A
Trap receivers
B
SNMP agent (meter)
C
NMS with SNMP manager software and MIB file installed
NOTE: The NMS computer can also function as a trap receiver.

SNMP trapping

SNMP trapping allows your meter's agent to notify the NMS of events with an unsolicited SNMP
message (a "trap" of the meter's alarm event).
You can enter up to four IP addresses for SNMP trap notification for generic and enterprise-
specific traps. For enterprise traps, you must also define the number of events or maximum time
delay before SNMP traps are sent to the NMS.
SNMP trapping is only supported on SNMP v2.

Configuring SNMP using ION Setup

You can enable SNMP and configure SNMP trapping using ION Setup.
Download the ION MIB file from www.usa.siemens.com/pds.
To configure SNMP using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Communications > Advanced Ethernet > SNMP.