hit counter script
Bosch B921C - Two-Line Capactive Keypad Installation Guide

Bosch B921C - Two-Line Capactive Keypad Installation Guide

Also See for B921C:

Advertisement

Bosch B921C - Two-Line Capactive Keypad Installation Guide

Overview

The B921C keypad is a SDI2 bus compatible device. Each keypad has user adjustable options such as volume and backlight, and an LCD display that shows two-line system messages. The keypad features capacitive keys.
The B921C connects to the SDI2 bus on the control panel using terminal wiring. You can connect more than one keypad to the control panel by wiring them in parallel.
You can program, diagnose, and troubleshoot the system from the control panel keypad as well as remotely through RPS.
You can wire up to 4 inputs to the keypad.
Keypad base overview
Figure 1.1: Keypad base overview

Callout ― Description

  1. 3 in octagon box holes
  2. Single gang box holes
  3. Double gang box holes
  4. Wire opening
  5. Surface mount wire openings
  6. in square box or wall mount holes
  7. Surface mount wire channel
  8. Bubble level
  9. SDI2 wiring terminal block
  10. Inputs wiring terminal block
  11. Wire tie posts

SDI2 address switches

Two switches determine the address for the keypad. The control panel uses the address for communications. Use a slotted screwdriver to set the switches.

Access the address switches

  1. Unlock the keypad by turning the lock counter-clockwise. Refer to Figure 2.1.
    Access the address switches - Step 1
  2. Hold the keypad by the base in one hand. With the other hand, gently push down on the keypad to remove it from the base. Refer to Figure 2.2.
    Access the address switches - Step 2
  3. Look at the back of the keypad, and locate the switches.

Set the address switches

Set the address switches per the control panel configuration. If multiple SDI2 keypads reside on the same system, each SDI2 keypad must have a unique address. For single-digit addresses 1 through 9, set the tens switch to 0. Figure 2.4 shows the address switch setting for address 1.
Set the address switches

Understand addresses and point numbers

To determine the point numbers for each keypad address, multiply the address number by 10 for the base number, and then use numbers 1 through 4 in the ones place for the point numbers.

Examples
For B921C address 01 the point numbers for the input devices are 11 through 14:

Terminal number 1 2 3 4
Point number 11 12 13 14

For B921C address 11 the point numbers for the input devices are 111 through 114:

Terminal number 1 2 3 4
Point number 111 112 113 114

Installation

After you set the address switches for the proper address, mount the keypad base, wire to the control panel, and attach the keypad to the base.

Mount the keypad

You can surface mount the keypad, or mount it to standard electrical boxes, including single and double gang boxes.
Mounting the keypad:

  1. Use the base as a template to mark the desired mounting surface. Refer to Figure 1.1 for mounting hole and wiring locations.
  2. Pull the wiring through the desired wire opening in the base.
  3. Use the appropriate mounting hardware (supplied) to mount the base to the desired mounting surface. Refer to Figure 1.1 for mounting hole and wiring locations.

Wire to the control panel

When you wire the keypad to a control panel, use the control panel terminals labeled R, Y, G, B (PWR, A, B, COM). Connect them to the keypad terminals labeled R, Y, G, B. Refer to Figure 3.1.
You can connect keypads to the SDI2 data bus by parallel wire run from the control panel to each keypad, wire from keypad to keypad, or a combination of the two techniques. Refer to Figure 3.2.
 Wiring the keypad to the SDI2 bus connection
Figure 3.1: Wiring the keypad to the SDI2 bus connection (B5512 shown)

Callout ― Description

  1. Control panel
  2. Terminal wiring
  3. Keypad's SDI2 wiring terminal block

Installing multiple keypads using the SDI2 terminals
Figure 3.2: Installing multiple keypads using the SDI2 terminals
Reconnect the keypad to the base by sliding the keypad onto the base (reverse of Step 2). The keypad automatically locks onto the base. Apply power to the system.

Sensor loop wiring

To wire detection devices to the B921C inputs, connect them to the keypad terminals labeled for 1, 2, 3, 4, and COM. Wire resistance on each sensor loop must be less than 100 Ω with the detection devices connected. The terminal strip supports 12 to 22 AWG (0.65 to 2 mm) wires.
The keypad detects open, short, normal, and ground fault circuit conditions on its sensor loops and transmits the conditions to the control panel. Each sensor loop is assigned a point number and transmits to the control panel individually. Run wires away from the premises telephone and AC wiring. Refer to Figure 3.3.

Figure 3.3: Wiring sensor loops

Callout Description
1 Keypad's COM 1, 2, 3, and 4 terminal strip
2 Keypad sensor loops
3 1 kΩ EOL resistor (ICP-1K22AWG-10)
4 Wiring to additional sensor loops

Display

You can adjust the keypad's display brightness level, and you can turn the keypad's nightlight feature on or off.
Adjusting the keypad display brightness:

  1. Press [MENU] to open the Main menu.
  2. Use [NEXT] to go to the Press 5 for Settings Menu option, or simply press [5].
  3. Use [NEXT] to go to the Press 4 for Keypad Config option, or simply press [4].
  4. Press [1] to adjust the brightness.
  5. Use [PREV] or [NEXT] to adjust the brightness level. The changes apply immediately.
  6. Press [ESC] to exit the menu.

Turning the keypad nightlight on or off:

  1. Press [MENU] to open the Main menu.
  2. Use [NEXT] to go to the Press 5 for Settings Menu option, or simply press [5].
  3. Use [NEXT] to go to the Press 4 for Keypad Config option, or simply press [4].
  4. Use [NEXT] to go to the Press 4 for Nightlight option, or simply press [4].
  5. Press [ENTER] to turn it on or off. The changes apply immediately.
  6. Press [ESC] to exit the menu.

Status icons

You can diagnose and troubleshoot the system using the keypad's status icons. Refer to Table 5.1.

Status icon Function status icon ― on
Green LED - Ready to turn All or Part On
Red LED - Turned On
warning Yellow LED - System trouble
Blue LED - Gas alarm
Blue LED - AC power present

Table 5.1: Keypad status LEDs

Audible tones

The keypad has a built-in speaker that produces several distinct warning tones. The keypad backlight illuminates when it emits an audible tone.

Tone Description
Fire signal When an area is in fire alarm, the keypad emits a pulsed, high-pitched bell tone.
Gas signal When a gas point activates, the keypad emits a unique high pitched tone.
User alarm When a user alarm (such as panic and medical alarms) occurs, the tone sounds for the programmed amount of time.
Burglary signal When an area is in alarm, the keypad emits a steady, high pitched bell tone.
Entrance warning The keypad emits an intermittent beep tone during entry delay periods to remind the user to disarm the area.
Exit warning The keypad emits an intermittent beep tone during exit delay.
Invalid button buzz When an invalid button, or sequence of buttons, is pressed, the keypad emits a fl at buzz tone.
Keypad encoding tone The keypad emits a muted beep tone as each button is pressed to indicate that the entry was accepted.
Trouble buzzer When a trouble event occurs, such as a service alert, the keypad emits a two-tone warble until you enter a programmed passcode with the appropriate authority.
Watch tone A single clean tweedle tone alerts the user anytime a watch point is faulted.

Table 6.1: Keypad audible tones

Supervision

The control panel supervises all keypads on the SDI2 bus. If a supervised keypad fails to respond to the control panel, the control panel declares a Missing Keypad Trouble. When the control panel can again communicate with the keypad, it restores the Missing Keypad Trouble. During a Missing Keypad Trouble, any connected keypad that maintained contact with the control panel shows the Missing Keypad Trouble as its idle text, and shows the missing keypad's address. The communicating keypads also sound a trouble tone. Users can silence the trouble tone. If no other troubles exist, the tone silences when the missing keypad restores.

Show the firmware version

Showing the keypad firmware version:

  1. Remove the keypad from the base to remove power to the keypad. Refer to Figures 2.1 and 2.2.
  2. Return the keypad to the base to restore power.

The keypad shows the model number, keypad address, and firmware version for 10 sec.
informationYou can also view a keypad's firmware version in RPS.

Cleaning the keypad

Use a soft cloth and non-abrasive cleaning solution to clean your keypad (for example, microfiber cloth and eyeglass cleaner). Spray the cleaner onto the cloth. Do not spray cleaners directly onto the keypad.

Certifications

Region Certification
US UL 365 - Police Station Connected Burglar Alarm Units and Systems
UL 609 - Local Burglar Alarm Units and Systems
UL 985 - Household Fire Warning System Units
UL 1023 - Household Burglar-Alarm System Units
UL 1076 - Proprietary Burglar Alarm Units and Systems
UL 1610 - Central Station Burglar Alarm Units
CSFM - California Office of The State Fire Marshal
FCC Part 15 Class B
Canada ULC-ORD C1076 - Proprietary Burglar Alarm Units and Systems
ICES-003 - Digital Apparatus
ULC S545 - Residential Fire Warning System Control Units

Specifications

Dimensions 6.2 in x 4.7 in x 1 in (158 mm x 120 mm x 26 mm)
Voltage (input) 12 VDC nominal
Current 45 mA in standby mode 85 mA in alarm mode
Operating temperature 0°C to +50°C (+32°F to +122°F)
Relative humidity 5% to 93% at +32°C (+90°F) noncondensing
Terminal wire size 12 AWG to 22 AWG (2 mm to 0.65 mm)
SDI2 wiring Maximum distance - wire size (unshielded wire only):
700 ft (213 m) - 22 AWG (0.65 mm)
1000 ft (305 m) - 18 AWG (1.02 mm)
Compatibility B5512 v2.02 or higher
B4512 v2.02 or higher
B3512 v2.02 or higher
D9412GV4 v2.02 or higher
D7412GV4 v2.02 or higher

Copyright
This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/.

Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450 USA
www.boschsecurity.com

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Bosch B921C - Two-Line Capactive Keypad Installation Guide

Advertisement

Need Assistance?

Do you have a question about the B921C that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents