hit counter script

Siemens SITRANS LR560 Operating Instructions Manual page 193

Radar transmitters
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

Communications via PROFIBUS PA
C.21 Acyclic extended diagnostics (general fault codes)
LCD display Meaning
S:0
The device was unable to get a measurement
within the Failsafe LOE Timer period. Possible
causes: faulty installation, antenna material
buildup, foaming/other adverse process con-
ditions, invalid calibration range.
S:2
Unable to collect profile because of a power
condition that is outside the operating range
of the device.
S:3
Device is nearing its lifetime limit according to
the value set in Maintenance Required Limit.
S:4
Device is nearing its lifetime limit according to
the value set in Maintenance Demanded
Limit.
S:6
Sensor is nearing its lifetime limit according to
the value set in Maintenance Required Limit.
S:7
Sensor is nearing its lifetime limit according to
the value set in Maintenance Demanded
Limit.
S:8
Service interval as defined in Maintenance
Required Limit has expired.
S:9
Service interval as defined in
Maintenance Demanded Limit
has expired.
S:10
Input parameters High Calibration Point and
Low Calibration Point are the same.
S:11
Internal temperature sensor failure.
S:12
* Internal temperature of the device has ex-
ceeded
specifications: it is operating outside its tem-
perature range.
S:14
Upper and lower input values (Process Value
Scale) for AIFB1 are the same.
192
Acyclic Extended Diagnostics /General Fault Codes
Corrective Action
Ensure installation details are correct.
Ensure no antenna material
buildup. Clean if necessary.
Adjust process conditions to minimize foam
or other adverse conditions.
Correct range calibration.
If fault persists, contact your local Siemens
representative.
Repair required. Contact your local Siemens
representative.
Replacement is recommended.
Replacement is recommended.
Replacement is recommended.
Replacement is recommended.
Perform service
Perform service.
Check calibration settings of device.
Ensure settings for High Calibration Point
and Low Calibration Point are different.
Repair required. Contact your local Siemens
representative.
Relocate device and/or lower process tem-
perature enough to cool device.
Inspect for heat-related damage and contact
your local Siemens representative if repair
is
required.
Fault code will persist until a manual reset is
performed using PDM or the LCD interface.
Check configuration for AIFB1.
Ensure that Upper Value and Lower Value
(Process Value Scale) are not the same.
Operating Instructions, 06/2018, A5E34648471-AE
Byte
Bit
0
2
0
3
4
6
7
0
1
3
4
5
1
6
LR560 (PROFIBUS PA)

Advertisement

Table of Contents
loading

Table of Contents