UDC2300 Universal Digital Indicator Product Manual Doc. No.: 51-52-25-84 Release: Last Revision Date: 10/00 Sensing and Control...
Page 2
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer’s sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose.
Page 3
This document provides descriptions and procedures for the installation, configuration, operation, and troubleshooting of your UDC2300 Indicator. Contacts World Wide Web The following lists Honeywell’s World Wide Web sites that will be of interest to our customers. Honeywell Organization WWW Address (URL) Corporate http://www.honeywell.com...
Page 4
Chassis Ground. Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements. UDC2300 Indicator Product Manual 10/00...
Introduction 1 Introduction 1.1 Overview The UDC2300 Indicator model provides only indication and alarms of Analog Inputs. No control functionality is included. The UDC2300 Indicator monitors temperatures and other variables in applications such as environmental chambers, plastic processing machines, furnaces and ovens, and packaging machinery.
Declaration of Conformity: 51309602-000 Deviation from the installation conditions specified in this manual, and the special conditions for CE conformity in Section 2.1, may invalidate this product’s conformity with the Low Voltage and EMC Directives. UDC2300 Indicator Product Manual 10/00...
2 Installation 2.1 Overview Introduction Installation of the UDC2300 consists of mounting and wiring the indicator according to the instructions given in this section. Read the pre-installation information, check the model number interpretation (Subsection 2.2), and become familiar with your model selections, then proceed with installation.
• Check that the model number shown on the inside of the case agrees with what you have ordered. Condensed Specifications Honeywell recommends that you review and adhere to the operating limits listed in Table 2-1 when you install your indicator. Table 2-1 Condensed Specifications Operating Limits Ambient Temperature: 32 °F to 131 °F (0 °C to 55 °C)
N.O. refer to Figure 2-2, Jumper positions W201 and W202: W201 is the ALARM RELAY 1 jumper. W202 is the jumper ALARM RELAY 2. See Table 2-3 for Alarm Relay contact information. See Alarm Relay Caution Note, Page 8. UDC2300 Indicator Product Manual 10/00...
W101 Alarm Relay #2 W202 NC (default) Input #1 S101 Position 1: thermocouple (default) Position 2: mV, Volt, RTD Position 3: not used Position 4: mA No jumper: 0 -10 volts Figure 2-2 Jumper Placements 10/00 UDC2300 Indicator Product Manual...
Table 2-3 Alarm Relay Contact Information Unit Alarm Relay Variable NOT in Alarm State Variable in Alarm State Power Wiring Relay Indicators Relay Indicators Contact Contact N.O. Open Open N.C. Closed Closed N.O. Closed Open N.C. Open Closed UDC2300 Indicator Product Manual 10/00...
Insert the prongs of the clips into the two holes in the top and bottom of the case. • Tighten both screws to secure the case against the panel. • Carefully slide the chassis assembly into the case, press to close, and tighten the screw. Replace the screw cover. UDC2300 Indicator Product Manual 10/00...
Use Suppression Devices—For additional noise protection, you may want to add suppression devices at the external source. Appropriate suppression devices are commercially available. For additional noise information, refer to Document #51-52-05-01, How to Apply Digital Instrumentation in Severe Electrical Noise Environments. 10/00 UDC2300 Indicator Product Manual...
Volts is supplied with the Volt indicator when the input is Source specified. You must install it when you wire the indicator before start-up. 1 24857 1 These inputs are wired differently than the UDC2000 Figure 2-7 Input Connections 10/00 UDC2300 Indicator Product Manual...
Open collector outputs are internally powered at 24 Vdc. CAUTION Connecting an external supply will damage the indicator. External relays should be fused between power and relay load. Figure 2-9 Open Collector Alarm Relay Output UDC2300 Indicator Product Manual 10/00...
Communications COMMUNICATION MASTER (RTN) SHLD D– D– 120 OHMS Connect shield wires together with Honeywell TO OTHER COMMUNICATION supplied crimp part number 30755381-001 CONTROLLERS Do not run these lines in the same conduit as AC power. D– 120 OHMS ON LAST LEG...
Failsafe Manual Mode, and indicator FAILSF will flash in the lower display and a message indicating which test failed will appear in the lower display. Then, “DONE” will appear in the lower display. 10/00 UDC2300 Indicator Product Manual...
When a key is pressed and the prompt KEYERR appears in the lower display, it will be for one of the following reasons: • parameter is not available, • not in Set Up mode, press key first, [SET UP] • key malfunction. UDC2300 Indicator Product Manual 10/00...
See Page 4.1 Overview 4.2 Configuration Prompt Hierarchy 4.3 Configuration Procedure 4.4 Lock Set Up Group 4.5 Input 1 Set Up Group 4.6 Communications Set Up Group 4.7 Alarms Set Up Group 4.8 Configuration Record Sheet 10/00 UDC2300 Indicator Product Manual...
It stores any changes you have made. If you do not press any keys for 30 seconds, the indicator times out and reverts to the mode and display used prior to entry into Set Up mode. 10/00 UDC2300 Indicator Product Manual...
CAL - all parameters are read/write except Calibration CONF – Lockout is available for Read/Write, other configuration parameters are Read Only ALL – Only the Lockout group is available for read/write. No other parameters are viewable. UDC2300 Indicator Product Manual 10/00...
This selection will be indicated on UNITS Units the annunciator. (“What display of temperature do you want?”) NONE Numeric English Numeric English Input 1 IN1TYP Actuation Type 100H 100L RADH NNMH RADI NNML 0-20 N90H 4-20 N90L 0-10 100m 10/00 UDC2300 Indicator Product Manual...
Page 32
Then 4 mA = 0 Gal/Min Range of Setting: –999 to 9999 floating in Engineering Units Ratio on Input Select the Ratio value you want on the Input. RATIO1 Range of Setting: –20.0 to 20.0 UDC2300 Indicator Product Manual 10/00...
Page 33
NOFS - NO FAILSAFE —This selection does not provide input failure detection and should only be used when an absolute accuracy is the most important criteria. (For this selection, no burnout signal went to the sensor.) 10/00 UDC2300 Indicator Product Manual...
Page 34
+24 Vdc Supply. Failure to set this parameter properly can cause normal mode noise problems in the input readings. LNGUAG Language Select what the language will be ENGL Selection for the displays. ENGL FREN GERM SPAN ITAL NUMB (Numeric) UDC2300 Indicator Product Manual 10/00...
ONE’s (or ZERO’s) in each permissible code expression is either ODD or EVEN BAUD RATE is the transmission Baud Rate 2400 BAUD 1006 speed in bits per second 2400 Baud 4800 Baud 9600 Baud 19200 Baud 10/00 UDC2300 Indicator Product Manual...
Page 36
FP_L Floating point little endian FPLB Floating point little endian with byte- swapped Communica- This selection determines how the UNITS 1010 tions Override indicator values are expressed Units during communications. Percent Engineering Units UDC2300 Indicator Product Manual 10/00...
Page 37
The UDC does not have to be connected to the RS-485 link to perform this test. If it is connected, only one UDC2300 should run the loopback test at a time. The computer should not be transmitting on the link while the loopback test is active.
Select whether you want the alarm HIGH AxSxHL Setpoint x type chosen in prompt "AxSxTY" to A1S1 1109 State alarm High or Low. A1S2 1110 X = 1 or 2 A2S1 1111 Low Alarm A2S2 1112 HIGH High Alarm UDC2300 Indicator Product Manual 10/00...
Page 39
The alarm is suppressed until the parameter gets to the non-alarm limit or band. Alarm blocking affects both alarm setpoints. Disable Blocking Block Alarm 1 only Block Alarm 2 only BK12 Blocks both Alarms 10/00 UDC2300 Indicator Product Manual...
What’s in this section? The following topics are covered in this section. TOPIC See Page 5.2 Operator Interface 5.3 Entering A Security Code 5.4 Lockout Feature 5.5 Monitoring The Indicator 5.6 Alarm Setpoints 10/00 UDC2300 Indicator Product Manual...
NONE. Thereafter, that selected number must be used to change the lockout level from something other than NONE. Write the number on the Configuration Record Sheet in the configuration section so you will have a permanent record. UDC2300 Indicator Product Manual 10/00...
This will be your security code. 5.4 Lockout Feature Introduction The lockout feature in the UDC2300 is used to inhibit changes (via keyboard) of certain functions or parameters by unauthorized personnel. Lockout levels There are different levels of Lockout depending on the level of security required. These levels are: •...
… Scratch Pad RAM Test Failed … Configuration Test Failed … Field or Factory Cal Test Failed Check the “Status” group. LOCK The lockout feature has been enabled to prevent unauthorized changes of certain functions or parameters. UDC2300 Indicator Product Manual 10/00...
A1S2VA = Alarm 1, Setpoint 2 A2S1VA = Alarm 2, Setpoint 1 A2S2VA = Alarm 2, Setpoint 2 Change a value [ ] [ ] To change any alarm setpoint value in the upper display. Return to Normal DISPLAY Display 10/00 UDC2300 Indicator Product Manual...
INPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION. Failure to comply with these instructions could result in death or serious injury. 10/00 UDC2300 Indicator Product Manual...
Before you calibrate the Input, check the internal jumper for the Input to make sure it is set for the correct input type. The jumper is located at position S101 on the printed wiring board. Figure 2-2 shows the location of the jumper and position selections. 10/00 UDC2300 Indicator Product Manual...
Place current source at zero before switching ON. • Do not switch current sources OFF/ON while connected to the UDC2300 input. For Radiamatic inputs only, set Emissivity value to 1.0. See Section 4.5 – Configuration Set Up prompt INPUT1, function prompt EMISS. UDC2300 Indicator Product Manual 10/00...
Thermocouple Source Step Action Connect the thermocouple extension wires to the terminals for the Input as shown in Figure 6-3. Thermocouple Source 24873 Thermocouple Extension Wire Figure 6-3 Wiring Connections for Thermocouple Inputs Using Thermocouple Source 10/00 UDC2300 Indicator Product Manual...
Action Connect the copper leads from the calibrator to the Input terminals as shown in Figure 6-4. Place current source at zero before switching on. Do not switch current sources ON/OFF while connected to the UDC2300 input. Decade Resistance 24875...
Action Connect the copper leads from the calibrator to the Input terminals as shown in Figure 6-6. Place current source at zero before switching on. Do not switch current sources ON/OFF while connected to the UDC2300 input. Volt Source 24877 Figure 6-6 Wiring Connections for 0 to 10 Volts 6.5 Input Calibration Procedure...
100 % range values. • Wait 15 seconds, and If … Then … you are calibrating a Thermocouple input go to step 4 you are calibrating other than a go to step 5 Thermocouple input UDC2300 Indicator Product Manual 10/00...
High and Low Range Limits. Be sure to protect any field calibration from accidental overwrites by configuring the appropriate LOCKOUT selection after calibration. See Section 4 - Configuration for specific instructions to set the lockout. 10/00 UDC2300 Indicator Product Manual...
Lower Display = INxTYP to return to Normal operating mode. Return to Normal DISPLAY Operation The factory calibration will be restored. If the problem is not corrected, contact the Honeywell Technical Assistance Center. 1-800-423-9883 USA and Canada UDC2300 Indicator Product Manual 10/00...
• Indicator Failure Symptoms • Customer Support • Determining the Software Version Number Power-up Tests Status Tests Background Tests Indicator Failure Symptoms Troubleshooting Procedures • Power Failure • Alarm Relay Output Failure • Keyboard Failure 10/00 UDC2300 Indicator Product Manual...
Page 58
Troubleshooting/Service Installation related problems Read the Installation section in this manual to make sure the UDC2300 has been properly installed. The installation section provides information on protection against electrical noise, connecting external equipment to the indicator, and shielding and routing external wiring.
Do not return your indicator without authorization from Honeywell’s Technical Assistance Center or until the replacement has been received. For a list of frequently asked questions and their answers, dial Honeywell’s Faxback 24 hour Service: 1-888-423-9883 USA Or check out Honeywell’s web site at:...
Lower Display = A1xx Basic Controller and Indicator A2xx Limit Controller Please give this number to the Customer Support person. It will indicate which version of UDC2300 you have and help them determine a solution to your problem. UDC2300 Indicator Product Manual...
Set Up Group Read the test FUNCTION You will see: results Upper Display = NO or YES YES indicates a failure Lower Display = FAILSF FUNCTION Upper Display = PASS or FAIL Lower Display = TEST 10/00 UDC2300 Indicator Product Manual...
Troubleshooting/Service Background Tests Introduction The UDC2300 performs ongoing background tests to verify data and memory integrity. If there is a malfunction, an error message will be displayed (blinking) in the lower display. In the case of simultaneously malfunctions, the messages will appear in sequence in the lower display.
This may lead to a different troubleshooting procedure. If the symptom still persists, refer to the installation section in this manual to ensure proper installation and proper use of the indicator in your system. 10/00 UDC2300 Indicator Product Manual...
Equipment needed You will need the following equipment in order to troubleshoot the symptoms listed in the tables that follow: • DC Milliammeter – mAdc • Calibration sources – T/C, mV, Volt, etc. • Voltmeter UDC2300 Indicator Product Manual 10/00...
Check the contacts. Make sure the NO or NC contact wiring is correct. Refer to Section 2 - Installation for relay jumper placement and relay contact information. Change Main board. Installation instructions supplied with new board. 10/00 UDC2300 Indicator Product Manual...
Refer to Section 4 – security code. Configuration. Using “1000” as a security code number will override the 4-digit code previously entered. Replace the display/keyboard if any Installation instructions supplied with new keys are not functioning. display/keyboard. UDC2300 Indicator Product Manual 10/00...
Exploded View Introduction Figure 8-1 is an exploded view of the UDC2300 Indicator. Each part is labeled with a key number. The part numbers are listed by key number in Table 8-1. Parts not shown are listed in Table 8-2.