Page 1
Introduction Safety instructions Description SENTRON Operation planning Power Monitoring Device SENTRON PAC3200 Installation Connection Manual Startup Operator control Parameterize Maintenance and servicing Technical data Dimension drawings Appendix ESD Guidelines List of abbreviations 02/2008 A5E01168664B-04...
Page 2
Trademarks All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Modbus command parameters ....................61 3.9.12 MODBUS standard device identification with the function code 0x2B ........62 3.10 Slot for expansion modules......................63 3.11 Slots on the rear of the device .....................64 Operation planning ..........................65 Operation planning........................65 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 4
Operator input steps in the "MAIN MENU" ................119 8.2.3 Operator input steps in the "SETTINGS" menu ................ 120 8.2.4 Operator input steps in device settings display................. 121 8.2.5 Operator input steps in edit mode of the device settings............122 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 6
Table 3-27 MODBUS standard device identification parameters ..............62 Table 7-1 Connection of supply voltage ...................... 92 Table 7-2 Available connection types......................95 Table 8-1 Assignments of the function keys in the "MAIN MENU" ............114 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 7
Figure 3-11 Switching the protocol to MODBUS TCP..................39 Figure 3-12 Restart prompt ..........................39 Figure 3-13 SENTRON PAC3200 with screw terminals, rear .................63 Figure 3-14 Not available for use! Slot for memory card and battery compartment ........64 Figure 4-1 Mounting position.........................65 Figure 5-1 Installation step E - Strain relief for RJ45 connector ..............71...
Page 8
Display of the device settings ....................115 Figure 8-11 Edit mode of the device settings ....................116 Figure 8-12 Display the instantaneous, maximum/minimum or average value..........118 Figure 8-13 Reset the maximum or minimum value to the instantaneous value ......... 118 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 9
Effect of delay and hysteresis on upper and lower limit violations ..........146 Figure 9-22 "LIMIT LOGIC" device settings ....................147 Figure 9-23 "RESET" device setting ......................148 Figure 9-24 "PASSWORD PROTECTION" device setting................151 Figure 9-25 Switch off password protection ....................152 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 10
Frame dimensions with optional PAC PROFIBUS DP expansion module connected ..... 168 Figure 12-4 Side-by-side installation ......................169 Figure 12-5 Clearances, device with screw terminal (on the left), device with ring lug terminal (on the right) ............................170 Figure B-1 ESD work center ........................174 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Introduction Purpose of this document This present manual describes the SENTRON PAC3200 Power Monitoring Device. It is intended for the use of: ● Planners ● Plant operators ● Commissioning engineers ● Service and maintenance personnel Required basic knowledge A general knowledge of the field of electrical engineering is required to understand this manual.
This CD is supplied with the SENTRON PAC Power Monitoring Device. Technical support Contact for technical problems and other questions Help is available from: ● Service and support contacts in your region - worldwide ● Online service and support ● Technical support SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Contacts in your region can provide support worldwide. Table 1-1 Contacts in your region - worldwide Utility Address, number Internet: Service and support (http://www.siemens.com/automation/service&support) under "Contact us > Contacts" Support address: SIEMENS AG A&D CD MM1 Gleiwitzerstr. 555 D-90475 Nuremberg Online support This comprehensive information system is available day and night via the Internet.
Safety instructions Safety notes General safety notes DANGER Danger! High voltage Will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Safety-related symbols on the device Symbol Meaning Danger of electric shock. Caution! General hazard area. See also Applying the measuring current (Page 101) Applying the measuring voltage (Page 100) Applying the supply voltage (Page 92) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Description Features The SENTRON PAC3200 is a Power Monitoring Device for displaying all the relevant system parameters in low-voltage power distribution. It is capable of single-phase, two-phase or three-phase measurement and can be used in two-wire, three-wire, four-wire, TN, TT and IT systems.
The minimum and maximum values are indicated in addition to the mean values. ● With the multi-range power supply, the SENTRON PAC3200 can be connected direct to 690 V (max. 600 V for UL) industrial systems (measuring category III, pollution degree 2).
Page 21
OR operation. ● Phase sequence monitor. ● Status monitoring of the digital input. ● Monitoring the operating status of the SENTRON PAC3200. Displays and controls ● Large backlit graphics LC display for optimal readability even from a distance.
● Multifunctional digital output, programmable as energy pulse output for active energy or reactive energy pulses, for showing the direction of rotation, indicating the working hours of the SENTRON PAC3200, outputting limit violations, or as a switching output for remote control via PC.
CAUTION Local power supply conditions Before connecting the SENTRON PAC3200, you must ensure that the local power supply conditions agree with the specifications on the type plate. The short code of the connection type must be entered in the device settings at startup. You can find the instructions for parameterizing the connection type in the chapter "Starting up".
The current direction can be changed on the device or via the interface for all phases in common. This means it is not necessary to change the terminal connections of the current transformer in the event of connection errors. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Current a ✓ ✓ ✓ ✓ ✓ Current b ✓ ✓ Current c ✓ ✓ Average Current a, b, c ✓ ✓ Apparent Power a ✓ ✓ ✓ Apparent Power b ✓ Apparent Power c ✓ SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 27
✓ ✓ Voltage Unbalance ✓ Current Unbalance ✓ Universal Counter ✓ ✓ ✓ ✓ ✓ Working Hours Counter ✓ ✓ ✓ ✓ ✓ See also Features (Page 19) Parameterize (Page 127) Connection examples (Page 82) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Average Current Float Total Apparent Power Total VA Total VA Float Total Active Power Total W Total W Float Total Reactive Power Total var Total var Float Total Power Factor Total PF Total PF Float SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 29
Maximum Total Power Factor ▲Total PF ▲Total PF Float Minimum Voltage V ▼V ▼V Float L1-N Minimum Voltage V ▼V ▼V Float L2-N Minimum Voltage V ▼V ▼V Float L3-N Min. Voltage U ▼V ▼V Float L1-L2 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 30
Active Tariff Unsigned long Working Hours Counter Unsigned 0 ... 999999999 long Universal Counter Unsigned 0 ... 999999999 long Relevant Parameter Changes Unsigned Counter long Counter All Parameter Changes Unsigned long Counter Limit Violations SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
● Period length in minutes (adjustable between 1 and 60 mins, default 15 mins). ● Synchronization via bus or digital input. Energy counter SENTRON PAC3200 has energy counters for off-peak and on-peak energy types (total of 10 counters): ● Active energy import ●...
The working hours counter is used for monitoring the runtime of a connected load. (Counts only in the case of energy counting). Tariffs SENTRON PAC3200 supports 2 tariffs for the integrated energy counter (on-peak and off- peak). Control of tariff switching Switching between on-peak and on-peak can be controlled via the digital input or the communication interfaces.
Description 3.6 Limits Limits The SENTRON PAC3200 has a function for monitoring up to 6 limit values. These can be monitored for violation of the upper or lower limit. If a limit value is violated, specific actions can be triggered.
Monitored data source Limit value currently violated: Yes , No ● Outputting the limit violation to the digital output. ● Output of limit violations via the interface. ● Counting limit violations with the universal counter. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
● Energy pulse output, programmable for active energy pulses or reactive energy pulses ● Indication of the direction of rotation ● Displaying the operating status of the SENTRON PAC3200 ● Signaling limit violations ● Switching output for remote control via the interface Energy pulse output The digital output supplies a number of pulses proportional to the energy measured.
A maximum voltage of 24 V can be applied to the digital input. Higher voltages require an external voltage divider. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
If the setting data is not known, the (patch) cable must not be connected. The SENTRON PAC3200 has an RJ45 socket on the top. The device can be connected to Ethernet with an RJ45 connector, type T-568B.
Switching the protocol to MODBUS TCP Confirm your selection with F4 terminates the input and a message window prompts you to restart. Figure 3-12 Restart prompt carries out a restart - your settings become effective. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Power Factor a Float 0 ... 1 Power Factor b Float 0 ... 1 Power Factor c Float 0 ... 1 THD-R Voltage a Float 0 ... 100 THD-R Voltage b Float 0 ... 100 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 41
0 ... 100 Maximum THD-R Voltage c Float 0 ... 100 Maximum THD-R Current a Float 0 ... 100 Maximum THD-R Current b Float 0 ... 100 Maximum THD-R Current c Float 0 ... 100 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 42
Float Limit Violations* Unsigned long Byte 3 Bit 0 Limit 0 Device Diagnostics and Device Status* Unsigned long Byte 0 System status Status of the digital outputs* Unsigned long Byte 3 Bit 0 Output 0 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 43
Overflow 1.0e+12 The following tables contain further details of all measured variables indicated by at least one *. Abbr. in the "Access" column Abbreviation Read; read access Write; write access Read Write; read and write access SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Status Byte Bit mask Access Status of the Digital Outputs 32 bits 0x00000001 Status of the Digital Inputs 32 bits 0x00000001 See also Modbus measured variables with the function codes 0x03 and 0x04 (Page 40) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Maximum pulse rate exceeded No synchronization pulse Device Configuration menu is active Voltage overload Current overload Digital input 0 Digital output 0 See also Modbus measured variables with the function codes 0x03 and 0x04 (Page 40) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
50019 Zero point suppression float 0.0 ... 10.0 level (% rated current) 50021 Demand Period Min. unsigned long 1 ... 60 50023 Synchronization unsigned long No synchronization Synchronization via bus Synchronization via the digital input SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Number of Name Unit Format Value range Access registers 50105 ON/OFF unsigned long 50107 Hysteresis float 0.0 ... 20.0 50109 Delay unsigned long 0 ... 10 50111 Operation in Limit Logic unsigned long not used SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 54
30 = I_AVG 31 = VA_SUM 32 = P_SUM 33 = VAR_SUM 34 = PF_SUM 35 = V_BAL 36 = I_BAL 50115 Value float 50117 Modus ≥ / < unsigned long greater than less than SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 57
36 = I_BAL 50143 Value float 50145 Modus ≥ / < unsigned long greater than less than See also Modbus measured variables with the function codes 0x03 and 0x04 (Page 40) Connection examples (Page 82) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
• 0 ... 255 0 = Auto 0x04 • 0x10 • 1) Only for the PAC RS485 expansion module See also Modbus measured variables with the function codes 0x03 and 0x04 (Page 40) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
3A00 ... F6FF [64025] Specific Profile ID unsigned short [64026] Version of the I&M data 2 unsigned char 0.0 ... 255.255 [64027] Supported I&M data unsigned short 00 ... FF *) 42 stands for Siemens AG SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Version of the I&M data 2 unsigned char 0.0 ... 255.255 [64143] Supported I&M data unsigned short 00 ... FF *) 42 stands for Siemens AG See also Modbus measured variables with the function codes 0x03 and 0x04 (Page 40) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Name Format Access OID 0 Manufacturer String OID 1 Manufacturer device name String OID 2 Firmware version / bootloader version String See also Modbus measured variables with the function codes 0x03 and 0x04 (Page 40) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Slot for expansion modules Interface The SENTRON PAC3200 has one slot (MOD1) for installing optionally available expansion modules. Only communication modules such as the PAC PROFIBUS DP expansion module can be used. Please consult the current catalogs to find out which modules are available for the SENTRON PAC3200.
Slots on the rear of the device Slot on the rear of the device The SENTRON PAC3200 does not have a card reading device and does not require a battery. The insertion openings visible on the rear of the SENTRON PAC3200 cannot be used and are blanked off.
Operation planning Operation planning Mounting location The SENTRON PAC3200 device is intended for installation in permanently installed switching panels within closed rooms. Conductive panels and doors on control cabinets must be grounded. The doors of the control cabinet must be connected to the control cabinet using a grounding cable.
Page 66
Please ensure that the ventilation slots of the housing are not obstructed. The wiring, cable feed or other components must not obstruct ventilation. Environmental conditions Only use the SENTRON PAC3200 device where the environmental conditions permit its operation: Temperature range Operating temperature range •...
● Make sure that the contents of the package are complete. ● Check the device for external damage. Please contact your Siemens sales partner in the following cases: ● The packaging is damaged ● The contents of the package are not complete ●...
You can find information on the cutout dimensions, frame dimensions and clearances in the Chapter "Dimension drawings". See also Dimension drawings (Page 167) Installation steps Proceed as follows to install the SENTRON PAC3200 in the switching panel: Procedure 1. Cut a hole in the panel measuring 92.0 x 92.0 (if not already available).
Page 69
8. An optional expansion module can be connected. You can find the installation instructions in the operating instructions of the expansion module. Installation is complete. NOTICE Ensure that no tools or other potentially hazardous objects have been left at the installation location. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 70
Installation 5.4 Installation steps Installation steps Installation step A, device with screw terminals Installation step A, device with ring lug terminals Installation step B Installation step B, detail SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
6. Go to the outside of the switching panel and remove the device from the cutout. 7. Pack the device into the original box together with the operating instructions and the delivered components listed in the operating instructions. Deinstallation is complete. Figure 5-2 Deinstallation, releasing the locking hooks SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Before power is applied to the device for the first time, it must have been located in the operating area for at least two hours in order to reach temperature balance and avoid humidity and condensation. Condensation on the device is not permissible during operation. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 74
• Is trained in the proper care and use of protective equipment in accordance with established safety practices. • First aid training. See also Applying the measuring voltage (Page 100) Applying the measuring current (Page 101) Applying the supply voltage (Page 92) Safety notes (Page 17) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Dummy connection. Cannot be used as a slot! Supply voltage L+, N/- Measuring inputs voltage V Measuring inputs current IL1, IL2, IL3 Slot for optional expansion modules Optional expansion module, not included in scope of supply Ethernet port, RJ45 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Dummy connection. Cannot be used as a slot! Supply voltage L+, N/- Measuring inputs voltage V Measuring inputs current IL1, IL2, IL3 Slot for optional expansion modules Optional expansion module, not included in scope of supply Ethernet port, RJ45 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Terminal Function ̇ ̇ ̇ k Phase current I , input Phase current I , output ̇ k Phase current I , input Phase current I , output ̇ k Phase current I , input SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Terminal designation - device with ring lug terminals Figure 6-4 Labeling of the ring lug terminals Terminal Function ̇ ̇ ̇ k Phase current I , input Phase current I , output ̇ k Phase current I , input SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Terminal block: digital input and output, reference potential (13) Reference potential terminal The connection "reference potential" discharges interference affecting the digital input and output and the RJ45 connector. Connect the reference potential to the equipotential bonding strip in the control cabinet. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 80
• SENTRON PAC3200 with multi-range power supply 0.6 A, Type C. • SENTRON PAC3200 with extra-low voltage power supply 1.0 A, Type C. If a fusible link is used, a suitable approved (UL / IEC) fuse holder has to be used. In addition, a suitable isolating device shall be connected upstream in order to permit disconnection of the device from the power supply.
Connecting cables to the screw terminal Connecting the cables to the ring lug terminals: Note The SENTRON PAC3200 with ring lug terminal is only intended for: • use in NAFTA / USA • Regions in which open terminals are permitted.
All input or output terminals not required for measuring remain free. The wiring method must be made known to the device in the device settings. The connection types given below refer to the device parameterization. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 83
(2) Three-phase measuring, four conductors, unbalanced load, with voltage transformers, with three current transformers Connection type 3P4W Figure 6-9 Connection type 3P4W, with voltage transformer, with three current transformers Fuses must be provided by the customer. Connection of supply voltage SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 84
(4) Three-phase measuring, four conductors, balanced load, with voltage transformers, with one current transformer Connection type 3P4WB Figure 6-11 Connection type 3P4WB, with voltage transformer, with one current transformer Fuses must be provided by the customer. Connection of supply voltage SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 85
(6) Three-phase measuring, three conductors, unbalanced load, with voltage transformers, with three current transformers Connection type 3P3W Figure 6-13 Connection type 3P3W, with voltage transformer, with three current transformers Fuses must be provided by the customer. Connection of supply voltage SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 86
(8) Three-phase measuring, three conductors, unbalanced load, with voltage transformers, with two current transformers Connection type 3P3W Figure 6-15 Connection type 3P3W, with voltage transformer, with two current transformers Fuses must be provided by the customer. Connection of supply voltage SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 87
(10) Three-phase measuring, three conductors, balanced load, with voltage transformers, with one current transformer Connection type 3P3WB Figure 6-17 Connection type 3P3WB, with voltage transformer, with one current transformer Fuses must be provided by the customer. Connection of supply voltage SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 88
(12) Single-phase measuring, two conductors, without voltage transformers, with one current transformer Connection type 1P2W Figure 6-19 Connection type 1P2W, without voltage transformer, with one current transformer Fuses must be provided by the customer. Connection of supply voltage SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 89
Figure 6-20 Connection type 3P3W, with voltage transformer, with three current transformers Fuses must be provided by the customer. Connection of supply voltage See also Measured variables (Page 24) Applying the supply voltage (Page 92) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
2. The device has been connected in accordance with the possible connection methods. 3. An optional expansion module has been installed. If the SENTRON PAC3200 is to be operated with an expansion module, the module must be installed before the SENTRON PAC3200 is started up.
If a supply voltage is applied that does not comply with the specifications on the type plate, this can result in malfunctioning and failure of the device. The SENTRON PAC3200 can be supplied with an AC / DC multi-range power supply or a DC extra-low voltage power supply.
● after resetting to factory settings, and ● after updating the firmware. English is the default language. Figure 7-1 Language selection Select the desired language by pressing <F2> or <F3> Apply the desired language with <F4> SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 94
8. Accept the desired language with: <F4> The language is permanently saved and becomes effective immediately. The display returns to display mode. 9. Return to one of the selection menus or to the measured values display: <F1> SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
4. In the "SETTINGS" menu, go to the "BASIC PARAMETERS" entry: <F2> or <F3> 5. Call the "BASIC PARAMETERS" entry: <F4> 6. In the "BASIC PARAMETERS" menu, call the "VOLTAGE INPUTS" entry: <F4> The display shows the currently valid settings. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Off: Measurement direct on the low-voltage system. The device setting is saved permanently and becomes effective immediately. The display remains in display mode. 5. Return to one of the selection menus or to the measured values display: <F1> SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Proceed in exactly the same way as when entering the primary voltage. The value of the secondary voltage is permanently saved and becomes effective immediately. The display returns to display mode. 8. Return to one of the selection menus or to the measured values display: <F1> SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
<F4> The value of the voltage input is permanently saved and becomes effective immediately. The display returns to display mode. 7. Return to one of the selection menus or to the measured values display: <F1> SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
The display returns to display mode. 7. Return to one of the selection menus or to the measured values display: <F1> Example You want to measure the current using current transformers for 5000 A/5 A. For this purpose, enter: SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
● 400 V phase-to-neutral (max. 347 V for UL) and ● 690 V phase-to-phase (max. 600 V for UL). The SENTRON PAC3200 with extra-low voltage power supplyis designed for measuring in systems with rated AC voltages to ● 289 V phase-to-neutral and ●...
Instead, change the interpretation of the direction in the device settings. You can find more information in the chapter "Parameterizing", "INVERTED CURRENT". See also Safety notes (Page 17) Measuring inputs (Page 22) Safety notes (Page 73) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
With the help of the table "Displaying the measured variables depending on the connection type", check whether the measured variables are displayed in accordance with the connection type executed. Any deviation indicates a wiring fault or configuration error. See also Measured variables (Page 24) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Operator control Device interface 8.1.1 Displays and operator controls Displays and operator controls The front of the SENTRON PAC3200 contains the following displays and operator controls. Figure 8-1 Device interface Display of the measured values, device settings, selection menus Display title...
Page 104
● Display of the device settings The display shows the values of the currently effective device settings. ● Edit mode of the device settings The display enables editing of the device settings. The figure below shows the structure. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 105
: Permanently saves the last set value and returns from edit mode to display mode. If no editing is intended, the key closes the display and returns to the menu selection. : Is an ON/OFF switch. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 106
Information structure and navigation Special display elements Device protection symbol The padlock symbol in the display title indicates whether the device settings are protected against unauthorized or inadvertent changes or not. Device is protected. Device is not protected. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 107
● If the menu list has more entries than can fit on the display, the display switches to scroll mode. The selection bar remains stationary in the middle of the display. The menu list rolls up and down "under" the bar. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 108
The horizontal bar above function key F1 shows the multiple assignments of the function key. The key assignment changes every time you press the key. Figure 8-5 Scroll bar Scroll bar of function key F1 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 109
● Maximum ● Minimum When displaying the average value, the maximum/minimum symbol indicates the following: ● (without symbol) current average value ● Maximum average ● Minimum average Figure 8-6 Maximum/minimum symbols Maximum symbol Minimum symbol SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Designation of the measured variable Designation of the measured value property Display number of the measured variable Measured value display Phase labels Measured value Unit of the measured variable Function keys Key labeling Scroll bar of function key F1 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 111
• Off peak • Universal counter UNIVERSAL COUNTER UNIVERSAL COUNTER 16.0 Working hours counter Bh WORKING HOURS WORKING HOURS 17.0 Unbalance UNBAL. %V, %A UNBALANCE 18.0 Voltage • Current • Device settings SETTINGS SETTINGS 20.1 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 112
Reset the maximum/minimum or average value to the instantaneous value Scroll up in the selection list Scroll down in the selection list Go to the menu selection See also Operator input steps in the "MAIN MENU" (Page 119) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
The main menu has no visible display number of its own. The display number shown refers to the currently selected measured variable. List of viewable measured variables The menu list shows the choice of viewable measured variables. Selection bar The selection bar highlights the currently selected measured variable. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Display number of the device setting List of device settings Line separating the start and end of the list Selection bar Scroll bar Function keys Key labeling The "SETTINGS" menu contains the same operator controls as the "MAIN MENU". SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Designation of the selected group of device settings Device protection symbol Display number of the device setting List of device settings Selection bar Current setting Function keys Key labeling Display title Specifies which group of device settings is currently selected. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
List of device settings Device setting in edit mode Note: Display mode also includes edit functions! In display mode, F4 functions as an ON/OFF switch with immediate effect. Calling edit mode is no longer applicable. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Display the instantaneous, maximum/minimum or average value F1 switches the display on. : Display of the maximum value : Display of the minimum value : Display of the instantaneous value : Display of the average value SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 118
Display the instantaneous, maximum/minimum or average value Reset the maximum or minimum value to the instantaneous value resets the last reached maximum/minimum value to the instantaneous value. Figure 8-13 Reset the maximum or minimum value to the instantaneous value SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
In the measured value display, you can switch to other measured value displays without calling the main menu. Displaying the measured variable The selection bar highlights the currently selected menu entry (white text on a black background). calls the display of the selected measured variable. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Selecting settings The selection bar highlights the currently selected menu entry (white text on a black background). moves the selection bar up in the menu list. moves the selection bar down in the menu list. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
You can recognize edit mode because the selection bar reduces to the width of the selected value. Figure 8-17 Calling edit mode Exiting the display closes the display and returns to the "SETTINGS" menu. Figure 8-18 Exiting the display SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
8.2 Operator input steps 8.2.5 Operator input steps in edit mode of the device settings Enter password If device protection is switched on, the SENTRON PAC3200 demands input of the valid password. Figure 8-19 Enter password You can find information on password management in the "Password management" chapter.
Page 123
Figure 8-23 Defining multi-digit values Saving the value saves the set value and returns to display mode. Canceling editing cancels editing and returns to display mode. All changes are discarded. Figure 8-24 Exiting edit mode SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Protection of the device settings As delivered, the device settings are not protected. At startup, a password should be assigned and the device protection activated to guard against unauthorized or inadvertent changes. See also Advanced (Page 142) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
● Language/Regional ● Basic parameters ● Power demand ● Integrated I/O ● Communication ● Display ● Advanced ● PROFIBUS module (only if the optional PAC PROFIBUS DP expansion module is plugged in) Figure 9-1 "Settings" menu SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 129
INVERT CT POLARITY POWER DEMAND 21.4 TIME INTERVAL SYNC. VIA BUS SYNC. VIA DIG.INPUT INTEGRATED I/O 24.0 DIGITAL OUTPUT 24.0 ACTION SOURCE PULSES PER UNIT PULSE LENGTH DIGITAL INPUT 24.1 ACTION PULSES PER UNIT UNIT SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Language of the display. Range: German, English, Portuguese, Turkish, Spanish, Italian, French, Chinese, Russian Default: English PHASE LABELS Designation of the phases on the display. Range: L1 L2 L3, a b c Default: L1 L2 L3 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 134
Rated voltage of the measuring system. Must be specified if measuring is done direct on the system without voltage transformers. SENTRON PAC3200 with multi-range power supply Range: 1 V to 690 V, freely adjustable (max. 600 V for Default value: 400 V...
Page 135
PT SECONDARY Secondary voltage. Must be specified if a voltage transformer is used for measuring. SENTRON PAC3200 with multi-range power supply Range: 1 V to 690 V, freely adjustable (max. 600 V for Default value: 400 V SENTRON PAC3200 with extra-low voltage power...
ON / OFF. OFF: SENTRON PAC3200 interprets the direction of current flow in accordance with the wiring. On: Direction of current flow is inverted. SENTRON PAC3200 interprets the direction of current flow opposite to the wiring. Default: 9.2.5 Power demand Device settings for acquiring the power demand.
The digital output is switched on by a limit violation and remains active while the limit violation prevails. The field "DIGITAL OUTPUT > SOURCE" selects the limit to be monitored. The definition of the limit is stored in "ADVANCED > LIMITS". SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 138
OUTPUT > PULSES PER UNIT". PULSES PER The field is available with the action "ENERGY PULSE". UNIT Number of pulses per unit. The unit is defined in the field "DIGITAL OUTPUT > SOURCE". Range: 1 to 999 Default: 1 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 139
The field is available with the action "PULSE INPUT". UNIT Range: 1 to 999 Default: 1 Figure 9-12 "DIGITAL INPUT" device setting UNIT Visible with action "PULSE INPUT" Countable unit with pulse counting: kWh (active energy) kvarh (reactive energy) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
OFF: Dark text on light background. On: Light text on dark background. Default: REFRESH TIME Refresh rate of the display. Range: 330 to 3000 ms Default: 330 ms. The tolerance of the refresh rate is 100 ms. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 143
LIMITS Monitoring of 6 limit values "LIMIT 0" to "LIMIT 5". The limit value "LIMIT LOGIC" comprises limits 0 to 5. Figure 9-19 "LIMITS" device setting Limit designation Monitored data source Limit currently violated: Yes, SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 144
UNBAL V, UNBAL I, Default: V L1 MODE Relational operators GREATER THAN, LOWER THAN the value in the VALUE field. Default operator: GREATER THAN VALUE Monitored threshold. Default: 0 V, corresponding to "SOURCE V L1" SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 145
Range: 0.0 to 20.0% Default: 0,0 % The percentage value refers to the threshold value in the VALUE field. See the figure below "Effect of delay" SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 146
Parameterize 9.2 Parameterizing the operator interface Figure 9-21 Effect of delay and hysteresis on upper and lower limit violations STATUS Indicates whether the limit value is currently violated. Yes, violation. No, no violation. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 148
• Energy counter for active energy, reactive energy, apparent energy. • Working hours counter UNIV.COUNTER RESET Resets the configurable universal counter to 0 (zero). FACTORY DEFAULTS Resets the device settings to the default values. Clears minimum/maximum values. Resets all counters. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
If the PAC PROFIBUS DP expansion module is plugged in , the device setting "PROFIBUS MODULE" is executed in the "SETTINGS" menu. Call: "SETTINGS > PROFIBUS MODULE". PROFIBUS ADDRESS PROFIBUS address number of the device Range: 0-126 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
2. In the main menu, go to the "SETTINGS" entry: or F3 3. Call the "SETTINGS" entry: 4. In the "SETTINGS" menu, go to the "ADVANCED" entry: or F3 5. Call the "ADVANCED" entry: 6. In the "ADVANCED" menu, call the "PASSWORD PROTECTION" entry: SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
The password becomes visible on the display when password protection is switched off. The password remains saved and becomes effective again the next time password protection is switched on. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Initial situation: Password protection switched off If password protection is switched off, the password is also unprotected and can therefore be changed without restriction. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 153
If you have entered the correct password, the password becomes visible in the PASSWORD field. 6. Open edit mode of the device setting "PASSWORD" with: 7. Change the password with: and F3 8. Accept the new password with: The password is permanently saved and becomes effective immediately. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
● You can find the MAC address under "SETTINGS > COMMUNICATION" NOTICE Change password immediately on receipt As soon as you receive the new password, you must change it and inform the group of authorized users. See also Technical support (Page 13) SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Maintenance and servicing 10.1 Cleaning Description The SENTRON PAC3200 is maintenance-free. Calibration The device has been calibrated by the manufacturer before shipping. Recalibration is not required provided the environmental conditions are maintained. Cleaning Clean the display and the keypad periodically. Use a dry cloth for this.
Procedure NOTICE Loss of warranty If you open the device, it loses its Siemens warranty. Only the manufacturer may carry out repairs to the device. Return faulty or damaged devices to Siemens for repair or replacement. If the device is faulty or damaged, proceed as follows: 1.
(in accordance with IEC/UL 61010 Part 1) Input voltage V to 230 V (V CAT III ph-n to 400 V (V CAT III ph-ph to 289 V (V CAT III ph-n to 500 V (V CAT III ph-ph SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 158
Digital input Number 1 input Input voltage Rated value 24 V DC Maximum input voltage 30 V DC Switching threshold for signal "1" > 11 V DC Input current For signal "1" typ. 7 mA SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
24 V, 48 V and 60 V DC or 22 to 65 V DC Work area ± 10% of rated range DC Power consumption Typically 8 VA (with optional expansion module). Overvoltage category CAT III SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 160
AWG 2 x 20 ... 16 Stripping length 10 mm Connection screws Tightening torque 0.8 ... 1.2 Nm 7 ... 10.3 lbf·in Tool Screwdriver PZ2 cal. ISO 6789 Crimping tool in accordance with EN 60947-1 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 161
0.8 ... 1.2 Nm 7 ... 10.3 lbf·in With vertical screwing 30 N force 6.75 lbf Tool Screwdriver PZ2 cal. ISO 6789 Crimping or pressing tool according to manufacturer's information for ring lugs Digital output, digital input SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 162
Degree of protection according to IEC 60529 Front IP65 Rear Device with screw IP20, NEMA 1A terminal Device with ring lug IP10 terminal If higher degree of protection requirements are placed on the application engineering, the customer must take suitable measures SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
- 10 °C to + 55 °C Storage and transport temperature - 25 °C to + 70 °C Relative humidity 95% at 25°C without condensation (normal conditions) Operating altitude above sea level Up to 2000 m Degree of pollution SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
The device has been tested in accordance with the following standards: IEC / UL 61010-1:2001 (2nd Ed.) with Corr. 1 CAN / CSA C22.2 No. 61010-1, second Edition EN 61010-1-1:2001 (2nd Ed.) DIN EN 61010-1:2002 with Corr. 1 SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Technical data 11.2 Labeling 11.2 Labeling Labels on the housing of the SENTRON PAC3200 Figure 11-1 Device labeling Symbol, label Explanation Protective insulation, device of protection class II. Products with this mark comply with both the Canadian (CSA) and the American (UL) requirements.
Page 166
Technical data 11.2 Labeling Symbol, label Explanation Caution! General hazard area. Overvoltage category CAT III for current and voltage inputs. Danger of electric shock. AC current (10) Three-phase AC SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 170
Dimension drawings 12.1 Dimension drawings Clearances Figure 12-5 Clearances, device with screw terminal (on the left), device with ring lug terminal (on the right) The clearances specified must be maintained for cable outlets and ventilation. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Appendix Certification marks CE mark The SENTRON PAC3200 Power Monitoring Device meets the requirements and protection goals of the following EC directives: ● Low Voltage Directive 2006/95/EC ● EMC Directive 2004/108/EC UL mark Products with this symbol meet both UL and Canadian requirements.
If you have to store or transport the component in non-conductive packaging, you must first pack the component in ESD-safe, conductive material, e.g., conductive foam rubber, ESD bag. The diagrams below illustrate the required ESD protective measures for electrostatic sensitive devices. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 174
B.1 Electrostatic sensitive devices (ESD) Figure B-1 ESD work center ESD seat ESD standing position ESD seat and ESD standing position Table B-1 Protective measures Conductive floor ESD table ESD footwear ESD smock ESD bracelet Cubicle ground connection SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Industrial, Scientific and Medical International Standardization Organization Liquid crystal display Media Access Control NAFTA North American Free Trade Agreement NEMA National Electrical Manufacturers Association Power Analysis & Control Registered Jack Formerly: Radio Selector; now usually: Recommended Standard SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
Page 176
C.1 Abbreviations Abbreviation Meaning TCP/IP Transmission Control Protocol/Internet Protocol Total Harmonic Distortion; German: Gesamte Harmonische Verzerrung THD-R Relative THD Underwriters Laboratories Inc. Association of Electrical Engineering, Electronics and Information Technology (Germany) Result of logic operation SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...
PROFIBUS is a bus system that connects PROFIBUS-compatible automation systems and field devices together at the cell level and field level. PROFIBUS address Every bus node receives a unique PROFIBUS address. The bus node is identified on PROFIBUS with this address. SENTRON PAC3200 Manual, 02/2008, A5E01168664B-04...