The B426 Ethernet Communication Module is a four-wire powered SDI, SDI2, or Option bus device that provides two-way communication with compatible control panels over IPv4 or IPv6 Ethernet networks. The B426 on-board switch determines the bus address of the device. Configuration of the B426 is performed through the B426 configuration web pages. On SDI2 control panels, configuration can also be done on the keypad or through Remote Programming Software (RPS).
Callout ― Description |
1 ― Ethernet RJ-45 port |
2 ― Yellow LINK LED |
3 ― Green 100MB LED |
4 ― Address switch |
5 ― Heartbeat LED (blue) |
6 ― Data bus communication LEDs (TX and RX) |
7 ― SDI2 terminal strip (to control panel or additional modules) |
8 ― SDI2 interconnect wiring connectors (to control panel or additional modules) |
9 ― Tamper switch connector |
One address switch determines the address for the B426 Conettix Ethernet Communication Module. The control panel uses the address for communications. Use a slotted screwdriver to set the address switches.
NOTICE!
The module reads the address switch setting only during power up. If you change the switches after you apply power to the module, you must cycle the power to the module in order for the new setting to be enabled.
Set the address switches per the control panel configuration. If multiple B426 modules reside on the same system, each B426 module must have a unique address.
Figure 2.1: Address switch
The B426 address switch provides a ones value for the module's address. Figure 2.1 shows the address switch setting for address 1. Refer to Table 2.1 for panel-specific settings.
Control panels | Switch position | B426 address | Bus type | Function |
For web-based configuration | 0 | Configurable | Any | Web-based configuration |
GV4 and B Series | 1 | 1 | SDI2 | Automation, Remote Programming, or Reporting |
GV4 Series | 2 | 2 | ||
GV4/GV3/, GV2 Series, G Series v6.3 or higher | 3 | 80 | SDI | Automation |
4 | 88 | Remote programming or Reporting | ||
GV4 and GV3 Series | 5 | 92 | ||
FPD-7024 | 9 | 250 | Option |
Table 2.1: Address switch settings
After you set the address switches for the proper address, install the module in the enclosure, and then wire it to the control panel and other devices.
NOTICE!
Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage.
Callout ― Description |
1 ― Module with mounting bracket installed |
2 ― Enclosure |
3 ― Mounting screws (3) |
For instructions on this optional switch, refer to the Conettix Ethernet Communication Module (B426) Installation and Operation Guide (P/N: F01U266226) and the EZTS Cover and Wall Tamper Switch Installation Guide (P/N: F01U003734).
When you wire a B426 to an SDI or SDI2 control panel, you can use either the module's terminal strip labeled R, Y, G, B (PWR, A, B, COM) or the module's interconnect wiring connectors (wire included). Figure 1.1 indicates the location of both the terminal strip and the interconnect connectors on the module. Refer to Figure 3.2.
NOTICE!
Use either the terminal strip wiring or interconnect wiring connector to the control panel. Do not use both. When connecting multiple modules, you can combine terminal strip and interconnect wiring connectors in series.
Run the wires from the module to the data bus terminals on the compatible control panel. Refer to Figure 3.2.
Figure 3.2: Wiring to the control panel (GV4 Series and FPD-7024 control panel shown)
Callout ― Description |
1 ― SDI2 control panel. For SDI control panels, wire R, Y, G, B to the SDI bus. |
2 ― Interconnect wiring connectors |
3 ― To Ethernet network |
4 ― Terminal strip wiring |
5 ― Interconnect cable (P/N: F01U079745) (included) |
6 ― Option bus control panel |
Configure the B426 using one of the methods described in this section for your control panel type.
NOTICE!
By default, when connecting a field replacement B426 to an existing SDI2 Control Panel, the panel overrides the module settings. To keep custom module settings when you connect a module to a configured SDI2 control panel, you must disable Panel Programming using web-based configuration, prior to connecting to the SDI2 bus.
An SDI2-compatible control panel automatically configures a newly connected module.
Configure for an SDI or option bus control panel using one of the methods described in this section.
When installing under the following conditions, the B426 needs no further configuration:
For installations where additional non-default settings are required, a web-based configuration menu is available.
Determine the module's hostname or IP address by one of the following methods:
NOTICE!
Before proceeding, ensure that the web browser is not configured to use a proxy server. Refer to the browser's online help for instructions on disabling proxy service.
To use web-based configuration (B426 configuration web pages):
NOTICE!
Before browsing to a new settings page, you must click OK to save edited values.
The B426 module includes the following on-board LEDs to assist with troubleshooting issues (refer to Figure 1.1 for the location of the LEDs):
Flash pattern | Function |
Flashes once every 1 sec | Normal state: Indicates normal operation state. |
3 quick flashes every 1 sec | Communication error state: Indicates (the module is in a "no communication state") resulting in an SDI2 communication error. |
On Steady | LED trouble state: Module is not powered (for OFF Steady only), or some other trouble condition prohibits the module from controlling the heartbeat LED. |
Off |
Table 4.1: Heartbeat LED descriptions
Flash pattern | Function |
RX (Receive) flashes | Occurs when the control panel bus receives a message. |
TX (Transmit) flashes | Occurs when the control panel bus sends a message. |
Table 4.1: Data bus LEDs descriptions
LINK (yellow) flash pattern | 100mb (green) flash pattern | Function |
Off | Off | No Ethernet link |
On Steady | Off | 10 BASE-T link |
Flash | Off | 10 BASE-T activity |
On Steady | On Steady | 100 BASE-T link |
Flash | On Steady | 100 BASE-T activity |
Table 4.1: Ethernet LINK and 100mb LEDs descriptions
To show the firmware version using an LED flash pattern:
Refer to Figure 6.1 for an example of flash patterns.
Figure 6.1: Firmware LED flash patterns
When the tamper switch is activated (closed to open), the heartbeat LED stays OFF for 3 sec before indicating the firmware version. The LED pulses the major, minor, and micro digits of the firmware version, with a 1 sec pause after each digit.
Flashing patterns do not start until the tamper is open (short is removed). In the following is an example, the version 1.4.3 shows as LED flashes:
[3 sec pause] *___****___*** [3 sec pause, then normal operation].
Dimensions | 59.5 mm x 108 mm x 16 mm (2.19 in x 4.25 in x 0.629 in) |
Voltage (operating) | 12 VDC nominal |
Current (maximum) | 100 mA max |
Connectors | LAN/WAN: RJ-45 modular port (Ethernet) |
Ethernet cable | Category 5 or better unshielded twisted pair, 100 m (328 ft) max length |
Interface | IEEE 802.3 |
Data bus wire size | 1.02 mm to 0.65 mm (18 AWG to 22 AWG) |
Data bus wire length | Maximum distance - Wire size: 150 m (500 ft) - 0.65 mm (22 AWG) 300 m (1000 ft) - 1.02 mm (18 AWG) |
Web browser | Microsoft Internet Explorer 6 or higher; Mozilla Firefox 3 or higher |
Compatibility | D9412, D7412, D7212, D9112 G Series Version 6.3 or higher GV2 Series GV3 Series GV4 Series B5512/B4512/B3512 |
Copyright
This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Bosch B426 - Conettix Ethernet Communication Module Installation Guide
Advertisement
Thank you! Your question has been received!
Need Assistance?
Do you have a question about the B426 that isn't answered in the manual? Leave your question here.