FILE NO. SVM-15008 SERVICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit <High Wall, Heat Pump Type> <Heat Pump Type> RAS-13 S 3KV-E RAS-13 S 3AV-E R410A January, 2015...
FILE NO. SVM-15008 1. SAFETY PRECAUTIONS For general public use Power supply cord of parts of appliance for outdoor use shall be at least polychloroprene sheathed flexible cord (design H07RN-F) or cord designation 60245 IEC66 (1.5 mm or more). (Shall be installed in accordance with national wiring regulations.) CAUTION New Refrigerant Air Conditioner Installation...
Page 4
• Appliance shall be installed in accordance with national wiring regulations. If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately. • Do not use any refrigerant different from the one specified for complement or replacement.
FILE NO. SVM-15008 3. REFRIGERANT R410A This air conditioner adopts the new refrigerant HFC 6. When an air conditioning system charged with a (R410A) which does not damage the ozone layer. large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, The working pressure of the new refrigerant R410A even when refrigerant leaks, its concentration...
Page 8
FILE NO. SVM-15008 Table 3-2-1 Thicknesses of annealed copper pipes Thickness (mm) Nominal diameter Outer diameter (mm) R410A 6.35 0.80 0.80 9.52 0.80 0.80 12.70 0.80 0.80 15.88 1.00 1.00 2. Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm.
Page 9
FILE NO. SVM-15008 d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. ØD By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conven- tional flare tool. Flare processing dimensions differ according to the type of flare tool.
Page 11
FILE NO. SVM-15008 3-3. Tools 3-3-1. Required Tools The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
Page 12
FILE NO. SVM-15008 3-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Page 13
FILE NO. SVM-15008 1. Be sure to make setting so that liquid can be charged. 2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
Page 14
FILE NO. SVM-15008 2. Characteristics required for flux 3-5-3. Brazing • Activated temperature of flux coincides with the As brazing work requires sophisticated techniques, brazing temperature. experiences based upon a theoretical knowledge, it must be performed by a person qualified. •...
FILE NO. SVM-15008 6. SPECIFICATIONS OF ELECTRICAL PARTS 6-1. Indoor Unit Parts name Type Specifications Fan motor (for indoor) RPG-240-25A AC220~240V, 25W Room temp. sensor (TA-sensor) ( - ) 10kΩ at 25°C Heat exchanger temp. sensor (TC-sensor) ( - ) 10kΩ...
FILE NO. SVM-15008 8. CONTROL BLOCK DIAGRAM 8-1. Indoor Unit Indoor Unit Control Unit M.C.U. Louver Functions Motor Heat Exchanger Sensor (Tc) • Cold draft preventing Function Room Temperature Sensor (Ta) Louver Motor • 3-minute Delay at Restart for Compressor Drive Control Infrared Rays Signal Receiver •...
Page 22
FILE N. SVM-15008 8-2. Outdoor Unit (Inverter Assembly) – 21 –...
FILE NO. SVM-15008 9. OPERATION DESCRIPTION 9-1. Outline of Air Conditioner Control • Detection of inverter input current and current release operation This air conditioner is a capacity-variable type air • Over-current detection and prevention operation conditioner, which uses AC or DC motor for the indoor to IGBT module (Compressor stop function) for motor and the outdoor fan motor.
Page 24
FILE NO. SVM-15008 9-2. Operation Description 1. Basic operation ......................24 1. Operation control ....................24 2. Cooling/Heating operation ..................25 3. AUTO operation ..................... 25 4. DRY operation ......................25 2. Indoor fan motor control ..................... 26 3. Outdoor fan motor control ................... 28 4.
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 1. Basic 1. Operation control operation Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are controlled. 1) The operation conditions are selected by the remote controller as shown in the below. 2) A signal is sent by ON button of the remote controller.
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 1. Basic 2. Cooling/Heating operation operation The operations are performed in the following parts by controls according to cooling/heating conditions. 1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal starts being transferred form the indoor controller to the outdoor unit.
Page 27
*5 : Fan speed = (M + –L) x 1/4 + L +1.0 +0.5 (Linear approximation L(W6) from M+ and L) (Table 1) Indoor fan air flow rate RAS-13S3KV-E Mode Fan speed Cooling Heating level Fan speed Air flow rate...
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 2. Indoor fan <In heating operation> 1) When setting the fan speed to L, motor control L+, M, M+ or H on the remote controller, the operation is per- formed with the constant speed HEAT ON shown in Fig.
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 3. Outdoor fan The blowing air volume at the outdoor unit side is controlled. 1) The operation command sent motor control from the remote controller is Receiving the operation command from the controller of processed by the indoor unit indoor unit, the controller of outdoor unit controls fan speed.
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 4. Capacity The cooling or heating capacity depending on the load is 1) The difference between set control adjusted. temperature on remote controller (Ts) and room temperature (Ta) According to difference between the setup value of tempera- is calculated.
Page 31
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 6. Release protective <In cooling/dry operation> 1) When temperature of the indoor control by tempera- heat exchanger drops below 5°C, (Prevent-freezing control for indoor heat exchanger) ture of indoor heat the compressor speed is In cooling/dry operation, the sensor of indoor heat exchanger...
Page 32
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 7. Defrost control (This function removes frost adhered to the outdoor The necessity of defrost operation is (Only in heating heat exchanger.) detected by the outdoor heat exchanger operation) temperature.
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 8. Louver control This function controls the air direction of the indoor unit. • The position is automatically controlled according to the operation 1) Louver mode (COOL/HEAT). position • The set louver position is stored in memory by the microcomputer, and the louver returns to the stored position when the next operation is performed.
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description When pressing [ECO] button on the remote controller, a 9. ECO <Cooling operation> Economic operation is performed. operation 1) The control target temperature <Cooling operation> increase 0.5ºC per hour up to 2ºC This function operates the air conditioner with the difference starting from the set temperature between the set and the room temperature as shown in the...
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 10. Temporary Pressing [RESET] button starts the temporary opera- 1) When pressing [RESET] button, the operation tion of [AUTO] operation. When keeping [RESET] temporary [AUTO] operation starts. button pressed for 10 seconds or more, the temporary 2) When keeping [RESET] button pressed [COOL] operation is performed.
Page 36
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 12. Pulse This function controls throttle amount of the 1) When starting the operation, move the Modulating refrigerant in the refrigerating cycle. valve once until it fits to the stopper. valve (P.M.V.) (Initialize) According to operating status of the air conditioner,...
Page 37
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 13. Self-Cleaning 1. Purpose The Self-Cleaning operation is to minimize the function growth of mold, bacteria etc. by running the fan and drying so as to keep the inside of the air conditioner clean. Unit now performing cooling or dry operation Self-Cleaning operation When the cooling or dry operation shuts...
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 13. Self-Cleaning • Self-Cleaning diagram function Operation display FCU fan rpm is depend on presetting. (500RPM) FCU louver OPEN OPEN (12.7º) CLOSE ON or OFF ON or OFF Timer display depend on presetting of timer function.
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description Quiet mode is the system which, control the 15. QUIET mode When the [QUIET] button is pressed, the fan of the revolving speed of indoor fan to work indoor unit will be restricted the revolving speed at −...
FILE NO. SVM-15008 Item Operation flow and applicable data, etc. Description 18. Hi-POWER ([Hi-POWER] button on the remote controller Mode is pressed) When [Hi-POWER] button is pressed while the indoor unit is in Auto, Cooling or Heating operation, Hi- POWER mark is indicated on the display of the remote controller and the unit operates as follows.
FILE NO. SVM-15008 9-3. Auto Restart Function This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of a power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored.
FILE NO. SVM-15008 9-3-2. How to Cancel the Auto Restart Function To cancel auto restart function, proceed as follows : Repeat the setting procedure : the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote controller after the main power supply is turned off. •...
The coutomised settings control temperature air flow strength, air flow direction and other settings to provide you alternate contact with "ONE-TOUCH" OF THE BUTTON. If you prefer other settings you can select from the many other operation functions of your Toshiba unit Press : Start the operaton.
Page 44
FILE NO. SVM-15008 4. DRY OPERATION (COOLING ONLY) For dehumidification, a moderate cooling performance is controlled automatically. 1. Press : Select Dry MODE 2. Press : Set the desired temperature. 5. Hi-POWER OPERATION To automatically control room temperature and airflow for faster cooling operation (except in DRY and FAN ONLY mode).
Page 45
FILE NO. SVM-15008 9. PRESET OPERATION Set your preferred operation for future use. The setting will be memorized by the unit for future operation (except air flow direction). 1. Select your preferred operation. 2. Press and hold for 3 seconds to memorize the setting. The mark displays.
Page 46
FILE NO. SVM-15008 9-4-3. Names and Functions of Indications on Remote Controller [Display] All indications, except for the clock time indicator, are displayed by pushing the button. Transmission mark (PRESET) indicator This transmission mark indicates when the remote Flashes for 3 seconds when the PRESET button is controller transmits signals to the indoor unit.
FILE NO. SVM-15008 10. INSTALLATION PROCEDURE 10-1. Installation Diagram of Indoor and Outdoor Units For the rear left and left piping Hook Installation plate Wall Insert the cushion between the indoor unit and wall, and tilt the indoor unit for better operation.
Page 48
FILE NO. SVM-15008 10-2. Installation 10-2-1. Optional installation parts Part Parts name Q'ty Code Refrigerant piping Liquid side : ∅6.35 mm each Gas side ∅ 9.52 mm Pipe insulating material (polyethylene foam, 6 mm thick) Putty, PVC tapes each <Fixing bolt arrangement of outdoor unit> 108 mm 125 mm 28 mm...
Page 49
Part Part name (Q’ty) Part name (Q’ty) Part name (Q’ty) Flat head wood screw Toshiba New IAQ filter (L) x 1 ∅3.1 x 25 s x 1 Installation plate x 1 Drain nipple* x 1 Battery-cover x 1 Wireless remote control x 1 Cap water proof* x 2 Mounting screw ∅4 x 25 s x 6...
Page 50
FILE NO. SVM-15008 10-2-3. Installation/Servicing Tools Changes in the product and components In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch) •...
Page 51
FILE NO. SVM-15008 10-3. Indoor Unit 10-3-2. Cutting a hole and mounting installation plate 10-3-1. Installation place <Cutting a hole> A place which provides the spaces around the indoor unit as shown in the diagram in part 8-2. When installing the refrigerant pipes from the rear. A place where there is no obstacle near the air inlet and outlet.
Page 52
FILE NO. SVM-15008 <When the installation plate is directly mounted on 10-3-3. Wiring connection the wall> <How to connect the connecting cable> 1. Securely fit the installation plate onto the wall by Wiring of the connecting cable can be carried out screwing it in the upper and lower parts to hook up the indoor unit.
Page 53
FILE NO. SVM-15008 <How to connect remote controller for wire operation> 70 mm * Wire size 28-22AWG or 0.08-0.32 mm Outer diameter not over 4.7 mm, Indoor unit control wire length 30 m. or less. 5 mm Notch for wire out Control wire Remote controller Fig.
Page 54
FILE NO. SVM-15008 Control wire Rear right Control wire Screw (∅3.1 x 16L) for Rear left Hole for hang hang remote controller remote controller Bottom left Remote controller Left Wall Bottom right Remote controller Right Screw (∅3.1 x 25L) for 1.
Page 55
FILE NO. SVM-15008 <Left-hand connection with piping> How to fix the drains cap 1) Insert hexagonal wrench (4 mm) in a center Bend the connecting pipe so that it is laid within 43 mm head. above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall.
Page 56
FILE NO. SVM-15008 10-3-5. Indoor unit fixing 10-3-6. Drainage 1. Pass the pipe through the hole in the wall, and hook 1. Run the drain hose sloped downwards. the indoor unit on the installation plate at the upper hooks. NOTE 2.
Page 57
FILE NO. SVM-15008 10-4. Outdoor Unit 10-4-1. Installation place • A place which provides the spaces around the Strong wind outdoor unit as shown in the left diagram. • A place which can bear the weight of the outdoor unit and does not allow an increase in noise level Fig.
Page 58
FILE NO. SVM-15008 <Using a vacuum pump> CAUTION Be sure to use a vacuum pump with counter-flow Do not apply excess torque. prevention function so that inside oil of the pump does Otherwise, the nut may crack depending on the not flow backward into pipes of the air conditioner conditions.
Page 59
FILE NO. SVM-15008 <Packed valve handling precautions> 10-4-5. Wiring connection • Open the valve stem all the way out, but do not try 1. Remove the valve cover from the outdoor unit. to open it beyond the stopper. 2. Connect power cord to the terminal block then connect the connecting cable to the Pipe size of Packed Valve Size of Hexagon wrench...
Page 60
FILE NO. SVM-15008 10-5. Others NOTE : 1. Repeat above step to reset Remote Control to be A. 10-5-1. Gas leak test 2. Remote Control A has not "A" display. 3. Default setting of Remote Control from Check places for factory is A.
FILE NO. SVM-15008 11. HOW TO DIAGNOSE THE TROUBLE The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according to the trouble diagnosis procedure as described below. (Refer to the check points in servicing written on the wiring diagrams attached to the indoor/outdoor units.) Table 11-1 Troubleshooting Procedure...
Page 62
FILE NO. SVM-15008 CAUTION A high voltage (equivalent to the supply voltage) is also energized to ground through the sensors, PMV and other low-voltage circuits. The sensor leads and other wires are covered with insulated tubes for protection. Nevertheless, care must be taken to ensure that these wires are not pinched.
Page 63
FILE NO. SVM-15008 11-1. First Confirmation 11-1-1. Confirmation of Power Supply Confirm that the power breaker operates (ON) normally. 11-1-2. Confirmation of Power Voltage Confirm that power voltage is AC 220–230–240 ± 10%. If power voltage is not in this range, the unit may not operate normally. 11-1-3.
Page 64
FILE NO. SVM-15008 11-2. Primary Judgment To diagnose the troubles, use the following methods. 1) Judgment by flashing LED of indoor unit 2) Self-diagnosis by service check remote controller 3) Judgment of trouble by every symptom Firstly use the method 1) for diagnosis. Then, use the method 2) or 3) to diagnose the details of troubles. 11-3.
Page 65
FILE NO. SVM-15008 11-4. Self-Diagnosis by Remote Controller (Check Code) 1. If the lamps are indicated as shown B to E in Table 11-3-1, execute the self-diagnosis by the remote controller. 2. When the remote controller is set to the service mode, the indoor controller diagnoses the operation condi- tion and indicates the information of the self-diagnosis on the display of the remote controller with the check codes.
Page 66
FILE NO. SVM-15008 11-4-2 Caution at Servicing 1. After using the service mode of remote controller finished, press the [ ] button to reset the remote controller to normal function. 2. After finished the diagnosis by the remote controller, turn OFF power supply and turn its ON again to reset the air conditioner to normal operation.
Page 67
FILE NO. SVM-15008 Block distinction Operation of diagnosis function Action and Judgment Check Check Display flashing Block Cause of operation conditioner code code error status Serial signal 1) Defective wiring of the Indoor unit Flashes when 1) to 3) The outdoor unit never and connecting connecting cable or operates...
Page 68
FILE NO. SVM-15008 Block distinction Operation of diagnosis function Action and Judgment Check Check Display flashing Block Cause of operation conditioner code code error status Outdoor P.C. Current on inverter circuit All OFF Flashes after 1. Remove connecting lead wire of the board is over limit in short time.
Page 69
FILE NO. SVM-15008 Block distinction Operation of diagnosis function Action and Judgment Check Check Display flashing Block Cause of operation conditioner code code error status Compressor drive output error. All OFF Flashes after 1. Check installation conditions such as (Relation of voltage, current error is detected packed valve opening, refrigerant 8 times*.
Page 70
FILE NO. SVM-15008 Block distinction Operation of diagnosis function Action and Judgment Check Check Display Block Cause of operation conditioner code code flashing error status Compressor does not rotate. All OFF Flashes after 1. Remove connecting lead wire of the Because of missed wiring, error is detected compressor, and operate again.
Page 71
FILE NO. SVM-15008 11-5. Judgment of Trouble by Every Symptom 11-5-1. Indoor Unit (Including Remote Controller) (1) Power is not turned on (Does not operate entirely) <Primary check> 1. Is the supply voltage normal? 2. Is the normal voltage provided to the outdoor unit? 3.
Page 72
FILE NO. SVM-15008 (2) Power is not turned on though Indoor P.C. board is replaced <Confirmation procedure> Turn on power supply. Is wired correctly to white and black Correct wiring. Does operation lamp flash? lead wires of terminal board? To item of “Power is not turned on”.
Page 73
FILE NO. SVM-15008 (3) Only the indoor motor fan does not operate <Primary check> 1. Is it possible to detect the power supply voltage (AC220–240V) between on the terminal block? 2. Does the indoor fan motor operate in cooling operation? (In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is turned on, to prevent a cold air from blowing in.) Shut off the...
Page 74
FILE NO. SVM-15008 (For AC fan motor) <Inspection procedure> 1. Remove the front panel. (Remove 2 screws.) 2. Remove the cover of the fan motor lead wires. 3. Check AC voltage with CN10 connector while the fan motor is rotating. NOTE : •...
Page 75
FILE NO. SVM-15008 (4) Troubleshooting for remote controller <Primary check> Check that A or B selected on the main unit is matched with A or B selected on the remote controller. There is no beep from the indoor unit Push the [ ] button.
Page 76
FILE NO. SVM-15008 11-5-2. Wiring Failure (Interconnecting and Serial Signal Wire) (1) Outdoor unit does not operate 1) Is the voltage between of the indoor terminal block varied? Confirm that transmission from indoor unit to outdoor unit is correctly performed based upon the follow- ing diagram.
Page 77
FILE NO. SVM-15008 11-6. How to Check Simple the Main Parts <Check procedure> Gas leakage, Discharge temp. error, disconnection of TS/TC gas leakage sensors (Check code 02, 1C) (Check code 03, 1E) Valve drive check Is coil of the pulse motor valve Set it correctly.
Page 78
FILE NO. SVM-15008 11-7. How to Diagnose Trouble in Outdoor Unit Check Power Supply (Voltage Rate ±10%) Turn OFF power supply. Remove connector of compressor. • Connect discharge Check 25A resistance (approx. 100Ω, fuse (F01) 40W) or soldering iron (plug) between +, – terminals of the electro- lytic capacitor (500µF or 760µF)
Page 79
FILE NO. SVM-15008 Does outdoor fan operate normally? Turn OFF power supply. Does compresser operate normally? Remove outdoor fan connector. Check winding resistance by ohmmeter are correct? Compressor Check rotor locking by rotate is normal with hand. Can it rotate? Turn OFF power supply.
Page 80
FILE NO. SVM-15008 11-8. How to Check Simply the Main Parts 11-8-1. How to Check the P.C. Board (Indoor Unit) (1) Operating precautions 1) When removing the front panel or the P .C. board, be sure to shut off the power supply breaker. 2) When removing the P .C.
Page 81
FILE NO. SVM-15008 (3) Check procedures Table 11-8-1 Procedure Check points Causes Turn off the power supply breaker Check whether or not the fuse (F01) Impulse voltage was applied or the and remove the P.C. board is blown. indoor fan motor short-circuited. assembly from electronic parts base.
Page 82
FILE NO. SVM-15008 11-8-2. P .C . Board Layout [1] Sensor characteristic table TD : Discharge temp. sensor TA : Room temp. sensor TC : Heat exchanger temp. sensor TO : Outdoor temp. sensor TS : Suction temp. sensor TA, TC, TO, TS, TE : Outdoor heat exchanger temp sensor Temperature (˚C)
Page 83
FILE NO. SVM-15008 11-8-3. Indoor Unit (Other Parts) Part name Checking procedure Room temp. (TA) sensor Disconnect the connector and measure the resistance value with tester. Heat exchanger (TC) sensor (Normal temp.) Temperature 10°C 20°C 25°C 30°C 40°C Sensor TA, TC (kΩ) 20.7 12.6 10.0...
Page 84
FILE NO. SVM-15008 11-8-5. Checking Method for Each Part Part name Checking procedure Electrolytic capacitor 1. Turn OFF the power supply breaker. (For raising pressure, smoothing) 2. Discharge all three capacitors completely. 3. Check that safety valve at the bottom of capacitor is not broken. 4.
Page 85
FILE NO. SVM-15008 11-9. How to Simply Judge Whether Outdoor Fan Motor is Good or Bad 1. Symptom • Outdoor fan motor does not rotate. • Outdoor fan motor stops within several tens seconds though it started rotating. • Outdoor fan motor rotates or does not rotate according to the position where the fan stopped, etc. Remote controller check code “02 : Outdoor block, 1A : Outdoor fan drive system error”...
Page 86
FILE NO. SVM-15008 11-10. How to setting the CLEAN OPERATION cancel • Self-Cleaning diagram 11-10-1. Self-Cleaning function Operation display FCU fan rpm is depend on presetting. (500RPM) FCU louver OPEN CLOSE OPEN (12.7º) ON or OFF ON or OFF Timer display depend on presetting of timer function.
FILE NO. SVM-15008 12. HOW TO REPLACE THE MAIN PARTS WARNING • Since high voltages pass through the electrical parts, turn off the power without fail before proceeding with the repairs. Electric shocks may occur if the power plug is not disconnected. •...
Page 88
FILE NO. SVM-15008 Part name Procedures Remarks Front panel 4) Press "PUSH" part under the front panel and remove hooks of the front panel from Installation plate the installation plate. Front panel Press 5) Remove the front panel fixing screws. (2 pcs.) 6) Take off three hooks of panel from rear side.
Page 89
FILE NO. SVM-15008 Part name Procedures Remarks Electric parts 1) Follow the procedure up to 3) in above. box assembly 2) Remove screw of earth lead attached to the end plate of the evaporator. 3) Remove the lead wire cover, and remove connector for the fan motor and connec- tor for the louver motor from the electric parts box assembly.
Page 90
FILE NO. SVM-15008 Part name Procedures Remarks Horizontal louver 1) Remove shaft of the horizontal louver from the back body. (First remove the left shaft, and then remove other shafts while sliding the horizontal louver leftward.) Evaporator 1) Follow to the procedure in the item (Heat exchanger) 2) Remove the pipe holder from the rear side of the main unit.
Page 91
FILE NO. SVM-15008 Part name Procedures Remarks „ Bearing 1) Follow to the procedure in the item 2) Remove the two screws used to secure the bearing base. Two screws 3) Remove the bearing base. <Caution at assembling> • If the bearing is out from the housing, push it into the specified position and then incorporate it in the main body.
Page 92
FILE NO. SVM-15008 Part name Procedures Remarks … Fan motor 1) Follow to the procedure till item 2) Loosen the set screw of the cross flow fan. 3) Remove two fixing screws of the motor cover and them remove the motor cover. 4) Remove two more fixing screws of the motor band and remove the motor band.
Page 93
FILE NO. SVM-15008 Part name Procedures Remarks Cross flow fan <Caution at reassembling> Fan motor D shaft Double point set screw 1) To incorporate the fan motor incorporate the motor into the position in the following figure, and then install the fan motor. •...
Page 94
FILE NO. SVM-15008 12-2. Microcomputer Part name Procedure Remarks Common procedure 1) Turn the power supply off to stop the Replace terminal block, operation of air-conditioner. microcomputer ass’y and the P .C. board ass’y. 2) Remove the front panel. •...
Page 95
FILE NO. SVM-15008 12-3. Outdoor Unit Part name Procedure Remarks Common 1. Detachment procedure NOTE Upper cabinet Wear gloves for this job. Otherwise, you may injure your hands on the parts, etc. Waterproof cover 1) Stop operation of the air conditioner, and turn off the main switch of the breaker for air conditioner.
Page 96
FILE NO. SVM-15008 Part name Procedure Remarks Front cabinet 1. Detachment 1) Perform step 1 in 2) Remove the fixing screws (ST1TØ4 × 10L 2 pcs.) used to secure the front cabinet and inverter cover, the screws (ST1TØ4 ×...
Page 97
FILE NO. SVM-15008 Part name Procedure Remarks Inverter 1) Perform work of item 1 in Inverter cover assembly 2) Remove screw (ST1TØ4 × 10L 2 pcs.) of the upper part of the front cabinet. P.C. board (Soldered surface) •...
Page 98
FILE NO. SVM-15008 Part name Procedure Remarks Control board 1. Disconnect the leads and connectors connected to assembly the other parts from the control board assembly. 1) Leads • 3 leads (black, white, orange) connected to terminal block. • Lead connected to compressor : Disconnect the connector (3P).
Page 99
FILE NO. SVM-15008 Part name Procedure Remarks Side cabinet 1. Side cabinet (right) 1) Perform step 1 in and all the steps in 2) Remove the fixing screw (ST1TØ4 × 10L 4 pcs.) used for securing the side cabinet to the bottom plate and valve fixing panel.
Page 100
FILE NO. SVM-15008 Part name Procedure Remarks Compressor 1) Perform work of item 1 of 2) Extract refrigerant gas. 3) Remove the partition board. (ST1TØ4 × 10L 3 pcs.) 4) Remove the sound-insulation material. 5) Remove terminal cover of the compressor, and disconnect lead wire of the compressor Partition...
Page 101
FILE NO. SVM-15008 Part name Procedure Remarks Electronic 1. Detachment expansion valve 1) Perform step 1 in , all the steps in coil and 1 in 2) Remove the coil by pull it upward. 2. Attachment 1) Insert a valve coil to value body by push it downward.
Page 102
FILE NO. SVM-15008 Part name Procedure Remarks TE sensor (outdoor heat exchanging temperature sensor) • Attachment Arrow D Install the sensor onto the straight pipe part of the condenser output pipe. Detail B Detail C Detail A • Shown in the above figure is the model 16k.
Page 103
FILE NO. SVM-15008 Part name Procedure Remarks Replacement of 1) Cut the sensor 100 mm longer than old temperature sensor one. Cutting here Thermal for servicing only Connector sensor part 2) Cut the protective tube after pulling out it (200 mm). Common service 3) Move the protective tube toward the Cutting here...
FILE NO. SVM-15008 13. EXPLODED VIEWS AND PARTS LIST 13-1. Indoor Unit (Part-E) Location Part Location Part Description Description 43T69319 TEMPERATURE SENSOR 43T6V540 PC BOARD 43T69320 TEMPERATURE SENSOR 43T60378 TERMINAL 43T62340 CORD-CLAMP 43T60417 TERMINAL 43T6V316 PC BOARD ASSY;WRS-LED – 103 –...
Page 105
FILE NO. SVM-15008 13-2. Indoor Unit Electric Parts Assembly Location Part Location Part Description Description 43T21442 STEPPING-MOTOR 43T39327 BEARING BASE 43T21433 FAN-MOTOR 43T39343 MOTOR BAND (LEFT) 43T22312 BEARING ASSY, MOLD 43T39329 MOTOR BAND (RIGHT) 43T70316 HOSE, DRAIN 43T09409 HORIZONTAL LOUVER 43T20325 CROSS FLOW FAN ASSEMBLY 43T79313...
Page 106
FILE NO. SVM-15008 13-3. Outdoor Unit Location Part Location Part Description Description 43T00468 FRONT CABINET 43T58309 REACTOR 43T00459 LEFT CABINET 43T20319 PROPELLER FAN 43T42327 BASE PLATE ASSEMBLY 43T21375 FAN MOTOR 43T00452 UPPER CABINET 43T47001 NUT FLANGE 43T19329 FAN GUARD 43T97001 43T00562 PACKED VALVE COVER ASSEMBLY 43T49335 RUBBER CUSHION COIL;V-4WAY 43T41476 COMPRESSOR 43T46376 COIL-4WAY 43T43511 CONDENSER ASSEMBLY 43T63327 43T46358 VALVE;PACKED 6.35 DIA...
Page 107
FILE NO. SVM-15008 13-4. P.C. Board Layout Ø TE Sensor ( (Ø6) TS Sensor (Ø6) TO Sensor (Ø4) TD Sensor Location Part Location Part Description Description 43T62351 HEATSINK 43T50334 TEMPERATURE SENSOR 43T6V573 PC BOARD 43T50304 SENSOR;HEAT EXCHANGER 43T60392 TERMINAL‐5P 43T62313 BASE‐PLATE‐PC 43T60326 FUSE –...