hit counter script

Siemens FS720 Mounting & Installation page 229

Fire detection system
Table of Contents

Advertisement

Remote (mimic) EVAC, 20 zones
RS485 (FCA2002-A1)
Usys (Peripherieboard 2-/4-Loop)
Building Technologies
Fire Safety
Example of using the diagram
Two remote EVAC-NL indicators, one with 20 zones, the other with 30 zones, are
supplied by the periphery board of the same ↑ station.
20 pin
Figure 138: Wiring example for calculating the cable resistance
Number of zones via the same supply cable: 50 (20 from panel 1 and 30 from
panel 2)
According to the diagram, this results in the following values for the EVAC-NL
mimic display driver:
Maximum cable resistance R' is 10 Ω (curve 1)
Maximum current is 0.85 A (curve 4)
In the same way, this would result in the following for a remote EVAC-NL indicator:
Maximum cable resistance R' is 22 Ω (curve 2)
Maximum current is 0.4 A (curve 3)
Installing, exchanging and connecting modules
Remote EVAC-NL and EVAC-NL mimic display driver
Remote (mimic) EVAC, 30 zones
mimic display driver
FT2003-N1
X4
FTI2002-N1
Connector
board
X2
X3
X1
X5
mimic display driver
FT2003-N1
X4
FTI2002-N1
Connector
board
X2
X3
X1
X5
mimic display driver
FT2003-N1
X4
FTI2002-N1
Connector
board
X2
X3
X1
X5
FTO2007-N1
X402
Operating unit
34 pin
'Master'
X400
X1
Synoptic panel
3 x 34 pin
FTO2007-N1
X402
Operating unit
34 pin
X400
'Slave'
X1
Synoptic panel
3 x 34 pin
FTO2007-N1
X402
Operating unit
34 pin
'Slave'
X400
X1
Synoptic panel
3 x 34 pin
229 | 248
A6V10210390_m_en_--
2018-08-29
7

Advertisement

Table of Contents
loading

Table of Contents