Display Function

1. Heating Model
Operation Indicator
• Cooling, Soft Dry, Fan, Heating
Sleep Timer Indicator
• Sleep Mode
Timer Indicator
• Timer Mode
Deicer Indicator
• Hot-start, Deice

Self-diagnosis Function

I Thermistor Cut Off or Short
Cut Off/Short : Blinks on and off the operation mode LED. (0.5 sec ON/3 sec OFF)
I Protection of the evaporator pipe from frosting
If the temperature of the indoor pipe is below 0°C after 7 minutes from starting the compressor, the compressor
and outdoor fan is stopped, and then after 3 minutes delay of operating of the compressor, when the tempera-
ture of the indoor pipe is over 7°C, the compressor and the outdoor fan is reoperated.
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
2. Cooling Model
Operation Indicator
• Cooling, Soft Dry, Fan
Sleep Timer Indicator
• Sleep Mode
Timer Indicator
• Timer Mode
Compressor on Indicator
- 29 -