InSTalleR SySTem TeST
FocusPRO
5000 Series
®
1.
To begin, press and hold the s and t buttons until the
display changes.
2.
Presss/t to turn system on/off.
System test
System status
number
number
10
0
Done
Next
3.
Press NEXT to advance to next test.
4.
Press DONE to terminate system test.
5.
Proceed to Installer System Tests on page 8.
6
FocusPRO
6000 Series
®
1.
To begin, press and hold the s and t buttons until the
display changes.
2.
Presss/t to turn system on/off.
System test
System status
number
number
10
0
Done
Next
3.
Press NEXT to advance to next test.
4.
Press DONE to terminate system test.
5.
Proceed to Installer System Tests on page 8.
7
InSTalleR SySTem TeSTS
Test the system's heating, emergency heat, cooling, and fan.
Available tests vary by thermostat and system type.
Table 2. Installer System Test
System Test
Test Type
System Status Number
Number
and Description
10
Heating system 0
Heat and fan off
1
First stage heat
on (Fan turns on if
Setup Function 1 is
set to 1, 5, 9, or 10
OR setup Function
3 is set to 1)
2
Second stage heat
on
3
Third stage heat
on
20
Emergency
0
Heat and fan off
heating system
1
Heat and fan on
2
Second stage heat
(Aux. heat) turns on
30
Cooling system 0
Compressor and
fan off
1
Compressor and
fan on
2
Second stage
compressor on
40
Fan system
0
Off
1
On
caution
EQUIPMENT DAMAGE HAZARD.
Compressor protection is bypassed during testing.
To prevent equipment damage, avoid cycling the
compressor quickly.
8
FocusPRO
5000
®
and 6000 Series
Thermostats
InSTalleR SeTuP and
SySTem TeST POckeT GuIde
69-2026