b. Position the mounting plates (item 1 in illustration on page 49) under the four
c. Turn the rack-mounting bolts (item 6 in illustration on page 49) three or four
4. Mark the floor around the edge of the mounting plates, as shown in the following
illustration:
(4x) Caster
5. Remove the mounting bolts from the threaded holes.
6. Move the rack away from the mounting plates.
7. Mark the floor at the center of each hole in the mounting plate (including tapped
holes).
8. Remove the mounting plates from the marked locations.
9. At the marked location of the tapped mounting holes, drill two holes approximately
1 inch to allow clearance for the ends of the two rack-mounting bolts. The ends of
the rack-mounting bolts may protrude past the thickness of the mounting plate.
Drill one hole in each group of anchor bolt location marks as indicated on the
marked floor.
Eserver pSeries 690 Installation Guide
50
rack-mounting bolts (item 6 in illustration on page 49) so that the mounting
bolts are centered directly over the tapped holes.
rotations into the tapped holes.
27.5 mm REF
(10x) 65.5 mm REF
(2x) Mounting Plate
20.1 mm
Mounting Plate
Bolt Locations
709.8 mm REF
(32x) 21 mm REF
(4x) ½ x 13 UNC REF
Rear
Rack
Front
79.65 mm
750 mm REF