hit counter script

Communication Test - Mitsubishi Electric RD78G4 User Manual

Motion module
Hide thumbs Also See for RD78G4:
Table of Contents

Advertisement

Communication Test

This function checks if transient transmission can be performed from the own station to the communication target.
Depending on selection for "Communication Method" ("Network No./Station No." or "IP Address"), the range that can be
checked may vary.
Selection of "Communication Method"
Network No./Station No.
IP Address
Explain the procedure of the communication test.
Precautions
Since this function uses ping, an error, "a communication test target station communication error" (error code D919H) occurs
if the communication target does not respond to ping. When executing this function, check if the security setting (such as
firewall) of the communication target is set to respond to ping. Moreover, if the target is set not to respond to ping in the
security settings (such as a firewall), it may take some time until a timeout error occurs on the engineering tool. For details on
when communication of the engineering tool is not allowed in the firewall settings of Windows, refer to the following.
GX Works3 Operating Manual
3 TROUBLESHOOTING
62
3.3 Checking the Network Status
Communication target of transient transmission
Stations on the same network
 Available for check
 Available for check
1.
Display the "Communication Test" window and select
"Network No./Station No." or "IP Address" from
"Communication Method".
[Diagnostics]  [CC-Link IE TSN/CC-Link IE Field
Diagnostics]  [Communication Test] button
2.
Enter values for "Target Station" and "Communication
Data Setting".
3.
Click the [Execute Test] button to execute the
communication test. If an error occurs, take corrective
actions according to the error message.

Advertisement

Table of Contents
loading

Table of Contents