hit counter script

Cisco 7600-SIP-400 - SPA Interface Processor 400 Installation Manual page 176

7600 series
Hide thumbs Also See for 7600-SIP-400 - SPA Interface Processor 400:
Table of Contents

Advertisement

Removing and Replacing the Power Supply
Figure 5-53
This illustration shows the terminal block barriers and terminal block guards attached.
Note
Power supply captive installation screws must be tight to ensure protective grounding continuity.
Warning
For proper 2700 W DC-input redundant power configuration, all two pairs of input wires for one 2700W
Note
DC-input power supply must come from the same battery system (A feed); all two pairs of input wires
for the other 2700 W DC-input power supply must come from another battery system (B feed).
For multiple DC input power supply, each DC input must be protected by dedicated circuit breaker or
Note
fuse. The circuit breaker or fuse should be sized according to the power supply input rating and local or
national electrical code requirements.
Cisco 7600 Series Router Installation Guide
5-48
Power Supply Captive Installation Screws
P W R - 2
7 0 0 - D C
/4
A LL FA
S TE N E
P R IO R
R S M U
TO O P
E R A TI
N G TH
Chapter 5
IN P U T1
IN P U T2
O K
FA N
O K
O U TP U
48 V- 60
T
V
O K
48 V- 60
FA IL
V
=4 0A
=4 0A
S T B E
FU LL Y
E N G A
E P O W
G E D
E R S U
P P LY
Removal and Replacement Procedures
OL-4503-26

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

76037603-s760476067606-s7609 ... Show all

Table of Contents