Installing, exchanging and connecting modules
7
Remote EVAC-NL and EVAC-NL mimic display driver
7.32.7 Connection FTO2007-N1
7.32.7.1 Adjustment elements
238 | 248
Building Technologies
Fire Safety
The EVAC-NL indicator is configured with the switch S20.
Setting for one or the first EVAC-NL
Switch S20
1
2
3
4
S0
S1
S2
Master Syn (Empty)
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
X
X
X
ON
Blank fields = Switch in 'OFF' position
X = Switch position according to addresses 1 to 5
If working with a single EVAC-NL indicator (10 zones) and if working with the first
1
EVAC-NL indicator, S20/4 (Master) must always be set to ON. If used in the EVAC-
NL mimic display driver, the S20/5 (Syn) switch must also be ON.
Each address can be assigned only once per ↑ station.
The factory setting is always made for the application in question.
Setting for the second and/or any subsequent EVAC-NL indicator
Switch S20
1
2
3
4
S0
S1
S2
Master Syn (Empty)
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
X
X
X
OFF
Blank fields = Switch in 'OFF' position
X = Switch position according to addresses 1 to 5
2 EVAC-NL indicators must not be operated on the same address (per station).
1
On the second or any subsequent indicator, the address must always be set 1
higher (slave). If used in the EVAC-NL mimic display driver, the S20/5 (Syn) switch
must also be ON.
Each address can be assigned only once per station.
The factory setting is always made for the application in question.
Meaning
5
6
OFF
Device address 1
OFF
Device address 2
OFF
Device address 3
OFF
Device address 4
OFF
Device address 5
ON
Mimic display outputs are actuated
and polled (LED, keys and key switch)
Meaning
5
6
OFF
Device address 1
OFF
Device address 2
OFF
Device address 3
OFF
Device address 4
OFF
Device address 5
ON
Mimic display outputs are actuated
and polled (LED, keys and key switch)
1
1
A6V10210390_m_en_--