Use
For zone valves VVP.., VXP.., VMP..: compatible with SSB161.05UT
Typically in chilled ceiling, VAV and fan coil unit applications
Max.10 units of SSB161.05UT can operate in parallel, provided the controller output
suffices.

Technical design

When the actuator is driven by DC 0...10 V positioning signal, it produces a stroke, which is
transmitted to the valve stem.
DC 0...10 V positioning signal
The valve opens / closes in proportion to the
positioning signal at Y.
At DC 0 V, actuator stem is retracted, the normally
closed valve is fully closed.
When there is no operating voltage, the actuator
maintains its current position.
Y = Positioning signal Y [V]
H = Percentage of calibrated valve stroke

LED indication

    Stroke movement: Stem retracting
   Stroke movement: Stem extending
* Hint: Error caused by mechanical jam or calibration failure. Calibration through resetting the
operating voltage required.

Type summary

Type
SSB161.05UT
Ordering
When ordering, specify both type and quantity.
2
Siemens
Smart Infrastructure
Status
Variants
Stem stays in position
Calibration
Error*
Manual operation
Stock
Operating
number
voltage
S55180-A148
AC/DC 24 V
LED indication patterns
SSB161.05UT
Flashing green in sequence: LED1-->LED2-->LED3 (500 ms each)
Flashing green in sequence: LED3-->LED2-->LED1 (500 ms each)
At H0 - H40: Constant green (LED3)
At H40 - H60: Constant green (LED2)
At H60 - H100: Constant green (LED1)
Flashing green (LED2): 100 ms on, 100 ms off
Constant red (LED2)
Flashing green/red alternatively (LED2): Green 500 ms, red 500 ms
Running
Running time
speed
5.5 mm
5 s/mm
27.5 s ± 25 %
Positioning
Actuator
signal
characteristic
DC 0...10 V
Linear