9410 series - User manual
4. Select Status and click Edit. The Incremental Energy Setup screen is displayed.
5. Select Enable to display parameters for configuration.
6. Select the parameter to configure.
7. Click OK to save your changes.
Conditional energy
Conditional energy allows you to define an accumulation period for real and reactive energy using
one of your meter's digital inputs.
You can use conditional energy to track four-quadrant accumulated energy during a specific
period. For example, you can track accumulated energy values during a particular process that is
controlled by a programmable logic controller (PLC).
Conditional energy is accumulated until it is reset. The conditional energy reset date and time
information is stored in the meter's event log.
Configuring conditional energy using ION Setup
You can enable and configure conditional energy settings using ION Setup.
When configuring your meter, the configuration interface may show all of the possible ports,
regardless of what is physically available on your meter.
One of your device's digital inputs must be connected and configured to define when conditional
energy is accumulated.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Energy Applications > Digital Input Based. Review the digital inputs assigned to
applications to help ensure there are no conflicting usages.
4. Select Conditional Energy and click Edit. The Conditional Energy Setup screen is
displayed.
5. Click Enabled to enable the conditional energy feature.
7EN05-0336-09
NOTE: Configuring any parameter resets the incremental energy values recorded by your
meter.
Parameter
Range
12:00 am to
Start time
11:59 pm
12:01 am to
End time
12:00 am
Interval
Configurable
duration
Description
The incremental energy first interval's start time. The
start time must be prior to the end time for energy
accumulation.
The end time for incremental energy.
The end time must be after the start time and be less
than or equal to 12AM (midnight).
The increment period for the incremental energy
duration.
Measurements
239