Power relay control
• Power relay turns on 1 second later after the power is input to the outdoor unit.
• Control sequence : power on
Protection from total current control
CT1 control
• If the operating current reaches I1, the operating frequency of the compressor decrease.
• After decreasing the operating frequency by 1step, if operating current is below I1 for 60 seconds continuous-
ly, the operating frequency of compressor increase by 1step.
CT2 control
• If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the
compressor restart again.
• If CT2 occurs 5 times within 1hour, the appliance turn off and display ERROR CODE 7.
Control table
Model
1
AS-W096DH0/GH0
2
AS-W126DH0/GH0
3
AS-W1865DH0
4
AS-W1224DH0
5
AS-W1424DH0
6
AS-W1825DH0
7
AS-W096E1G0
8
AS-W126E1G0
cf. I1 is set the lowest level between intial value and in case dectection of dc paeak current.
Protection from DC Peak Current
DC Peak Current Error by a fault signal of IPM
• If the operating current of IPM reaches 35A ±3A, the compressor stop instantly.
• If DC PEAK occurs 5 times within 1 hour, the appliance turns off and display ERROR CODE 6.
DC Peak Current Error by the compressor lock
• If the DC LINK voltage below DC 140V occurs 5 times within 1 hour while the compressor is operating, the
appliance turns off and display ERROR CODE 6.
DC Peak Current Error by the Outdoor Fan Lock
• If it's 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C while the compressor is
operating, the appliance turns off and display ERROR CODE 6.
PTC operating
power relay on
I1:Current of operating frequency down
I2: Current of compressor cut off
Outdoor temp ≥ 38°C
Cooling
Heating
5.5
6.5
6.5
7.5
9
10.5
6
6.5
6
6.5
10.5
11.5
7
8.5
7
8.5
I1
Outdoor temp < 38°C
Cooling
Heating
6
7
9.5
6.5
6.5
11
7.5
7.5
Operation
I2
7
9
8
10
11
13
7
8.5
7
9
12
14
9
10
9
10
Service Manual 39