WIRING

Siemens Industry, Inc.
Building Technologies Division
Silenceable
Wiring Type
Total Current Drawn
If the zone usage is set in the Zeus Programming tool as "Sil Horn Only (Horn Strobe)" ,
the Silenceable Option is always set and is specific to the Horn of the Horn Strobe
device and the strobe is always Non-Silenceable.
Some restrictions apply to certain usage selections (for example, Municipal Tie can
only be configured as Class B wiring type) that are enforced by the Zeus tool during
Edit mode or Compile time.
Refer to the Zeus Quick Start Manual, P/N 315-033875, or the Zeus self-help index
for more information.
Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)
All field wiring to the ZIC-4A is connected to
the terminal blocks of the CC-5 card cage
slot in which it is installed (Refer to Figure 3).
To Connect External Wiring
1.
Loosen the screw of the terminal
by turning it counterclockwise.
2.
Insert the wire into the side of the
terminal block.
3.
Tighten the screw of the terminal
block by turning it clockwise.
The top terminals (1 through 8 and 9
through 16) are connected to the notifica-
tion appliance devices such as bells, horns,
strobes, speakers, etc. Each zone has four
terminal connections: (+), Class A (+), (-),
Class A (-). These terminals are power
limited.
The bottom terminals (17 through 24) are
connected to the input power source of the
NAC devices. Each zone has a (+) terminal
and (-) terminal. These terminals are not
power limited.
Determines if the circuit is Silenceable or
Non-Silenceable.
Defines if the circuit is Class A or Class B
wiring type.
Select actual current load of output
circuit (see list).
0
0 .
A
m
p
0
5 .
A
m
p
1
0 .
A
m
p
ZONE 1
1
9
17
ZONE 1
INPUT
Figure 3
Wiring The 24VDC Power Lines To The
ZIC-4A Slot In The CC-5
8
1
5 .
A
m
p
3
0 .
A
m
p
2
0 .
A
m
p
3
5 .
A
m
p
2
5 .
A
m
p
4
0 .
A
m
p
OUTPUTS SHOWN IN ACTIVE STATE
ZONE 2
2
3
4
5
6
7
10
11
12
13
14
15
ZONE 3
ZONE 4
ONE SLOT OF CC-5
18
19
20
21
22
23
ZONE 2
ZONE 3
ZONE 4
INPUT
INPUT
INPUT
P/N 315-033050-15
8
16
24