3. SIGNALS AND WIRING

3.7 Input power supply circuit

CAUTION

3.7.1 Connection example

Wire the power supply and main circuit as shown below so that the servo-on (SON) turns off as soon as
alarm occurrence is detected and power is shut off.
A no-fuse breaker (NFB) must be used with the input cables of the power supply.
(1) For 3-phase 200 to 230VAC power supply
3-phase
200 to 230 VAC
Always connect a magnetic contactor (MC) between the main circuit power supply
and L
L
and L
of the servo amplifier, and configure the wiring to be able to shut
,
,
1
2
3
down the power supply on the side of the servo amplifier's power supply. If a
magnetic contactor (MC) is not connected, continuous flow of a large current may
cause a fire when the servo amplifier malfunctions.
Use the trouble (ALM) to switch power off. Otherwise, a regenerative transistor
fault or the like may overheat the regenerative resistor, causing a fire.
POINT
For the power line circuit of the MR-J2S-11KA to MR-J2S-22KA, refer to
section 3.13 where the power line circuit is shown together with the servo
motor connection diagram.
Emergency
stop
RA
NFB
MC
Emergency
stop
Servo-on
3 - 47
WWW.NNC.IR
ON
OFF
MC
MC
SK
Servo amplifier
L
1
L
2
L
3
L
11
L
21
EMG
SON
VDD
SG
COM
ALM
Trouble
RA