2-Pipe Fan Coil Unit - Siemens RDG20 KN Series Basic Documentation

Room thermostats, communicating and standalone
Hide thumbs Also See for RDG20 KN Series:
Table of Contents

Advertisement

4
Functions
Control sequences

4.7.3 2-pipe fan coil unit

On/Off control
Control sequence
On/Off control output
Modulating control:
3-position, PWM or
DC 0...10 V
Control sequence
modulating output
Note
Note
80 | 186
In 2-pipe applications, the thermostat controls a valve in heating/cooling mode with
changeover (automatically or manually), heating only, or cooling only (factory
setting, P001 = 1).
The diagrams below show the control sequence for On/Off control.
Heating mode
T[°C] Room temperature
w
Room temperature setpoint
YHC Control command "Valve"
The diagrams below show the control sequence for modulating PI control.
Heating mode
T[°C] Room temperature
w
Room temperature setpoint
YHC Control command "Valve"
The diagrams only show the PI thermostat's proportional part.
For setting sequence and control outputs, see Application overview [➙ 43],
Sequence overview (setting via P001) [➙ 77] and Control outputs [➙ 101].
Parameter P256 (RDG264KN only), P260 & P261 (RDG26..) sets the
heating/cooling flow limitation. See Additional functions [➙ 48].
Cooling mode
SDH
Switching differential "Heating"
(P051)
SDC
Switching differential "Cooling"
(P053)
Cooling mode
XpH
Proportional band "Heating"
(P050)
XpC
Proportional band "Cooling"
(P052)
A6V11545892_en--_e