Operating place ........................................................................................................................................................
Page 1
Swing door drive mechanism with fire protection rating ETS 64-R Mounting and operating instructions Original Com. no........... Pos........Construction year ....Operator ................................Operating place ................................ 0548-990/62g 2019.10...
ETS 64-R Mounting and operating instructions TABLE OF CONTENTS GENERAL REMARKS ........................ 5 Target group ........................5 Where to keep these instructions .................. 5 Adresses ......................... 5 Auxiliary tools and service performances ..............6 SAFETY ............................7 Appropriate use ......................7 Safety notices .........................
Page 3
ETS 64-R Mounting and operating instructions ELECTRICAL CONNECTIONS ....................44 Power supply ....................... 44 Cable layout ......................... 46 5.2.1 Lintel mounting ..................... 46 Fire protection PCB ...................... 47 External elements ......................49 Motorized lock ......................50 5.5.1 Motorised lock with direct connection to motor coil ........50 5.5.2...
The present instructions have to be kept close to the installation, together with the control book- let! Adresses Distribution agent/ After-sales service Distribution ECO Schulte GmbH & Co. KG Iserlohner Landstrasse 89 D-58706 Menden Tel. +49 23 73 / 92 76-0 +49 23 73 / 92 76-40 www.eco-schulte.de...
ETS 64-R Mounting and operating instructions Auxiliary tools and service performances The auxiliary tools and service performances listed hereafter are available, depending on the respective situation and authorization (please ask your distribution agent): • Company portrait • Homepage • News •...
SAFETY Appropriate use The swing door drive mechanism with fire protection rating ETS 64-R has been exclusively de- signed for operating swing doors with fire protection rating. Any other use beyond these appli- cation limits is deemed inappropriate and inadmissible! In the event of an inappropriate use of this system, the safety of the user may be jeopar dized and/or the installation be damaged.
Page 8
• In its assembled state, the installation must answer all the safety requirements specified by the machinery directive. • The swing door drive mechanism with fire protection rating ETS 64-R may only be installed and operated in dry rooms. If this condition cannot be fulfilled, the customer must provide sufficient protection from moisture.
A safe and reliable function of the installation can only be guaranteed if it is operated with the original ECO Schulte GmbH & Co. KG accessories/spare parts. ECO Schulte GmbH & Co. KG decli- nes all responsibility for damages resulting from unauthorized modifications of the installation or from the use of foreign accessories/spare parts.
PRODUCT DESCRIPTION General remarks The swing door drive mechanism with fire protection rating ETS 64-R resp. ETS 64-R GSd (special gear for sliding rods pushing function) opens and closes the door leaf via a rod assembly (is not shown in the illustration). The fire protection drive mechanism is implemented by means of a fire- protection PCB.
Sliding rods pulling function pushing function Drive mech. ETS 64-R – – – ETS 64-R GSd * * special gear Normal rods RS Normal rods Sliding rods RG Sliding rods A Clamping piece B Rotating arm C Joint...
Mounting and operating instructions Inverse application The swing door drive mechanism ETS 64-R is also appropriate for inversed operation. This parti- cular function can be separately programmed for each drive mechanism. The inverse application is suitable for smoke extraction from buildings (RWA = smoke and heat exhaust vent solution) as well as for escape and rescue ways.
ETS 64-R Mounting and operating instructions Technical data Drive mechanism Standard GSd (special gear for sliding rods pushing function) Power transmission Normal rods Sliding rods Dimensions drive mechanism Height 95 mm, Width 690 mm Depth 120 mm Weight drive mechanism...
ETS 64-R Mounting and operating instructions Application limits without safety elements according to EN 16005 Warning: In the event of swing doors installed in a non publicly accessible areas, without ins- tallation of safety elements that monitor the door leaf movement, the setting values specified hereafter for the opening speed Vo and the closing speed Vc must not be exceeded.
ETS 64-R Mounting and operating instructions MOUNTING Preparation Attention: Standard + inverse application It is imperative for the customer to install a door leaf stop piece! The latter limits the opening motion of the door leaf and prevents it's being damaged in the manual operating mode.
ETS 64-R Mounting and operating instructions Mounting versions 4.2.1 Rod assemblies narrow RS/RG DIN left DIN right Normal rods 0548-163/01 pushing function Normal rods 0548-163/01 pushing function Lintel mounting see chapter 4.4.1 Lintel mounting see chapter 4.4.1 Lintel depth 0...250 mm Lintel depth 0...250 mm...
ETS 64-R Mounting and operating instructions 4.2.2 Rod assemblies stainless steel DIN left DIN right Normal rods 0548-104 Normal rods 0548-104 pushing function 0548-104/01 KTL pushing function 0548-104/01 KTL Lintel mounting see chapter 4.5.1 Lintel mounting see chapter 4.5.1 Lintel depth 0...240 mm...
0548-360 Mod The mounting plate 0548-360 can be used in cases where an existing FDC-B drive mechanism needs to be replaced by an ETS 64-R drive mechanism and where the existing fastening holes of the FDC-B-mounting plate have to be reused.
Page 20
ETS 64-R Mounting and operating instructions Warning: The drive mechanism must be fastened without torsion and perpendicularly, using all the six fixing holes! Tighten all the six M6 fixing screws (A) with a torque of 10 Nm! 0548-358 0548-360 MOD...
ETS 64-R Mounting and operating instructions Rod assemblies narrow RS/RG 4.4.1 Normal rods RS pushing function / Lintel mounting Material: Drive mechanism 0548-032 Covering aluminium Drive mechanism 0548-033 Covering inox incl. fixing set 0548-107 Mounting plate 0548-358 resp. 0548-360 MOD...
Page 22
ETS 64-R Mounting and operating instructions with mounting plate Options Axle extension (mm) (mm) (mm) Standard 0548-190 3...13 0548-191 3...23 0548-192 3...33 0548-193 3...43 0548-194 3...53 DIN right = as shown DIN left = mirror-inverted Fixing drive Fixing mechanism mounting plate Ø20...
Page 23
ETS 64-R Mounting and operating instructions Drive mechanism standard Inverse application 5. Close the door leaf. 5. Separate the rotating arm (C) from the rod arm (B) by loosen the screw (E). 6. Separate the rotating arm (C) from the rod arm (B) by loosen the screw (E).
Page 24
ETS 64-R Mounting and operating instructions Inverse application 1. Let the door leaf be opened by spring power. 2. Using a screwdriver, carefully prize the service cover (C) out of the gearbox housing. 3. By means of a socket wrench 1,5 mm, slightly loosen the locking screw (B) and leave the socket wrench inserted in the locking screw (B).
ETS 64-R Mounting and operating instructions 4.4.2 Sliding rods RG pulling function / Lintel mounting Material: Drive mechanism 0548-032 Covering aluminium Drive mechanism 0548-033 Covering inox incl. fixing set 0548-107 Mounting plate 0548-358 resp. 0548-360 MOD Sliding rods 0548-164/01 650 mm incl. sliding bolts 18/46 mm Procedure: Mark out and drill the fastening holes on the lintel and the door leaf.
Page 26
ETS 64-R Mounting and operating instructions with mounting plate DIBt Lintel Min. width door Max. door Options Axle extension che- depth leaf (mm) opening (mm) (mm) (mm) (mm) cked (mm) without / with angle without / with Standard 26...51 FLATSCAN (°)
Page 27
ETS 64-R Mounting and operating instructions Drive mechanism standard Inverse application 6. Close the door leaf. 6. Mount the drive mechanism. 7. Prior to the installation of the drive unit: 7. Open the door leaf (max. 115°). Screw down the lever arm (D) on the drive unit ...
ETS 64-R Mounting and operating instructions 4.4.3 Sliding rods RG pushing function / Lintel mounting Material: Drive mechanism GSd 0548-034 Covering aluminium Drive mechanism GSd 0548-035 Covering inox incl. fixing set 0548-107 Mounting plate 0548-358 resp. 0548-360 MOD Sliding rods 0548-164/01 650 mm incl.
Page 29
ETS 64-R Mounting and operating instructions with mounting plate DIBt Lintel Min. width door Max. door ope- Options Axle extension che- depth leaf ning angle (mm) (mm) (mm) cked (mm) (mm) (°) (mm) Standard -30...0 0548-190 3...13 1...10 ...
Page 30
ETS 64-R Mounting and operating instructions Drive mechanism standard Inverse application 7. Close the door leaf. 7. Open the door leaf (max. 115°). 8. Screw down the lever arm (D) on the drive unit 8. Slide the open position stop piece (B) into the sliding Tightening moment 25 Nm.
ETS 64-R Mounting and operating instructions Rod assemblies stainless steel 4.5.1 Normal rods pushing function / Lintel mounting Material: Drive mechanism 0548-032 Covering aluminium Drive mechanism 0548-033 Covering inox incl. fixing set 0548-107 Mounting plate 0548-358 resp. 0548-360 MOD Normal rods...
Page 32
ETS 64-R Mounting and operating instructions Drive mechanism standard Inverse application 5. Close the door leaf. 5. Separate the rotating arm (D) from the rod arm (B) by dismounting the ball and socket joint (E). 6. Separate the rotating arm (D) from the rod arm (B) by dismounting the ball and socket joint (E).
ETS 64-R Mounting and operating instructions 4.5.2 Sliding rods pulling function / Lintel mounting Material: Drive mechanism 0548-032 Covering aluminium Drive mechanism 0548-033 Covering inox incl. fixing set 0548-107 Mounting plate 0548-358 resp. 0548-360 MOD Sliding rods 0548-134 620 mm incl. sliding bolts 14/38 mm...
Page 34
ETS 64-R Mounting and operating instructions DIBt che- Lintel depth Min. width door Max. door ope- Rod assem- cked (mm) leaf (mm) ning angle blies (mm) (mm) (mm) without / with (°) (art. no.) without / with FLATSCAN FLATSCAN -30...+30...
Page 35
ETS 64-R Mounting and operating instructions Drive mechanism standard Inverse application 4. Close the door leaf. 4. Mount the drive mechanism. 5. Install the mounting profile (E) on the door leaf. 5. Install the mounting profile (E) on the door leaf.
ETS 64-R Mounting and operating instructions 4.5.3 Sliding rods pushing function / Lintel mounting Material: Drive mechanism GSd 0548-034 Covering aluminium Drive mechanism GSd 0548-035 Covering inox incl. fixing set 0548-107 Mounting plate 0548-358 resp. 0548-360 MOD Sliding rods 0548-134 620 mm incl.
Page 37
ETS 64-R Mounting and operating instructions DIBt che- Lintel depth Min. width door Max. door opening Rod assem- cked (mm) leaf (mm) angle blies (mm) (mm) (mm) (°) (art. no.) -30...+10 0548-105 11...20 0548-105 21...30 0548-105 –...
Page 38
ETS 64-R Mounting and operating instructions Drive mechanism standard Inverse application 5. Close the door leaf. 5. Install the mounting profile (E) on the door leaf. 6. Install the mounting profile (E) on the door leaf. 6. Hook the guide profile (G) into the mounting profile (E), on both sides insert and screw down (with 7.
ETS 64-R Mounting and operating instructions Adjusting the pre-stressing of the closing spring Upon delivery, the closing spring is pre-stressed for a measure X* = 26 mm. To ensure a safe and optimal operation of the swing door drive mechanism, the correct pre-stressing must be adjusted for the closing spring (by means of the setting screw).
Page 40
ETS 64-R Mounting and operating instructions Inverse application EN class EN 3 EN 4 EN 5 EN 6 Width of door leaf 950 mm 1'100 mm 1'250 mm 1'400 mm Normal rods Measure X * 40 mm 36 mm 31 mm...
ETS 64-R Mounting and operating instructions Setting the accelerating function (forceful closing) Note: The accelerating function (forceful closing) is only activated for the standard drive mechanism. 4.7.1 Accelerating force While an installation is in the state “without mains power” or in the operating mode MANUAL, the motor acts as an attenuator, thus guaranteeing a constant closing speed until the Closed posi- tion is reached.
ETS 64-R Mounting and operating instructions 4.7.2 Forceful closing range Upon delivery from the factory, the activation of the accelerating function (forceful closing) is pre- set (i.e. it intervenes approx. 5° before reaching the closed position). Under normal conditions, it...
Attention: For any bi-parting fire protection door, it is compulsory to mount the integrated closing sequence regulator ECO SRI (0548-172), homologated by the "Deutsche Institut für Bautechnik" Berlin (DIBt). For any bi-parting door with escape way function, a driver flap (supplied by customer) must be provided, unless this function is guaranteed by the locking system.
ETS 64-R Mounting and operating instructions ELECTRICAL CONNECTIONS Power supply Warning: Before working on the drive mechanism, make sure that the mains cable is voltage- free! The mains supply line including mains plug (with respective protection) has to be provided by customers.
Page 45
ETS 64-R Mounting and operating instructions Connect the mains supply cable as illustrated (see also wiring diagram E4-0141-713 in the appendix). Mount the side cover extensions. Mount the side covers. Program selector closer to the door hinges Strain relief Side cover extension...
PCB. Installation: The ETS 64-R is compatible with passives or actives fire alarm centrals. The settings described hereafter must only be carried out on the fire protection PCB which has been connected to the central fire alarm system.
Page 48
ETS 64-R Mounting and operating instructions Diagnostics: Fire alarm central Manual triggering The identified fire protection PCB is displayed as Smoke detector/Thermal switch follows in the diagnostic menu: no response ------------------------------------------------------------------------------------------------------------ Short-circuit R0 Relay PCB with DIP switch on position...
ETS 64-R Mounting and operating instructions External elements Mount all the required control and safety elements at their respective place. Lead the cables of the elements up to the drive mechanism (by customers). Connect the cables according to the diagram E4-0141-713_ECO (in the appendix).
ETS 64-R Mounting and operating instructions Motorized lock The swing door drive mechanism and its control unit are always configured as Master. All the commands are transmitted to this control unit. The latter then unlocks/locks the motorized lock. Attention: The motorized lock must be homologated together with the fire safety profile system!
ETS 64-R Mounting and operating instructions 5.5.2 Motorized lock with own evaluation control The motorized lock is equipped with an own evaluation control (either integrated or external). The swing door drive mechanism is configured as the Master unit and transmits a voltage free impulse for control unit of the motorized lock for relasing the latter.
ETS 64-R Mounting and operating instructions 5.5.3 Motorized lock with separate evaluation control/power pack The motorized lock is equipped with a separate evaluation control and a separate power pack ensuring the power supply. The swing door drive mechanism is configured as the Master and transmits a voltage free impulse to the control unit of the motorized lock for releasing the latter.
ETS 64-R Mounting and operating instructions COMMISSIONING Warning: During the setting-up procedure (which must only be carried out by experts), the safety devices (radar, sensors, ...) are switched off! Before initiating the setting-up procedure, it is important to make sure that neither...
Page 54
ETS 64-R Mounting and operating instructions Adjust the opening speed Vo and validate by means of OK. Adjust the closing speed Vc and validate by means of OK. If desired: Invers Program the inverse application (spring-powered opening) and validate it by pressing OK.
ETS 64-R Mounting and operating instructions Note: A renewed setting-up procedure (Teach) is required if: • the spring tension has been changed • the leaf weight has been changed • the type of rod assembly has been changed • the opening angle Ao has been changed •...
ETS 64-R Mounting and operating instructions Closing sequence control For bi-parting installations, the closing sequence control determines the order in which the door leaves are opened and closed. For the opening procedure, the earlier door leaf (Master leaf) is the first one to be opened, whereas for the closing procedure the delayed door leaf (Slave leaf) is the first one to be closed.
Page 57
ETS 64-R Mounting and operating instructions Function: The first door leaf to be put in motion for the opening procedure is the Master; by means of DubleD, this leaf is configured as MastrA. Its partner is the Slave, which is configured as SlaveA by means of DubleD.
Page 58
ETS 64-R Mounting and operating instructions Procedure: Connect both control units by means of the CAN cable 0383-194/07 (by plugging it into the socket X117). Note: The respective control and safety elements are connected to the corresponding drive mechanism. Take the Master drive mechanism into operation (see chapter 6).
ETS 64-R Mounting and operating instructions Interlock operation Procedure: Note: Both installations must be plugged Exterior side into resp. out of the same power supply. Side A Connect both control units by means of the CAN cable (by plugging it into the socket X117).
X104 X107 X103 X104 X106 X106 Sep. Stückliste anderer Nr. 3 Benennung Zeichnu ECO Schulte GmbH & Co. KG Using a permanent marker, tick off the exis- Benennung Zeichn Iserlohner Landstrasse 89 Détecteur de fumée ou thermo- Monats-Kleber D-58706 Menden...
ETS 64-R Mounting and operating instructions Mount the drive mechanism covering Material: Covering 0548-400 Aluminium Covering accessories 0548-143 Aluminium Covering 0548-303 Stainless steel Covering accessories 0548-115 Stainless steel Procedure: Mount the covering and the accessories as shown in the illustration.
ETS 64-R Mounting and operating instructions CONTROL Main switch The drive mechanism is supplied with a built-in main switch (A). This main installation switch enables you to disconnect the power supply from the drive mechanism. The door leaf then is closed from any position by means of spring power (Invers = spring opening, unless the door leaf has not been locked).
ETS 64-R Mounting and operating instructions Operating modes The following operating modes can be enabled by means of the program selector: AUTOMATIC Automatic opening via the opening elements inside/outside + Key. Automatic closing upon expiration of the adjustable hold-open time.
ETS 64-R Mounting and operating instructions Adjustings The parameters can be changed on the control unit by means of the display and the Joystick joystick. The movements of the joystick have the Display scroll following effects: • Vertical joystick movement (upward/ change downward) ...
ETS 64-R Mounting and operating instructions 7.4.2 Configuration (CONFIG) Parameter Description Setting range Default APuGo Triggering angle Push&Go (angle push&go) OFF, 2...10° ASES 1) Suppression point Safety Element stop (angle safety element stop). 45°...Ao 95° If Ao is changed, ASES is auomatically set to Ao.
ETS 64-R Mounting and operating instructions open open ASES closed closed 7.4.3 Installations with multiple door leaves (DOUBLE DOOR) Parameter Description Setting range Default Closing sequence role (Master/Slave) and interlock side (A/B) DubleD MastrA SlaveA MastrB SlaveB AoSeq Current delay angle for opening sequence control (Slave) 0..110°...
ETS 64-R Mounting and operating instructions 7.4.4 Menu navigation 0548-990/62g 0548-990-61---70g_2019.10.indd Page 68 of 95...
Page 69
ETS 64-R Mounting and operating instructions On the 1st level, the following information is shown on the display: 1st display line: The door position is represented by means of the arrows (><). Alternatively, the motion-relevant opening and safety signals are displayed. The double hash signs (##) indicate that the door is locked.
Page 70
ETS 64-R Mounting and operating instructions DIAGNOSTICS Diagnostic tools • K-I-O-R-S-E shows the inputs KEY (K), OEI (I), OEO (O), SER (R), SES (S), EMY (E). (+) stands for active, (-) for inactive. • 5.1A 95° shows the motor current and the door opening angle.
Page 71
ETS 64-R Mounting and operating instructions BLOCK/UNBLOC Lock/unlock the joystick • BLOCK Lock the joystick. For a temporary unlocking, press OK for more than 1 second. 60 seconds after the last joystick actuation, the joystick is automatically relocked. • UNBLOC Permanent unlocking of the joystick.
ETS 64-R Mounting and operating instructions SERVICE A regular service (maintenance/checking) is absolutely indispensable in order to guarantee a safe operation and long lifetime of the installation. The service must be carried out at least once a year: • by a expert (according to the following checklist) •...
Rating plate, arrow sticker, glass sticker, etc. existing? Control booklet existing and completed? Only for redundant drive mechanisms. ECO cleans all the elements of the installation provided this is necessary for the function of the installation. A general cleaning of the installation is not planned. 0548-990/62g 0548-990-61---70g_2019.10.indd...
ETS 64-R Mounting and operating instructions Fundamental checking Warning: Switch the main installation switch off on the drive mechanism! Dismount the covering of the drive mecha- nism. Check all the cable connections. Normal rods: Separate the rod arm (B) from the rotating arm (A): Pull the spherical joint (C) apart.
ETS 64-R Mounting and operating instructions TROUBLESHOOTING Warning: Electrocution hazard! Before working on any live elements, pull out the mains plug respectively switch off the main installation switch! If a malfunction occurs which might be detrimental to the safety of the users, and which cannot be eliminated without delay, the operator must be informed and if requi- red the installation shall be taken out of operation.
ETS 64-R Mounting and operating instructions 9.1.2 Operating Description Cause Elimination Checking time Reaction E10 01 Fullteach required Parameter Ao, Rod, Invers or Carry out a teach. Upon changing the dAxis changed. drive mechanism configuration. Minimum opening angle has not Check the locking/electric lock.
ETS 64-R Mounting and operating instructions 9.1.5 System Description Cause Elimination Checking time Reaction E50 01...99 System error Unexpected hard- Switch the drive mechanism off/on. Permanent. W or H or F ware or software Carry out a Factory Reset, carry out a Software Update, E51 01...99...
ETS 64-R Mounting and operating instructions Malfunction without error-no. In some cases, it will be technically impossible to display an "irregular functioning" of the instal- lation by a definite error number. An alleged error may by all means also be due to "correct" cau- ses.
ETS 64-R Mounting and operating instructions Software update via USB A software update of the ETS 64-R control unit can be easily and rapidly achieved by means of an USB memory stick. Note: Not all the USB memory sticks can be used. We thus recommend a previous testing of their function together with the ETS 64-R.
ETS 64-R Mounting and operating instructions 9.3.2 Procedure Switch off the main installation switch on the ETS 64-R. Plug the USB stick into the control unit socket X118. X118 Switch on the main installations switch on the ETS 64-R.
ETS 64-R Mounting and operating instructions SHUT-DOWN No particular measures need to be taken for de-commissioning the installation. If the swing door drive mechanism will not be used during at least 1 month, it is recommended to pull out the mains plug.
ETS 64-R Mounting and operating instructions DISPOSAL OF THE INSTALLATION An ecologically acceptable disposal of the installation is ensured if the different materials are separated and recycled. No particular measures are required for the protection of the environment. However, the relevant legal prescriptions...
The D-BEDIX is connected to the control unit ETS 64-R via a screened two-core connection cable (e.g. U72M or EIB-Y(St)Y, max. length 50 m). Only one D-BEDIX can be connected per door installation.
ETS 64-R Mounting and operating instructions 13.1.3 Operating modes With the D-BEDIX, the following operating modes can be selected by means of the corresponding symbols: AUTOMATIC Automatic operation. The installation can be locked. NIGHT The installation is locked . As opening commands, only the key-operated impulse switch is accepted.
ETS 64-R Mounting and operating instructions 13.1.5 Menu level Short and simultaneous actuation of both arrow keys (=access to the menu level). Select the desired menu item bymeans of the arrow key. Confirm by means of the OK key. Display...
ETS 64-R Mounting and operating instructions 13.1.6 Setting examples Changing the operating mode Select the desired symbol by means of the arrow key (symbol starts flashing). Confirm with the OK key (frame/bar switch over). Preselecting the operating mode An overriding switch is active and determines the operating mode (only the selection frame is visible, the bar underlines the preselected operating mode).
ETS 64-R Mounting and operating instructions Parameters (hold-open timeday) Short simultaneous actuation of the arrow keys (= access to the menu level). By means of the arrow key, select TOEx. Confirm with the OK key. By means of the arrow key, change the value.
ETS 64-R Mounting and operating instructions 13.2 KOMBI-D-BEDIX In addition to the functions of the D-BEDIX, the KOMBI-D-BEDIX contains a key-operated switch (round or profile cylinder) with the following function: Lockout of the KOMBI-D-BEDIX against unautho- rized use. Free Locked...
Open position stop piece integrated in the drive mechanism Attention: The swing door drive mechanism ETS 64-R with fire protection rating must imperatively be complemented by an open position stop piece (to be installed by customers). The purpose of this stop piece is to limit the opening motion of the door leaf, thus ensuring its reliable closing in the event of a fire.
ETS 64-R Mounting and operating instructions 13.5 Continuous covering For bi-parting installations, the two drive mechanisms can be optically connected by inserting an intermediate covering piece. Note: A fire alarm is displayed by the red LED in the side cover.
ETS 64-R Mounting and operating instructions 13.6 Optional PCBs All the optional PCBs are plugged into the control unit via a universal connector. A maximum number of two optional PCBs can be combined. Attention: All optional PCBs must only be plugged into/removed from the control unit after the dive unit has been disconnected from the power supply source! 13.6.1...
ETS 64-R Mounting and operating instructions 13.6.2 Radio PCB A radio control PCB can be plugged into the control of the drive mechanism. Using a hand-held radio transmitter/radio transmitter/radio code lock, this PCB can be programmed with a code, upon which the drive mechanism can be controlled via this element.
ETS 64-R Mounting and operating instructions 13.7 LZR-FLATSCAN In the event of swing doors, the FLATSCAN is mounted on the moving leaf, on the upper leaf cor- ners (as close as possible to the secondary closing edge). The FLATSCAN can only be used in pairs! Master and Slave are connected among each other (see wiring diagram in the appendix).
ETS 64-R Mounting and operating instructions APPENDIX The following documents are added as an appendix to this instructions: Wiring diagram ...................... E4-0141-713_ECO Wiring diagram Fire protection PCB ............... E4-0141-714_ECO Wiring diagram Relay PCB ..................E4-0141-715_ECO Wiring diagram Flatscan LZR .................. E4-0142-149_ECO Wiring diagram motorised locks ................