Connecting-Up and Wiring
7.2.2
Auxiliary power supply, precharging
X9 - external
DC 24 V supply,
precharging
contactor control
5
4
3
2
1
Fan supply
7.2.3
Protective conductor connection
NOTE
7-10
The 5-pole terminal strip is used for connecting up a 24 V voltage
supply and for connecting a precharging contactor.
The connections for the contactor control are floating.
The position of the terminal strip can be seen from the connection
overviews.
Terminal
Designation
5
Precharge contr. Precharging contactor control
4
Precharge contr. Precharging contactor control
3
n.c.
2
0 V
1
+24 V (in)
Connectable cross-section: 2.5 mm
Table 7-4
Connection of external DC 24 V aux. voltage supply and precharging
contactor control
AFE inverters of construction type J (compare above) require a supply
cable cross-section of 2.5 mm
F101 and F102 (fan fuses).
For AFE basic mains module, directly via the mounting surface and via
PE screw.
For AFE inverter via PE1 and PE2 and contact via the mounting
surface.
It is important to ensure that the basic mains module and the AFE
inverter are earthed at the same potential, use equipotential bonding if
necessary.
Meaning
Not connected
Reference potential
24 V voltage supply
2
(AWG 12)
2
(AWG 12). Connection to
6SE7087-6CX86-2BA1
Operating Instructions SIMOVERT MASTERDRIVES AFE
04.2006
Range
AC 230 V
1 kVA
0 V
DC24 V ≤ 3.5 A
Siemens AG