Parameter
Description
3
P8553
Menu type
0
1
A.2
Fault and warning codes
Fault code list
Fault
Description
F1
Overcurrent
F2
Overvoltage
F3
Undervoltage
F4
Inverter overtemperature
F5
Inverter I
t
2
F6
Chip temperature rise exceeds critical levels
F11
Motor overtemperature
F12
Inverter temperature signal lost
F20
DC ripple too high
F35
Auto restart after n
F41
Motor data identification failure
F51
Parameter EEPROM fault
F52
Inverter software fault
F60
Asic timeout
F61
MMC / SD card parameter cloning failed
● To navigate through the current list of faults, press
● To clear / acknowledge the fault, press
● To ignore the fault, press
After you acknowledge or ignore the fault, the screen returns to the previous display. The fault icon remains active until the
fault is cleared / acknowledged.
Alarm code list
Alarm
Description
A501
Current limit
A502
Overvoltage limit
A503
Undervoltage limit
A504
Inverter overtemperature
A505
Inverter I
t
2
A506
IGBT junction temperature rise warning
A507
Inverter temperature signal lost
A511
Motor overtemperature I
A535
Braking resistor overload
A541
Motor data identification active
Note that alarms cannot be acknowledged. They are cleared automatically once the warning has been rectified.
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
Getting Started
24
A5E31842771, 02/2013
End quick commissioning only for motor data
Menus with no text
Menus with some text
or acknowledge externally if the inverter has been set up so.
OK
OK
.
M M
t
2
Range
0 - 1
Fault
Description
F62
Parameter cloning contents invalid
F63
Parameter cloning contents incompatible
F64
Inverter attempted to do an automatic clone during
startup
F71
USS setpoint fault
F72
USS / MODBUS setpoint fault
F80
AI lost input signal
F85
External fault
F100
Watchdog reset
F101
Stack overflow
F221
PID feedback below minimum value
F222
PID feedback above maximum value
F350
Configuration vector for the inverter failed
F395
Acceptance test / confirmation pending
F410
Cavitation protection failure
F452
Belt failure
or
.
Alarm
Description
A600
RTOS overrun warning
A910
Vdc_max controller deactivated
A911
Vdc_max controller active
A912
Vdc_min controller active
A921
AO parameters not set properly
A922
No load applied to inverter
A923
Both JOG left and JOG right are requested
A930
Cavitation protection warn
A936
PID autotuning active
A952
Belt failure detected
Factory default
Acc. level
0
1
Getting Started
A5E31842771, 02/2013