Occupancy setpoints
Register Type=Holding
Scaling=0.01
Reg Address
3007
3004
3008
3005
3009
3006
Special functions
Register Count=1
Reg
Name
Address
3725
PipePurge Time
3779
Purge Interval
2925
Valve Cycle
3780
Heat Time Out
5053
Hybrid Control
Enable Heat
5054
Hybrid Control
Enable Cool
2945
CoolTime Out
Occupancy setpoints
Table 22 Occupancy setpoints
Register Count=1
Name
Occupied Heat Setpoint
Occupied Cool Setpoint
Standby Heat Setpoint
Standby Cool Setpoint
Unoccupied Heat Setpoint
Unoccupied Cool Setpoint
Table 23 Special functions
Access=Read/Write
Register
Type
Holding
Holding
Holding
Holding
Coil
Coil
Holding
Access=Read/Write
Range
40 to 120°F
40 to 120°F
40 to 120°F
40 to 120°F
40 to 120°F
40 to 120°F
Memory Type=Non Volatile
Range
0 to 5 minutes
0.5 to 2 hours
1Min/24Hours=1
2Min/24Hours=2
Disable=3
1 to 4 hours
Off=0
On=1
Off=0
On=1
1 to 4 hours
Memory Type=Non Volatile
Default
68°F
Occupied heating setpoint
76°F
Occupied cooling setpoint
65°F
Standby heating setpoint
80°F
Standby cooling setpoint
55°F
Unoccupied heating setpoint
85°F
Unoccupied cooling setpoint
Default
Scaling
5
0.01
minutes
minute
0.5 hours
0.01
hour
1
1
4 hours
0.01
hour
1
1
1
1
4 hours
0.01
hour
Description
Description
Pipe purge duration
Pipe purge interval
Valve cycle type
When heating keep
working for timeout
time check whether
pipe temperature
meet pipe sensor
threshold.
2-pipe single coil
heat hybrid control
enable flag
2-pipe single coil
cool hybrid control
enable flag
When heating/
cooling keep working
for timeout time
check whether pipe
temperature meet
pipe sensor
threshold.
43