Voltage Supply - Bosch rexroth ctrlX CORE X2 Operating Instructions Manual

Table of Contents

Advertisement

ctrlX CORE X2, X3
Mounting notes:
For the power connector XD10, one-wire cables and stranded cables can be used with or without
wire end ferrule (acc. to DIN 46228). These wire end ferrules can be with or without plastic collar.
The contact surface has to be 8 mm.
The cable cross-section allowed is between 0.75 and 1.5 mm
Use only cables approved for temperatures of at least 60°C.
Use freely routed 1-wire cables. The wire distance has to be at least the wire diameter.
The stripping length is 8 mm.
To use stranded cables without wire end ferrules, twist the strand between 180° and 360°. The
stripped area has to be 8 mm after twisting. If stranded cables are introduced, keep the pushbutton
of the push-in terminal pressed.
To remove the cables, press the pushbutton of the push-in terminal.
Positioning the power connector
1.
Position the connector on the connector holder.
2.
Engage the connector on top.
10.5.3 24 V voltage supply
For the voltage supply, use a power supply unit as described in the following chapter:
⮫ Chapter 10.5.1 "External power supply unit " on page
The GND (U
) is not grounded to the device!
L
R911405645, Edition 07