Values in hex
notation
0x8A
0x8D
0x8E
Values in hex
notation
0x4B
0x4C/0x4F
0x47
Values in hex
notation
0x10
0x01
0X1F
This could happen when a firmware download has been done, but a system reset has not been
a)
done. This could also happen if the function blocks are not configured properly using the handheld
programmer, PDM or acyclic services.
C.15
Condensed status
These codes are available when Condensed Status is enabled. See Condensed Status
(3.4.) for more details.
Hex value
0x80
0x84
0x86
0x80
...0x8E
LR560 (PROFIBUS PA)
Operating Instructions, 06/2018, A5E34648471-AE
Status Codes for good quality
Description
Active high warning.
Active low alarm.
Active high alarm.
Status Codes for Uncertain Quality
Description
Value is a substituted value (normally used in Failsafe).
Initial value.
Last usable value.
Status Codes for Bad Quality
Description
The LOE timer has expired: this could be caused by LOE or by a sensor
malfunction: value is BAD.
There is an error in the configuration of the function blocks in PROFIBUS
PA
.
a)
The function block, or the transducer block, has been placed out of
service.
Condensed Status (GOOD)
Status - GOOD
Description
GOOD – ok
No error or special condition is associated with this value.
GOOD – update event Set if the value is good and the block has an active Update
event. (This status remains active for 20 seconds.)
GOOD – active advi-
Set if the value is good and the block has an active Alarm.
sory alarm
GOOD – limit check/
See Status Codes for Good Quality (Page 186).
update event
Communications via PROFIBUS PA
C.15 Condensed status
187