Siemens SIMATIC IPC RW-545A Operating Instructions Manual

Siemens SIMATIC IPC RW-545A Operating Instructions Manual

Industrial pc workstation
Table of Contents

Advertisement

Quick Links

Workstation SIMATIC IPC RW-545A
SIMATIC
Industrial PC
Workstation
SIMATIC IPC RW-545A
Operating Instructions
08/2023
A5E52943278-AA
Preface
Product description
Safety instructions
Unpacking and installing
the device
Connecting the device
Commissioning the device
Operating the device
Expanding and assigning
parameters to the device
Device maintenance and
repair
Technical specifications
Dimension drawings
Standards and approvals
Hardware description
Technical support
Markings and symbols
1
2
3
4
5
6
7
8
9
10
11
A
B
C

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC IPC RW-545A

  • Page 1 Workstation SIMATIC IPC RW-545A Preface Product description SIMATIC Safety instructions Unpacking and installing the device Industrial PC Workstation SIMATIC IPC RW-545A Connecting the device Commissioning the device Operating Instructions Operating the device Expanding and assigning parameters to the device Device maintenance and...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Preface

    • Service and maintenance of industrial PCs General knowledge in the field automation control engineering is recommended. Range of validity of these operating instructions These operating instructions are valid for all order versions of the SIMATIC IPC RW-545A. History Currently released versions of these operating instructions:...
  • Page 4 Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 5: Table Of Contents

    Safety instructions on transport and storage............... 40 Safety instructions for assembly ..................42 Safety instructions on ambient and environmental conditions ..........44 Safety instructions for I/O devices ..................46 Safety instructions on device and system extensions ............47 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 6 Setting up the onboard RAID system in the firmware (Create Volume) ........ 79 6.4.3.2 Monitoring the onboard RAID system with "Intel® Optane™ Memory and Storage Management" ........................81 6.4.3.3 Integrating a new drive into an onboard RAID system ............82 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 7 Install the internal drive on the side panel of the device ............ 121 7.6.5 Install M.2 NVMe SSD....................... 123 Device maintenance and repair ......................125 Safety instructions for repairs ................... 125 Maintenance intervals ...................... 125 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 8 Technical specifications of the plug connectors for the power supply of graphics cards ..157 9.10 Technical specifications of the telescopic rails ..............157 9.11 Technical specifications of the operating systems ............. 158 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 9 Troubleshooting ......................176 B.2.1 Problems with device functions ..................176 B.2.2 Problems when booting the device .................. 177 B.2.3 Problems with RAID systems .................... 178 B.2.4 Problems when using expansion cards ................178 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 10 Markings and symbols ........................181 Overview ......................... 181 Symbols for safe use and disposal ..................181 Symbols for operator controls ..................181 Symbols of certificates and approvals ................182 Interface icons ......................... 183 Index ..............................185 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 11: Product Description

    • Supplied in printed form with the device • Link and QR code to the online form for the quality control notification in the SIEMENS After Sales Information System (ASIS) • Operating Instructions of the device • Installation of the device •...
  • Page 12: Product Highlights

    (http://w3.siemens.com/mcms/au tomation/en/industrielle- kommunikation/Seiten/Default.as Product highlights The SIMATIC IPC RW-545A is a high-performance industrial PC as workstation in 19" rack format (4 U). It is perfectly suited for high-performance industrial PC applications. Device view Note Depending on the configuration ordered the features and illustrations described in this manual may differ from the features of your device.
  • Page 13 RAID configurations and unique numbering • Status display (front LEDs) for Ethernet; alarm display for fan, temperature, watchdog and drives in RAID configurations • Remote control and remote maintenance through iAMT (Intel® Active Management Technology) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 14 • Can be used in different positions with telescopic rails or as an industrial tower PC (tower kit optional) • Pre-installed and activated operating systems: – Windows 10 IoT Enterprise 2021 LTSC (64-bit) • Fast restoration of the delivery state by restoring from USB stick Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 15: Scope Of Application

    1.3 Scope of application Scope of application The SIMATIC IPC RW-545A offers system integrators, electrical panel builders, plant builders and machine builders a 19" rack PC platform for high-performance applications and IT applications on the control and cell level for: •...
  • Page 16: Drive Cage

    You can install drives in removable trays, in which the drives are easily accessible from the outside without opening the device. The removable trays can be locked, thus protecting the drives from unauthorized access. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 17 Components of the removable tray Status display (Page 30) Status display (Page 30) Number of the mounting location (here: Mounting location 0) Lock See also Installation options for drives with drive cage type A (Page 104) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 18: Drive Cage Type B

    3.5" drive in the assembly kit • 5.25" drive or 5.25" component Cover (if no drive is installed) or drive cover Cover See also Installation options for drives with drive cage type B (Page 114) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 19: Rear Of The Device

    • "Connection of power supply unit 550 W (Page 22)" • "Connection of power supply unit 850 W (Page 23)" • "Connection of power supply unit 700 W (2 modules, each 700 W, redundant) (Page 23)") Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 20: Device Ports

    SuperSpeed backwards compatible to USB 3.0 / 2.0 / 1.1; each 900 mA / high current Sum of the currents on the USB interfaces of the device (including the internal USB interfaces) ≤ 3 A Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 21: Connections On The Rear Of The Device

    USB 3.0 / 2.0 / 1.1; each 1500 mA / high current • (X63) ⑩ USB 3.2 Gen2 Type A (10 Gbps) Backwards compatible to USB 3.0 / 2.0 / 1.1; each 900 mA / high current • (X60) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 22: Connection Of Power Supply Unit 550 W

    "Connecting several monitors (multi-monitoring) (Page 63)". You can find information on the graphics cards under "Technical specifications of graphic (Page 152)". 1.4.4.3 Connection of power supply unit 550 W Socket for power plug Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 23: Connection Of Power Supply Unit 850 W

    1.4 External design of the device 1.4.4.4 Connection of power supply unit 850 W Socket for power plug 1.4.4.5 Connection of power supply unit 700 W (2 modules, each 700 W, redundant) Sockets for power plug Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 24: Operator Controls

    Reset button ② The reset button is for the emergency when the device can no longer be operated. You can find information on the hardware reset under "Switching off the device (Page 74)" Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 25: Alarm Reset Button For Power Supply Unit 700 W (2 Modules, Each 700 W, Redundant)

    Risk of electric shock The on-off switch does not fully disconnect the device from the line voltage. You also need to observe the notes and information under "Switching off the device (Page 74)". On-off switch Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 26: On-Off Switch For Power Supply Unit 850 W

    The redundant power supply unit 700 W does not have an on-off switch. To completely disconnect the device from the mains voltage, follow the instructions under "Switching off the device (Page 74)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 27: Status Displays

    Data traffic ⑥ WATCHDOG Watchdog status Not activated (function GREEN Activated currently not Expired available) ⑦ TEMP Temperature status No error Possible causes: • CPU temperature is critical • Device temperature is critical Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 28 Memory and Storage You can find information under "RAID1 Management" software system (Page 78)" differs from this numbering. See important note under "Display of a defective drive of an onboard RAID system (Page 78)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 29: Status Displays Of The Lan Ports

    • Data transfer active GREEN (Blinking then steady) • Ready to wake up from S5 mode LED 2 Data transmission rate • 10/100 Mbps ORANGE • 1000 Mbps GREEN • 2500 Mbps Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 30: Status Displays Of Power Supply Unit 700 W (2 Modules, Each 700 W, Redundant)

    Device is switched on and a drive is installed ② Activity Status of the drive ORANGE • Drive is active • Drive is not active See also Drive cage type A (Page 16) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 31: Internal Construction Of The Device

    Drive cage (here in the example: Drive cage type A or type B) ⑥ Guide rail for long expansion cards ⑦ Motherboard ⑧ Expansion card slots ⑨ Slot brackets (numbering of the slots for expansion cards on the enclosure) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 32: Accessories And Replacement Parts

    Accessories and replacement parts 1.6.1 Hardware accessories Accessories from Siemens are available for your device. These are not included in the scope of delivery. Obtaining accessories from the SIEMENS Industry Mall You can find additional information in the online ordering system Industry Mall (https://mall.industry.siemens.com).
  • Page 33 DP adapter 3 adapters 6ES7648-3AJ00-1XA0* Mini DisplayPort to DisplayPort Available as single-pack or 3- pack* * Included in scope of delivery of NVIDIA T400 and NVIDIA RTX A2000 graphics cards. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 34 5.25" mounting frame for 5.25" mounting frame for removable tray. A5E35804114 HDD / SSD removable tray You can use a 2.5 "or a 3.5" drive in the removable tray. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 35: Software Accessories

    • Catalog and ordering system for Automation and Drives: Industry Mall (https://mall.industry.siemens.com). First select your region here and then navigate to the desired topic area. • Industrial automation technology portfolio: Products & Services (https://www.siemens.com/global/en/products/automation/pc-based.html) Area: "SIMATIC IPC software and accessories". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 37: Safety Instructions

    Touching these areas or components can cause death or serious physical injury. • Disconnect the control cabinet from the power supply before opening it. • Ensure that the power to the control cabinet cannot be turned on accidentally. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 38 "Switching off the device (Page 74)". • Do not touch power cables and data transmission cables during a thunderstorm. • Keep sufficient distance from electric cables, distributors, systems, etc. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 39 • Do not short-circuit the battery. • Do not reverse the polarity of the battery. • Do not heat the battery over 100 °C. • Protect the battery from direct sunlight, moisture and condensation. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 40: Safety Instructions On Transport And Storage

    Risk of physical injury The device is heavy and may injure persons and be damaged if it falls. • Use the handles on the front panel of the device to carry and lift the device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 41 • Do not expose the device to direct heat radiation from a heating device. • If condensation develops, wait approximately 12 hours or until the device is completely dry before switching it on. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 42: Safety Instructions For Assembly

    There is a risk of overheating and personal injury. Note the following instructions and information under: • "Climatic and mechanical environmental conditions (Page 148)" • "Safety instructions on ambient and environmental conditions (Page 44)" Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 43 Touching these areas or components can cause death or serious physical injury. • Disconnect the control cabinet from the power supply before opening it. • Ensure that the power to the control cabinet cannot be turned on accidentally. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 44: Safety Instructions On Ambient And Environmental Conditions

    • When the device is operated in severe environments which are subject to caustic vapors or gases, ensure sufficient clean air is provided. • Clean the enclosure surface with a damp cloth. • Make sure that no water gets inside the device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 45 • Remove radiation sources from the environment of the device. • Switch off radiating devices. • Reduce the radio output of radiating devices. • Read the information on electromagnetic compatibility. • Read the information in the technical specifications. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 46: Safety Instructions For I/O Devices

    • Switch off the affected device and then insert the power plug. • Connect all cables from the system to the device and switch all components of the system to active before starting the measurement. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 47: Safety Instructions On Device And System Extensions

    Contact your technical support team (Page 175) or the point of sale to find out which device and system expansions are suitable for installation. • Note the Information on electromagnetic compatibility (Page 165). Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 48 If you install or exchange system expansions and damage your device, the warranty becomes void. It is therefore essential that you observe the information under "Open the device (Page 93)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 49 • UL approval of the device only applies when the UL-approved components are used according to their "Conditions of Acceptability". • We are not liable for functional limitations caused by the use of third-party devices or components. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 50 Safety instructions 2.6 Safety instructions on device and system extensions Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 51: Unpacking And Installing The Device

    You can find information on ordered Microsoft® Windows® operating systems under: Important instructions and manuals for operating the device (Page 11) or Technical specifications of the operating systems (Page 158). Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 52: Checking The Delivery Package

    Printed documents • Quick Install Guide for the device with link and QR code to the online form for quality control (quality control notification) in the SIEMENS After Sales Information System (ASIS) • Product Information "Important notes on your device"...
  • Page 53: Device Identification Data

    The following illustrations are examples. The data of your device may differ from the data in these examples. Nameplate The nameplate is located inside the front door. Example: SIMATIC IPC RW-545A nameplate (the information on the nameplate is device- specific) Identification data of the device ①...
  • Page 54: Mounting The Device

    The device can be installed horizontally in control cabinets and 19" rack systems. When telescopic rails are used for mounting, the device can be withdrawn fully from the cabinet or rack. Note the information in "Technical specifications of the telescopic rails (Page 157)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 55: Securing The Device

    It is essential that you follow the installation and mounting instructions under: • Safety instructions for assembly (Page 42) • Safety instructions on ambient and environmental conditions (Page 44) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 56 You can find the dimensions for the drill holes under "Dimension drawing for drill holes for telescopic rails (Page 162)". You can find detailed information on the telescopic rails under: "Technical specifications of the telescopic rails (Page 157)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 57: Connecting The Device

    The power supply cable and the device plug must bear the prescribed markings. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 58: Connection Of Equipotential Bonding Line

    • The permissible rated voltage of the device must match the local mains voltage. • Operate the device only in grounded electricity grids (TN networks in accordance with VDE 0100 Part 100 or IEC 60364-1). • Operation via non-grounded or impedance-grounded grids is prohibited. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 59 5. To prevent unintentional removal of the power plug, secure the power plug on the device. 6. Remove the retaining screw ①. 7. Screw on the power plug latch ② with the fixing screw ①. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 60: Connecting The Power Supply Unit 850 W

    3. Insert the power cable in the electrical socket. 4. Switch on the device at the on-off switch (position |). 5. To prevent unintentional removal of the power plug, secure the power plug on the device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 61: Connecting The Power Supply Unit 700 W (2 Modules, Each 700 W, Redundant)

    • For control cabinet mounting: Use a central, easily accessible AC circuit breaker close to the device, if possible. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 62: Connecting I/O Devices

    1. Connect the I/O devices to the respective interfaces. Information on the position of the interfaces is available in "Device ports (Page 20)". 2. Secure the cables (Page 72) with a strain relief. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 63: Connecting Audio Devices

    You will find 3 additional connection sockets on the rear of the device for connecting monitors to the optional NVIDIA T400 graphics card. • 3 x mDP (Mini DisplayPort) At these connection sockets, you can use adapters to connect monitors to other graphics ports. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 64 Monitor 6 (DisplayPort) Monitor 7 (DisplayPort) Labeling on the device via adapter, see "Hardware accessories (Page 32)" Requirement • You have observed the information in the following sections: "Connecting external devices (Page 62)" Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 65: Connecting Monitors For Using The Nvidia Rtx A2000 Graphics Card

    You can find information on the connection sockets on the rear of the device under: "Device ports (Page 20)". You can find information on the adapters under "Hardware accessories (Page 32)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 66 Monitor 7 (DisplayPort) Monitor 8 (DisplayPort) Labeling on the device via adapter, see "Hardware accessories (Page 32)" Requirement • You have observed the information in the following sections: "Connecting external devices (Page 62)" Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 67: Connecting Monitors For Using The Nvidia Rtx A4000 Graphics Card

    • 4 x DisplayPort You can find information on the connection sockets on the rear of the device under: "Device ports (Page 20)". You can find information on the adapters under "Hardware accessories (Page 32)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 68 Monitor 7 (DisplayPort) Monitor 8 (DisplayPort) Labeling on the device via adapter, see "Hardware accessories (Page 32)" Requirement • You have observed the information in the following sections: "Connecting external devices (Page 62)" Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 69: Connecting Monitors For Using The Nvidia Rtx A5000 Graphics Card

    • 4 x DisplayPort You can find information on the connection sockets on the rear of the device under: "Device ports (Page 20)". You can find information on the adapters under "Hardware accessories (Page 32)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 70 Monitor 7 (DisplayPort) Monitor 8 (DisplayPort) Labeling on the device via adapter, see "Hardware accessories (Page 32)" Requirement • You have observed the information in the following sections: "Connecting external devices (Page 62)" Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 71: Connecting The Device To Networks

    Control level. Additional information is available under SIMATIC NET (http://w3.siemens.com/mcms/automation/en/industrielle- kommunikation/Seiten/Default.aspx). The software package and the documentation are not included in the scope of delivery Additional information You can find additional information on the Internet at: Technical support (https://support.industry.siemens.com) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 72: Securing The Cables

    4. Fasten the cables to the corresponding openings in the strain relief ④ using simple cable ties. Example: Cable fastened to strain relief with cable ties Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 73: Commissioning The Device

    1. Select: "Advanced > Power Management > Restore AC after Power Loss". 2. Assign the "Always on" value to the firmware setting "Restore AC after Power Loss". See also Important instructions and manuals for operating the device (Page 11) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 74: Switching Off The Device

    • Then pull out the power plug or operate the central AC circuit breaker if installed in a control cabinet. Therefore, when installing the device in a control cabinet, ensure that the AC circuit breaker is easily accessible. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 75 Hardware reset with reset button: • Press the reset button. – The device switches off and on again. Information on the position of the buttons is available under "On-off button and reset button (Page 24)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 76 Commissioning the device 5.3 Switching off the device Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 77: Operating The Device

    To connect several monitors to the device at the same time (multi-monitoring), you can install a graphics card. You can find information on this here: • Connecting several monitors (multi-monitoring) (Page 63) • Installing a graphics card (Page 102) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 78: Drive Configurations

    Numbering of the drives for "Intel® Optane™ Memory and Storage Management" and the device Note Different numbering of the drives Note the different numbering of the drives for "Intel® Optane™ Memory and Storage Management" and the device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 79: Onboard Raid1 System: Installation Options For Sata Drives

    Memory and Storage Management" software. Requirement • The drives required for the onboard RAID system are built into the device, see information under: – Onboard RAID1 system: Installation options for SATA drives (Page 79) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 80 – In the list, the mounted drive is marked with an "X" ②. – You can find the assignment of the drive to the mounting location in the device ③ in front of the drive model designation. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 81: Monitoring The Onboard Raid System With "Intel® Optane™ Memory And Storage Management

    RAID system (Page 78)". 2. Right-click on a drive from the list or on "Volume". Status displays are shown for functions and components of the drives or the onboard RAID system. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 82: Integrating A New Drive Into An Onboard Raid System

    Configure the mounted drive under "Create Raid Volume". Mount new drive during operation in the onboard RAID system (after an error has occurred) Requirement The system is configured to mount new drives manually (not automatically), see above. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 83 4. From the drive information, select the function "Mark as spare" ③. The drive is mounted to the onboard RAID system and appears in the mounted drives area. See also Data synchronization in the RAID system (Page 84) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 84: Data Synchronization In The Raid System

    Monitoring of the device 6.5.1 Monitoring functions Note No support of monitoring functions by SIMATIC DiagBase or SIMATIC DiagMonitor The SIMATIC DiagBase and SIMATIC DiagMonitor software do not support the monitoring functions of this device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 85 The power supply units do not report a fan error. If the fan of the power supply unit fails or is defective, no fan alarm is output. The device switches off automatically to protect against overheating. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 86: Remote Maintenance Of The Device

    Device requirements for remote maintenance with Intel® AMT The following device requirements must be met for using Intel® Active Management Technology (iAMT): • Processor that supports iAMT technology • Connection to the network Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 87: Activate Intel® Amt

    4. Assign the "Enabled" value to the firmware setting "AMT BIOS Features". 5. Press the button <F4> (Save & Exit) and confirm the subsequent dialog with <Y>. 6. Switch off the device or restart it. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 88: Logging Onto Mebx (Assigning Password)

    – A special character . ! @ # $ % ^ & * Note The underscore and blank space are valid password characters but do not increase password complexity. 7. Now configure the Intel® AMT functions in the Options of the MEBx (Page 89). Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 89: Configuring The Amt Functions In The Options Of The Mebx

    4. Assign the "Enabled" value to the firmware setting "Unconfigure ME". 5. Press the button <F4> (Save & Exit Setup) and confirm the subsequent dialog with <Y>. 6. Switch off the device or restart the device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 90: Disabling Intel® Amt Access To The Firmware/Bios Settings

    Use of the Trusted Platform Module is subject to legal restrictions in some countries and is not permitted there. • Always observe the respective import restrictions of the country in which the device will be used. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 91 6.7 Trusted Platform Module (TPM) Activating the Trusted Platform Module You can find information on activating the Trusted Platform Module in the detailed firmware/BIOS description in "Important instructions and manuals for operating the device (Page 11)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 92 Operating the device 6.7 Trusted Platform Module (TPM) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 93: Expanding And Assigning Parameters To The Device

    2. Unplug all connecting cables. 3. Open the front panel. (Page 77) 4. Unscrew the locking screw of the enclosure cover ①. 5. Push the enclosure cover back. 6. Lift up and remove the enclosure cover. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 94: Installing And Removing Expansion Cards

    ⑤ from the card retainer and install it in the opposite hole. If you are installing a low-profile expansion card, use one of the longer card holders that are shipped with the device for mounting. 10.Close the device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 95: Removing Expansion Cards

    The memory transaction rate depends on the combination of memory modules used. Depending on the combination of memory modules used, the actual memory transaction rate can take the following values due to the system: – 4400 MT/Sec. – 4000 MT/Sec. – 3600 MT/Sec. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 96 • In case of operating errors, it may be sufficient to remove one or two memory modules or to use a memory module with lower capacity so that the physical memory expansion on the motherboard and the reserved memory of the expansion card do not overlap. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 97: Installing Memory Modules

    • Memory module 1: DIMM_A1 slot • Memory module 2: DIMM_A2 slot • Memory module 3: DIMM_B1 slot • Memory module 4: DIMM_B2 slot The slots of the memory modules are labeled on the motherboard. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 98 7. To prevent tilting, press evenly on both sides of the memory module ② until the lock audibly engages. 8. Close the device. Display of a changed memory configuration A changed memory allocation is automatically recognized when the device is switched on. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 99: Removing Memory Modules

    2. Open the device. Be sure to follow the important instructions under "Open the device (Page 93)". 3. To obtain better access to the memory modules, remove expansion cards (Page 95) if required. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 100: Connecting A Usb Stick To The Internal Interface

    2. Open the device. Be sure to follow the important instructions under "Open the device (Page 93)". 3. Insert the USB stick into the socket of the internal USB interface on the motherboard (Page 167). Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 101 (Page 19)". 6. Slide the bar of the retainer ③ onto the USB stick. 7. Fix the retainer by turning the screw ② on the guide rail. 8. Close the device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 102: Installing And Removing A Graphics Card

    You can find information on this in the firmware description of the device, see "Important instructions and manuals for operating the device (Page 11)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 103 2. To open the firmware settings, press the <Del> or <Esc> button during the boot phase, when a boot message appears. 3. Select "Advanced" > "Graphics Configuration". 4. Assign the "Auto" value to the firmware setting "Primary Display". See also Service and support (Page 175) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 104: Removing A Graphics Card

    You can install up to six drives at the following bays in the drive cage type A and on the side panel of the device. Note The 4 SATA connectors on the motherboard of the device support the use of 4 drives. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 105 2 x internal in the device • 2 x HDD inside on the side panel of the device (Page 121) 1 If more than 4 drives are used, an additional controller is required Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 106: Change 2.5" And 3.5" Drive In Removable Tray

    Fully disconnect the device from the line voltage, see "Switching off the device (Page 74)". 2. Open the front panel (Page 77). 3. Open the lock of the removable tray with the appropriate key. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 107 Ensure that the removable tray fits tightly in the drive cage. 11.Close the tray bracket. 12.Lock the removable tray with the key. Note The removable tray must always be locked to ensure reliable operation of the devices with removable trays. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 108: Installing A 5.25" Mounting Frame For Removable Tray

    – Press on the surfaces ① on the two side mounting bars ② of the 5.25" component. – Press and hold surface ① to push the 5.25" component forward out of the drive holder ④. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 109 9. Make sure that the removable tray is firmly seated in the 5.25" mounting frame. 10.Close the tray bracket. 11.Lock the removable tray with the key. 12.Close the device. 13.Connect the power supply. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 110: Installing A Backplane For Removable Tray

    1. Fully disconnect the device from the line voltage, see "Switching off the device (Page 74)". 2. Open the device. Be sure to follow the important instructions under "Open the device (Page 93)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 111 5. On the front of the drive cage, remove the cover ③, which may be located to the right of the cover ②. 6. Remove all existing removable trays until the drive cage is freely accessible. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 112: Removing A Backplane For Removable Tray

    A and is equipped with interfaces for data cables to the motherboard. This enables the convenient connection of the data cables from the motherboard to the drive in the removable tray at these interfaces. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 113 3. Unlatch the backplane by firmly pressing on the latches ② in the direction of the arrow and simultaneously pressing on the ejector ③. 4. Remove the unlatched backplane board ④ by turning it upwards from the brackets and removing it from the drive cage. 5. Close the device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 114: Installing Drives In Drive Cage Type B

    2 x internal in the device • 2 x HDD inside on the side panel of the device (Page 121) If more than 4 drives are used, an additional controller is required Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 115 You can implement the following drive configurations in the drive cage type B and on the side panel of the device. • Non-RAID system • RAID1 system • RAID5 system • RAID1 system with hot spare drive • RAID5 system with hot spare drive Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 116: Change 2.5" And 3.5" Drive In Assembly Kit For 5.25" Tray

    1. Fully disconnect the device from the line voltage, see "Switching off the device (Page 74)". 2. Open the device. Be sure to follow the important instructions under "Open the device (Page 93)". 3. Remove all power supply and data cables from the drive. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 117 6. Remove the left and right drive mounting bars ② and the drive cover③ from the drive. Note: The drive cover is labeled "L" ④ and "TOP" ⑤. The drive mounting bars are labeled "L" and "R" respectively. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 118 10.Attach the left and right drive mounting bars ② on the drive bay ⑥. 11.Slide the drive bay evenly and without tilting 3/4 (not completely) into the guide rail of the drive cage. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 119: Installing A 5.25" Drive

    1. Fully disconnect the device from the line voltage, see "Switching off the device (Page 74)". 2. Open the device. Be sure to follow the important instructions under "Open the device (Page 93)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 120 6. Slide the new drive with the drive mounting bars evenly backwards into the guide rails of the drive cage and without tilting, until it clicks into place. 7. Close the device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 121: Install The Internal Drive On The Side Panel Of The Device

    2. Screw from outside the drive bay plate on the inside to the side panel of the enclosure, at position ① or position ②. The SATA connections each lie in the middle ③. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 122 7.6 Installing and removing drives 3. Connect the SATA cables to the required SATA connectors of the motherboard (Page 167) and to the drive (position ③). 4. Close the device. 5. Connect the power supply unit. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 123: Install M.2 Nvme Ssd

    4. Insert the M.2 NVMe SSD ③ slightly inclined from above into the slot parallel to the motherboard. 5. Carefully press down M.2 NVMe SSD. 6. Fix the end of the M.2 NVMe SSD to the motherboard with a screw. 7. Close the device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 124 Expanding and assigning parameters to the device 7.6 Installing and removing drives Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 125: Device Maintenance And Repair

    Component Replacement interval Drives 3 years Backup battery 5 years 3 years Filter mat of the fan (front fan) Depending on the degree of soiling Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 126: Removing And Installing Hardware

    1. Remove the filter mat from the fan cover. 2. Insert the new filter mat loosely into the fan cover. Place the filter mat evenly in the fan cover. 3. Replace the fan cover. See also Maintenance intervals (Page 125) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 127: Changing The Front Fan

    6. Press on the clip on the small fan cable plug connector ② and remove the connector from the larger adapter plug, 7. Press on the side of the clips ③ and loosen the adapter plug from the cable holder. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 128 14.Insert the small fan cable connector ② in the larger adapter connector again. 15.Place the fan support with the new fan on the front of the device. See also Maintenance intervals (Page 125) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 129: Change The Fan On Drive Cage Type A

    The fan holder is labeled as follows: – At the top with "Top" – At the bottom with arrows which indicate the direction of rotation and air flow of the fan. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 130: Changing The Backup Battery

    Replace spent batteries promptly, see information under "Maintenance intervals (Page 125)". WARNING Risk of explosion and release of harmful substances Before replacing the backup battery, take note of the important safety instructions regarding battery replacement under "General safety instructions (Page 37)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 131 The battery is unlocked and disengages from the socket. 5. Remove the battery from socket. 6. Insert the new battery into the socket with slight pressure and lock it into place. 7. Close the device. 8. Check the firmware settings. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 132: Replacing The Power Supply Unit

    9. Connect the cables to the drives and the motherboard. 10.Secure the power supply unit cables in the device again using cable ties. 11.Close the device. 12.Check the safe state of the device. 13.Switch on the power supply unit. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 133: Replacing The Power Supply Unit 850 W

    9. Connect the cables to the drives and the motherboard. 10.Secure the power supply unit cables in the device again using cable ties. 11.Close the device. 12.Check the safe state of the device. 13.Switch on the power supply unit. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 134: Replacing The Module Of The Redundant Power Supply Unit 700 W

    4. Insert the new module and push it to the rear edge of the enclosure until it clicks into place there. 5. Re-insert the power plug into the socket ① of the newly inserted module. 6. Check the safe state of the device. Check the correct function on the status display. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 135: Changing The Enclosure Of The Redundant Power Supply Unit 700 W

    11.Replace the two modules of the redundant power supply unit and push them to the rear edge of the enclosure until they click into place. 12.Insert the power plugs into the sockets of the inserted modules. 13.Check the safe state of the device. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 136: Replacing The Processor

    4. Lift the release lever ④ and release the processor bracket ①. 5. Carefully lift the release lever ④ upwards. When doing so, ensure that you do not let go of the release lever. Illustration of processor socket without processor Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 137: Replacing The Motherboard

    For information on the firmware settings in the user manual (UM) for the motherboard, see "Important instructions and manuals for operating the device (Page 11)". • Screwdriver TORX T10 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 138: Installing The Operating System, Software, And Driver

    For information on restoring the operating system you ordered with the device in the detailed description of the operating system, see "Important instructions and manuals for operating the device (Page 11)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 139: Installing A New Microsoft® Windows® Operating System

    1. On the Internet, go to "Online Service Delivery Portal (https://www.automation.siemens.com/swdl/register/ipc)". 2. Log in with your credentials or register. 3. Enter the serial number and article number of the device for which you want to install software or drivers. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 140: Configuring Firmware/Bios

    Note If your device no longer boots, for example, after operating system crash during a firmware update, contact your local SIEMENS contact person. Recycling and disposal The devices described in these operating instructions can be recycled thanks to their low level of pollutants.
  • Page 141: Technical Specifications

    Power supply unit 550 W: • Continuous current at 100 V: ≤ 8 A • Continuous current at 230 V: ≤ 4 A • At startup ≤ 80 A for 3.6 ms Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 142 300 W secondary: • ≤ 270 W with 85% efficiency Power loss, heat emission Power supply unit 550 W: • 300 W = 300 J/s = 0.28 BTU/s Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 143 Protection class I compliant with IEC 61140 Safety regulations • IEC 61010-2-201 • EN 61010-2-201 • UL 61010-2-201 • CAN/CSA C22.2 No 61010-2-201 See also Safety instructions on ambient and environmental conditions (Page 44) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 144: Current And Power Requirements And Power Supply Units

    The requirements of the expansion card for the temperature of the intake air (inside the device) must be observed. Operation only permissible in conjunction with power supply unit 850 W Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 145: Technical Specifications Of The 550 W Power Supply Unit

    ± 5% +5 V +5%, -3% The total output of the +5 V and +3.3 V voltage must be ≤ 150 W. The total output of all voltages is max. 550 W. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 146: Technical Specifications Of The 850 W Power Supply Unit

    +5 V 3.0 A +5%, -3% The total output of the +5 V and +3.3 V voltage must be ≤ 130 W. The total output of all voltages is max. 700 W. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 147: Electromagnetic Compatibility

    80% AM to IEC 61000-4-3 • 10 V; 10 kHz up to 80 MHz 80% AM to IEC 61000-4-6 Immunity to magnetic fields 30 A/m; 50 Hz; 60 Hz (according to IEC 61000-4-8) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 148: Climatic And Mechanical Environmental Conditions

    The device must be free of any mechanical faults when disk drives are installed in the removable trays. See also Installation options for drives with drive cage type A (Page 104) Installation options for drives with drive cage type B (Page 114) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 149: Technical Specifications Of The Drives

    Slots for memory modules 4 x DIMM sockets for DDR5 4400 MHz, expandable to 128 GB Main memory 8 to 128 GB, DDR5 See also Technical specifications of the expansion card slots (Page 150) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 150: Technical Specifications Of The Expansion Card Slots

    • 3.3 V; 3 A • Gen. 4 • 12 V; 5.5 A • Active lanes: 8 • 3.3 V ; 0.4 A Power loss of the slot, permitted: ≤ 75 W Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 151 In sum, the current for 3.3 V must not exceed 1.2 A. Mounting position for graphics card ① Slot 1 (slot 2 cannot be used for graphics card NVIDIA RTX A2000 and RTX A5000) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 152: Technical Specifications Of Graphic

    5120 × 2880 at 60 Hz; 32-bit color depth • up to 3x DVI: 1920 × 1200 at 60 Hz; 32-bit color depth • up to 3x VGA: 2048 × 1536 at 60 Hz; 32-bit color depth Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 153 Maximum resolution • Up to 4x DVI: with adapter: 1920 × 1200 at 60 Hz; 32-bit color depth • Up to 4x VGA: 2048 × 1536 at 60 Hz; 32-bit color depth Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 154 The NVIDIA RTX A4000 and NVIDIA RTX A5000 graphics cards can only be connected, operated and configured for SIMATIC IPC RW-545A for devices with power supply unit 850 W. The NVIDIA RTX A4000 and NVIDIA RTX A5000 graphics card is then supplied with a voltage of 12 V via the slot on the motherboard and via an 6-pin or 8-pin plug-in connector.
  • Page 155: Technical Specifications Of The Connections

    24-pin (5 V; 500 mA) USB Type A USB Type A: • High-current USB Type C USB Type C: • High-current 5 V; 1.5 A; up to 10 Gbps Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 156 Realtek ALC887, 8-channel DAC support Line IN (light blue) – Headphone OUT (pastel green) – 1: Ground (max. 2 W at 4 Ω) 2: Audio links Microphone IN (pink) – 3: Audio right Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 157: Technical Specifications Of The Plug Connectors For The Power Supply Of Graphics Cards

    M5 x 6 mm The mounting screws of the telescopic rails may not protrude by more than 5 mm into the enclosure. See also Dimension drawing for drill holes for telescopic rails (Page 162) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 158: Technical Specifications Of The Operating Systems

    260 MB 260 MB 260 MB Windows System FAT32 or 40 GB 60 GB 120 GB 240 GB 300 GB 400 GB NTFS Data Data NTFS Remainder Remainder Remainder Remainder Remainder Remainder Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 159: Dimension Drawings

    10.1 Dimension drawing of the device Note IEC60297_3_100 The system meets the requirements for 4 U according to IEC60297_3_100. All dimensions in mm. ① Upper side of the device when installed vertically Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 160: Dimension Drawing Of The Tower Kit

    Dimension drawings 10.2 Dimension drawing of the Tower Kit 10.2 Dimension drawing of the Tower Kit Front view and top view All dimensions in mm. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 161: Dimension Drawing Of The Expansion Cards

    • Device with extender: 339 mm ② Height of the expansion card PCI: 106.7 mm (free space via expansion card: 38.3 mm) PCIe: 111.2 mm (free space via expansion card: 33.8 mm) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 162: Dimension Drawing For Drill Holes For Telescopic Rails

    800 mm cabinet; TS 3659.191 Dimensions of Heitec telescopic rails • for 600 mm cabinet; RP 3659.181 • for 800 mm cabinet; RP 3659.191 ② Dimensions of Schroff telescopic rails; Type 20110-072 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 163: Standards And Approvals

    Certificates and approvals 11.1.1 ISO 9001 certificate The Siemens quality management system for our entire product creation process (development, production and sales) meets the requirements of ISO 9001. This has been certified by DQS (the German society for the certification of quality management systems).
  • Page 164: Fcc Rules (Usa)

    Emission standard for residential, commercial and light-industrial environments. 11.1.8 Eurasion Customs Union EAC Identification for Eurasion Customs Union • EAC (Eurasian Conformity) • Declaration of conformity according to Technical Regulations of the Customs Union (TR Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 165: Kc Mark (Korea)

    • 2014/35/EU "Electrical equipment for use within specific voltage limits" (Low-Voltage Directive). Conformance with this standard has been verified according to EN 61010-2-201. • 2011/65/EU "Restriction of the use of certain hazardous substances in electrical and electronic equipment" (RoHS Directive) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 166 Standards and approvals 11.2 Directives and declarations Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 167: Hardware Description

    Sum of the currents on the USB ports of the device (including the internal USB ports) ≤ 3 A Technical features of the motherboard Technical features of the motherboard can be found under "General technical specifications of the motherboard (Page 149)". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 168: Expansion Cards

    PIRQ C PIRQ C INT D PIRQ D PIRQ A PIRQ D PIRQ D PIRQ D PIRQ D PIRQ D PIRQ D PIRQ D Organizationa l Pins Request REQ0 Grant GNT0 AD16 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 169: Exclusive Pci Hardware Interrupt

    Windows®: 1. Press the "Windows® key" and "R" simultaneously. The "Run" dialog box opens. 2. Enter "msinfo32" in the "Open" field. 3. Confirm your entry with "OK". Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 170: I/O Address Allocation

    0000 0A00 0000 0A0F Motherboard resources 0000 0D00 0000 FFFF 62208 PCI Express Root Complex 0000 164E 0000 164F Motherboard resources 0000 1854 0000 1857 Motherboard resources 0000 2000 0000 20FE Motherboard resources Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 171: Interrupt Assignments

    Address (hex) Description of the basic function from 000A 0000 000B FFFF PCI Express Root Complex 000E 0000 000E 3FFF PCI Express Root Complex 000E 4000 000E 7FFF PCI Express Root Complex Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 172 Intel® Serial IO I2C Host Controller - 7ACC 7F FFEF B000 7F FFEF BFFF Intel® GNA Scoring Accelerator module 7F FFEF C000 7F FFEF FFFF High Definition Audio Controller 7F FFF0 0000 7F FFFF FFFF High Definition Audio Controller Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 173: Assignment Of Expansion Interfaces To The Software In The Tia Portal (Cp Assignment)

    TIA Portal. Slot Designation on the motherboard TIA Portal Number on the enclosure PCIE4X16_1 X100 PCIE3_X8_1 X101 PCIE4X16_2 X102 PCIE3_X4_1 X103 PCIE4_X4_1 X104 PCIE_X4_2 X105 PCI1 X106 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 174 Hardware description A.4 Assignment of expansion interfaces to the software in the TIA Portal (CP assignment) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 175: Technical Support

    You can find additional information and support for the products described on the Internet at the following addresses: • Technical support (https://support.industry.siemens.com) • Support request form (https://www.siemens.com/supportrequest) • After Sales Information System SIMATIC IPC/PG (http://www.siemens.com/asis) • SIMATIC Documentation Collection (https://www.siemens.com/simatic-tech-doku-portal) • Your local representative (https://www.automation.siemens.com/aspa_app) • Training center (https://siemens.com/sitrain) •...
  • Page 176: Troubleshooting

    Time and/or date of the PC is 1. Open the firmware configuration menu. To do not correct this, press the <F2> key during the boot operation. 2. Set the date and the time in the "Main" tab. Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 177: Problems When Booting The Device

    You can find the files and descriptions needed for GPT data storage medium is this on the supplied data storage medium. aborted with the following error message: "Status: 0xc0000225 Info: The boot selection failed because a required device is inaccessible" Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 178: Problems With Raid Systems

    Different pin assignment expansion card and restart the device. If the error no longer occurs, the expansion card was the cause of the fault. Replace this with a Siemens expansion card or contact the supplier of the expansion card. If the device still crashes, contact your technical support team.
  • Page 179 Remove the installed expansion card and reinsert is integrated. connector Examples: • Clean the contact surface of the expansion card • The operating system does with pure ethanol. not boot. • The expansion card is not detected Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 180 Technical support B.2 Troubleshooting Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 181: Markings And Symbols

    Attention ESD (Electrostatic sensitive Warning of hot surface device) Disposal information, observe the local regulations. Symbols for operator controls Symbol Meaning Symbol Meaning On-off switch, without electrical isolation On-off button, without electrical isolation Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 182: Symbols Of Certificates And Approvals

    Marking of Federal Communications Commission for the USA EFUP (Environment Friendly Use Approved for Korea Period) marking for China Test mark of the Underwriters Approval for United Kingdom Laboratories Approval for India Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 183: Interface Icons

    Connection for functional grounding Line Out (Equipotential-bonding cable) DisplayPort interface Microphone input DVI port LAN interface, not approved for connecting WAN or telephone Serial port USB 2.0 high-speed port USB 3.0 Gen 1 SuperSpeed port Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 184 Markings and symbols C.5 Interface icons Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 185: Index

    Fehler! Textmarke nicht definiert. Disposal, 140 Backup battery Documentation, 11 Changing, 131 Drive cage type A, 16 Maintenance interval, 125 Installation options for drives, 104 Battery, (Backup battery) possible drive configurations, 106 BIOS, (Firmware settings) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 186 Front fan, 15 Graphics memory, 152 Maintenance interval, 125 Fan cover Acceptance, 126 Front fan, 15 Fan monitoring, 85 Hardware interrupt Fan on the front of the device, (Front fan) Assigning, 169 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 187 Index Hardware reset, 75 High frequency radiation KC Mark (Korea), 165 Immunity to interference, 45 Korea Holes KC Mark, 165 for telescopic rails, 56 Korean Certification, 165 hot swap Changing the drive in the removable tray, 106 LAN port Status displays, 29 I/O addresses LEDs, (Status displays) Assignment, 170...
  • Page 188 RCM (Australia/New Zealand), 164 Installing, 139 Recycling, 140 Restore, 138 Redundant 700 W power supply unit Shutdown, 74 Output voltage, 146 Redundant power supply unit Status displays, 30 Remote maintenance, (Intel® AMT) Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...
  • Page 189 Disconnecting the device from the line voltage, 74 Forced shutdown, (Hardware reset) Hardware reset, 75 Shutting down the operating system, 74 Switching on Configure automatic startup, 73 Switching on the device, 73 Workstation SIMATIC IPC RW-545A Operating Instructions, 08/2023, A5E52943278-AA...