Zones; Groups - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Advertisement

Zones

ZONE FUNCTIONS
OHS
OUTSTATIONS
ASSIGNED TO
LOOP1
ZONE 4
INTERFACE
MCP
OUTSTATIONS
ASSIGNED TO
OHS
ZONE 4
H
LOOP2
INTERFACE
MCP
¨
A zone has a collection of trigger devices that are
located in the same general area. It may be used for
one or all three of the following:
for illumination of zonal fire lamps on Main panel
or Zonal mimic panel
for common disablement purposes
¨
There can be up to 128 Zones per A2 / 64 Zones per
A4 zonal mimic panel.
¨
Zones are used to provide local indication of fire at the
main panel and to send fire messages to zonal mimic
and loop repeat panels and repeat indicator panels off
main panel.
integral zonal indicators can be configured to give
steady / flashing indication of 1st zone in fire
¨
Devices from any loop may be assigned to the same
zone.
¨
A device may only be assigned to one zone.
¨
Input/output lines of an interface can not be assigned
individually to zones. The interface lines can only be
assigned collectively to a zone.

Groups

¨
There can be up to 128 groups
¨
all devices default to Group 1
¨
all local controller events are in group 0, ie faults,
warning, silence alarms and reset.
"
All MCC / MCB / LCC (local controller) events are in
Group 0, ie FAULTS, WARNING, SILENCE ALARMS and
RESET etc.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
ZONE INDICATORS ON THE PANEL
On
Test/Eng
Off
Flashing
ZONAL MIMIC PANEL
ZONE 4
DISABLE
ZONE Z
NOTE: AN OUTSTATION CAN ONLY
BE ASSIGNED TO ONE ZONE
ZONE E
ENABLE
Vigilon (EN & BS) Compact (VA) panels
1
2
3
4
5
6
7
Zones
17
18
19
20
21
22
23
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE X
8
9
10
11
12
13
14
15
24
25
26
27
28
29
30
30
121
16
32