Cabinet Configuration and EMC Booksize
7.7 Cooling
7.7.2

Information about ventilation

The SINAMICS equipment is ventilated separately by means of integrated fans and is in
some cases cooled by means of natural convection.
The cooling air must flow through the components vertically from bottom (cooler region) to
top (region heated by operation).
If filtered fans, heat exchangers, or air conditioners are used, you must ensure that the air is
flowing in the right direction. You must also ensure that the warm air can escape at the top.
A ventilation clearance of at least 80 mm above and below must be observed.
Note
Cables must not be routed on the modules; the ventilation grilles must not be covered.
Cold air must not be allowed to blow directly onto electronic equipment.
Figure 7-18
7-38
Examples of cabinet ventilation
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2