hit counter script

Filtering (2.8.); Narrow Echo Filter (2.8.1.); Reform Echo (2.8.2.); Average Amount (2.8.3.) - Siemens SITRANS LR560 Operating Instructions Manual

Radar transmitters
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

Parameter Reference
8.2 SETUP (2.)
8.2.8

FILTERING (2.8.)

8.2.8.1

NARROW ECHO FILTER (2.8.1.)

Factory setting:
Setting range:
Purpose:
Description:
8.2.8.2

REFORM ECHO (2.8.2.)

Factory setting:
Setting range:
Purpose:
8.2.8.3

AVERAGE AMOUNT (2.8.3.)

Factory setting:
Setting range:
Purpose:
112
0 = OFF
0 to 255, greater = wider
Filters out echoes of a specific width.
To remove a false echo from the Echo Profile, take its width in mm and
multiply it by 0.006. Enter the result.
Example: to filter out a spike with 500 mm width, enter 6 or 7 (the closest
integer product of 500 x 0.006). When a value is keyed in, the nearest ac-
ceptable value is entered.
0 = OFF
0 to 255 samples, greater = wider (recommended: 10 samples)
Smooths jagged peaks in the echo profile. Reforms fragmented echoes into
one echo.
0.75
0.0 to 0.99
The fraction of the old shot data that is kept for averaging purposes. A
higher value will give a smoother profile at the expense of a slower echo
profile response.