hit counter script

Quick Start Wizard Via The Handheld Programmer - Siemens SITRANS LR260 Operating Instructions Manual

Radar
Hide thumbs Also See for SITRANS LR260:
Table of Contents

Advertisement

Quick Start Wizard via the handheld programmer

Notes:
• The Quick Start Wizard is a complete package and the settings are inter-related.
• Do not use the Quick Start wizard to modify individual parameters: see instead
Parameter Reference
the quick start has been completed).
1. Quick Start
a.
Point the programmer at the display (from a maximum distance of 500 mm [1.64 ft]),
then press RIGHT arrow
b.
Press RIGHT arrow
view.
c.
Press RIGHT arrow
values and move directly to the next item.
d.
To change a setting, scroll to the desired item or key in a new value.
e.
After modifying a value, press RIGHT arrow
to move to the next item.
1.1. Application Type
Options
1.2. Response Rate
Sets the reaction speed of the device to measurement changes in the target range.
Options
Use a setting just faster than the maximum filling or emptying rate (whichever is
greater).
1.3. Units
Select the units for the Quick Start variables (high and low calibration point, and level,
distance, or space)
Options
A5E32337685
SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS
on page 53 (perform customization for your application after
to activate PROGRAM mode and open menu level 1.
twice to navigate to menu item 1.1 and open parameter
to open Edit mode or DOWN arrow
STEEL
Silo construction
CONCRETE
Default: STEEL
SLOW
0.1 m/minute
MED
1.0 m/minute
FAST
10.0 m/minute
Default: FAST
M, CM, MM, FT, IN
Default: M
to accept default
to accept it and press DOWN arrow
Page 35

Advertisement

Table of Contents
loading

Table of Contents