhidonglu, Xibeiwang, HaiDian District, © Data and design subject to change without notice. Beijing, 100094, China Tel: +10 6476 8806 Fax: +10 6476 8899 Doc No.