Configuration Instructions
2.6
Order Number Classification for SIRIUS 3RW44 Soft Starters
2-8
Order number classification using the 3RW44 22-6BC44 as an example
3RW4
4
22
I
II
III
*Gray fields cannot be configured
I
Designation of the basic unit:
Semiconductor AC motor control device (soft starter)
II
Device version:
4
High End soft starter
III
Operating efficiency rating P
Rated operating current I
P
e
22
-
15 kW
23
-
18.5 kW
24
-
22 kW
25
-
30 kW
26
-
37 kW
27
-
45 kW
34
-
55 kW
35
-
75 kW
36
-
90 kW
43
-
110 kW
44
-
132 kW
IV
Type of connection
1
-
Standard screw connection (main/auxiliary lead connection)
(for devices
2
-
Main lead: Conductor-rail bond / auxiliary lead: Spring-type terminal
(for devices > 3RW44 27)
3
-
Main lead: Screw connection / auxiliary lead: Spring-type terminal
(for devices
6
-
Main lead: Conductor-rail bond / auxiliary lead: Terminal screw (for
devices > 3RW44 27)
V
Special function:
B
-
With bypass:
VI
Number of controlled phases:
C
-
All 3 phases controlled
VII
Rated control supply voltage U
3
-
115 V AC
4
-
230 V AC
VIII
Rated operating voltage U
4
-
200 to 460 V
5
-
400 to 600 V
6
-
400 to 690 V
-
6
B
IV
V
(at U
400 V)
e
e
(for utilization category AC-53a) (at TU 40 °C)
e
I
e
29 A
45
36 A
46
47 A
47
57 A
53
77 A
54
93 A
55
113 A
56
134 A
57
162 A
58
203 A
65
250 A
66
≤
3RW44 27)
≤
3RW44 27)
:
s
:
e
C
4
VI
VII
P
I
e
e
-
160 kW
313 A
-
200 kW
356 A
-
250 kW
432 A
-
315 kW
551 A
-
355 kW
615 A
-
400 kW
693 A
-
450 kW
780 A
-
500 kW
880 A
-
560 kW
970 A
-
630 kW
1076 A
-
710 kW
1214 A
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
4
VIII