hit counter script

Advertisement

LOGO!Power

Power supply

LOGO!Power
Operating Instructions
LOGO!Power 5 V / 3 A
6EP1311-1SH03
LOGO!Power 5 V / 6.3 A
6EP1311-1SH13
LOGO!Power 12 V / 1.9 A
6EP1321-1SH03
LOGO!Power 12 V / 4.5 A
6EP1322-1SH03
LOGO!Power 15 V / 1.9 A
6EP1351-1SH03
LOGO!Power 15 V / 4 A
6EP1352-1SH03
LOGO!Power 24 V / 1.3 A
6EP1331-1SH03
LOGO!Power 24 V / 2.5 A
6EP1332-1SH43
LOGO!Power 24 V / 4 A
6EP1332-1SH52
06.2014
C98130-A7560-A999-3-7629
___________________
Overview
___________________
Safety instructions
Description, device design,
___________________
dimension drawing
___________________
Mounting/disassembly
___________________
Mounting position, mounting
clearances
___________________
Installation
___________________
Technical data
___________________
Safety, approvals, EMC
___________________
Ambient conditions
___________________
Applications
___________________
Environment
___________________
Service and support
1
2
3
4
5
6
7
8
9
10
11

Advertisement

Table of Contents
loading

Summary of Contents for Siemens LOGO!Power Series

  • Page 1: Power Supply

    ___________________ LOGO!Power Overview ___________________ Safety instructions Description, device design, ___________________ dimension drawing Power supply ___________________ Mounting/disassembly ___________________ Mounting position, mounting LOGO!Power clearances ___________________ Installation Operating Instructions ___________________ Technical data ___________________ Safety, approvals, EMC ___________________ Ambient conditions ___________________ Applications ___________________ Environment LOGO!Power 5 V / 3 A ___________________ 6EP1311-1SH03...
  • Page 2: Legal Information

    Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Overview

    Overview LOGO!Power are powerful power supplies that can be extremely flexibly used in a host of applications – in installation distribution boards for example – as a result of their flat, stepped profile. The 12 V and 24 V versions are ideal as power supplies for the LOGO! logic modules.
  • Page 4 Overview Ordering data The following device options are available: LOGO!Power stabilized power supply Type Order number Input 85 to 264 VAC 6EP1311-1SH03 110 to 300 VDC Output 5 VDC / 3 A Input 85 to 264 VAC 6EP1311-1SH13 110 to 300 VDC Output 5 VDC / 6.3 A Input 85 to 264 VAC 6EP1321-1SH03...
  • Page 5: Table Of Contents

    Table of contents Overview..............................3 Safety instructions ........................... 7 Description, device design, dimension drawing..................9 Device description .......................... 9 Connections and terminal designation ..................10 Potentiometer ..........................11 Status displays and signaling ....................... 12 Block diagram ..........................13 Dimensions and weight ........................ 14 Mounting/disassembly ...........................
  • Page 6 Table of contents Ambient conditions ..........................45 Applications ............................47 Parallel connection to increase power rating ................47 Parallel connection for redundancy ..................... 49 Series connection for increased voltage ..................50 Protection against short-time voltage dips .................. 51 Environment ............................53 Service and support ..........................
  • Page 7: Safety Instructions

    Safety instructions WARNING Correct handling of the devices When operating electrical devices, it is inevitable that certain components will carry dangerous voltages. Therefore, failure to handle the units properly can result in death or serious physical injury as well as extensive property damage. Only appropriately qualified personnel may work on or in the vicinity of this equipment.
  • Page 8 Safety instructions LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 9: Description, Device Design, Dimension Drawing

    Description, device design, dimension drawing Device description LOGO!Power are primary switched-mode power supplies for connection to a 1-phase AC system or to DC systems. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof.
  • Page 10: Connections And Terminal Designation

    Description, device design, dimension drawing 2.2 Connections and terminal designation Connections and terminal designation Note UL requirement: Use suitable copper cables that are designed for operating temperatures of at least 65 °C / 75 °C. ① The line input terminals can be used to establish the connection to supply voltage.
  • Page 11: Potentiometer

    Description, device design, dimension drawing 2.3 Potentiometer Potentiometer ③ The potentiometer on the front of the device is used to set the output voltage. The output voltage is set to the rated value at the factory and can be set within certain limits; for example, to compensate voltage drops across long supply lines to the connected load.
  • Page 12: Status Displays And Signaling

    Description, device design, dimension drawing 2.4 Status displays and signaling Status displays and signaling 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A)
  • Page 13: Block Diagram

    Description, device design, dimension drawing 2.5 Block diagram Block diagram Figure 2-5 Block diagram LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 14: Dimensions And Weight

    Description, device design, dimension drawing 2.6 Dimensions and weight Dimensions and weight Figure 2-6 Dimension drawing 6EP1311-1SH03, 6EP1321-1SH03, 6EP1351-1SH03, 6EP1331-1SH03 Figure 2-7 Dimension drawing 6EP1311-1SH13, 6EP1322-1SH03, 6EP1352-1SH03, 6EP1332-1SH43 LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 15 Description, device design, dimension drawing 2.6 Dimensions and weight Figure 2-8 Dimension drawing 6EP1332-1SH52 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1332-1SH52 (24 V / 4 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A)
  • Page 16 Description, device design, dimension drawing 2.6 Dimensions and weight LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 17: Mounting/Disassembly

    Mounting/disassembly WARNING Installing the device in a housing or a control cabinet The LOGO!Power power supplies are built-in units. They must be installed in a casing or control cabinet to which only qualified personnel have access. The devices can be mounted in a control cabinet on standard mounting rails according to EN 60715 35x7,5/15.
  • Page 18 Mounting/disassembly WARNING Use in hazardous zones If the device is to be used in a hazardous zone (Ex II 3G Ex nA IIC T3) it must be installed in a distributor box with degree of protection IP54 or higher. LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 19: Mounting Position, Mounting Clearances

    Mounting position, mounting clearances Standard mounting position The device is mounted on standard mounting rails according to EN 60715 35x7,5/15. The device must be mounted vertically in such a way that the input terminals and the output terminals are at the top to ensure correct cooling. A clearance of at least 20 mm should be maintained above and below the device.
  • Page 20: Other Mounting Positions

    Mounting position, mounting clearances 4.2 Other mounting positions Other mounting positions For mounting positions that deviate from the standard mounting position, derating factors (reduction of the output power or the permissible ambient temperature) must be observed in accordance with the following diagrams. Note In the case of mounting postilions that deviate from the standard mounting position, reduced mechanical resistance of the devices against vibration and shock must be expected.
  • Page 21 Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-5 Mounting position (3) Figure 4-6 Mounting position (4) Figure 4-7 Mounting position (5) LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 22 Mounting position, mounting clearances 4.2 Other mounting positions LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 23: Installation

    Installation WARNING Hazard due to electric shock Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. Line-side connection The LOGO!Power power supplies are power packs according.
  • Page 24 Installation 5.1 Line-side connection Note For operation on a direct voltage network (DC), the plus pole (+) must be connected to L1 and the minus pole (–) to N. Protection LOGO!Power Recommended line-side protection 6EP1311-1SH03 (5 V / 3 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A 6EP1311-1SH13 (5 V / 6.3 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A...
  • Page 25: Output-Side Connection

    Installation 5.2 Output-side connection Output-side connection LOGO!Power power supplies provide an isolated (= non-grounded) SELV (Safety Extra Low Voltage) output voltage at the output. The output of the power supplies is no-load, overload and short-circuit proof. If an overload occurs, the electronic current limiting function limits the output current to a maximum value (see Section Technical data (Page 27)).
  • Page 26 Installation 5.2 Output-side connection LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 27: Technical Data

    Technical data Note For an AC input voltage, the technical data is applicable for rated input voltage, rated load and +25° C ambient temperature (if nothing else is specified). Input 6EP1311-1SH03 6EP1311-1SH13 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 (5 V / 3 A) (5 V / 6.3 A) (12 V / 1.9 A) (12 V / 4.5 A)
  • Page 28 Technical data 6.1 Input 6EP1352-1SH03 6EP1331-1SH03 6EP1332-1SH43 6EP1332-1SH52 (15 V / 4 A) (24 V / 1.3 A) (24 V / 2.5 A) (24 V / 4 A) Input 1-phase AC or DC Rated voltage 100...240 V e rated / for AC Voltage range / for AC 85...264 V Input voltage / for DC...
  • Page 29: Output

    Technical data 6.2 Output Output 6EP1311-1SH03 6EP1311-1SH13 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 (5 V / 3 A) (5 V / 6.3 A) (12 V / 1.9 A) (12 V / 4.5 A) (15 V / 1.9 A) Output Regulated, isolated DC voltage Rated voltage value 12 V 12 V...
  • Page 30 Technical data 6.2 Output 6EP1352-1SH03 6EP1331-1SH03 6EP1332-1SH43 6EP1332-1SH52 (15 V / 4 A) (24 V / 1.3 A) (24 V / 2.5 A) (24 V / 4 A) Output Regulated, isolated DC voltage Rated voltage value 15 V 24 V 24 V 24 V Ua rated DC...
  • Page 31 Technical data 6.2 Output Figure 6-2 Startup delay/voltage rise Figure 6-3 Output characteristic The device supplies a constant output voltage until the current limit is reached. In the event of an overload, the output current and the output voltage are reduced. The device does not switch off.
  • Page 32: Efficiency And Power Loss

    Technical data 6.3 Efficiency and power loss Efficiency and power loss 6EP1311-1SH03 6EP1311-1SH13 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 (5 V / 3 A) (5 V / 6.3 A) (12 V / 1.9 A) (12 V / 4.5 A) (15 V / 1.9 A) Efficiency at Ua rated, 79 % 80 %...
  • Page 33 Technical data 6.3 Efficiency and power loss Figure 6-5 Efficiency 6EP1311-1SH13 Figure 6-6 Efficiency 6EP1321-1SH03 Figure 6-7 Efficiency 6EP1322-1SH03 LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 34 Technical data 6.3 Efficiency and power loss Figure 6-8 Efficiency 6EP1351-1SH03 Figure 6-9 Efficiency 6EP1352-1SH03 Figure 6-10 Efficiency 6EP1331-1SH03 LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 35 Technical data 6.3 Efficiency and power loss Figure 6-11 Efficiency 6EP1332-1SH43 Figure 6-12 Efficiency 6EP1332-1SH52 LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 36: Closed-Loop Control

    Technical data 6.4 Closed-loop control Closed-loop control 6EP1311-1SH03 6EP1311-1SH13 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 (5 V / 3 A) (5 V / 6.3 A) (12 V / 1.9 A) (12 V / 4.5 A) (15 V / 1.9 A) Dyn. mains 0.2% 0.2% 0.2% 0.2%...
  • Page 37: Protection And Monitoring

    Technical data 6.5 Protection and monitoring Protection and monitoring 6EP1311-1SH03 6EP1311-1SH13 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 (5 V / 3 A) (5 V / 6.3 A) (12 V / 1.9 A) (12 V / 4.5 A) (15 V / 1.9 A) Output overvoltage Yes, according to EN 60950-1 protection Current limitation, typ.
  • Page 38: Mechanical System

    Technical data 6.7 Mechanical system Mechanical system 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1332-1SH52 (24 V / 4 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A)
  • Page 39: Dimension Drawing

    Technical data 6.9 Dimension drawing Dimension drawing See Section Dimensions and weight (Page 14) CAD data that can be downloaded from the Internet: 6EP1311-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00535) 6EP1311-1SH13 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00538) 6EP1322-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00544) 6EP1321-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00541) 6EP1351-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00556) 6EP1352-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00559) 6EP1331-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00547) 6EP1332-1SH43 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00550) 6EP1332-1SH52 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00553)
  • Page 40 Technical data 6.9 Dimension drawing LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 41: Safety, Approvals, Emc

    Safety, approvals, EMC Safety 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) 6EP1332-1SH52 (24 V / 4 A)
  • Page 42: Test Voltage

    Safety, approvals, EMC 7.2 Test voltage Test voltage Figure 7-1 Test voltage diagram Only the manufacturer can perform the type test and production test; users can also perform the field test. Preconditions for performing the field test: Test (A) ● Connect the input terminals to one another ●...
  • Page 43: Certifications

    Safety, approvals, EMC 7.3 Certifications Certifications Certifications 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1332-1SH52 (24 V / 4 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A)
  • Page 44: Emc

    Safety, approvals, EMC 7.4 EMC 6EP1311-1SH03 (5 V / 3 A) 6EP1332-1SH52 (24 V / 4 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A)
  • Page 45: Ambient Conditions

    Ambient conditions 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) 6EP1332-1SH52 (24 V / 4 A) Ambient temperature...
  • Page 46 Ambient conditions 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) 6EP1332-1SH52 (24 V / 4 A) Damaging gases...
  • Page 47: Applications

    Applications Parallel connection to increase power rating To enhance performance, two LOGO!Power power supplies of the same type can be galvanically connected in parallel. The following must be observed: ● The cables connected to each power supply at terminals "+" and "-" must have identical lengths and the same cable cross-sections (or the same impedance) up to a common external network junction (terminal strip) if possible.
  • Page 48 Applications 9.1 Parallel connection to increase power rating NOTICE Protective circuit for the parallel connection of more than two power supplies For connection of more than two power supplies in parallel, additional measures must be taken to prevent high backward feeding currents in the event of a secondary device fault.
  • Page 49: Parallel Connection For Redundancy

    Applications 9.2 Parallel connection for redundancy Parallel connection for redundancy The parallel switching of several LOGO!Power power supplies of the same type for redundancy is required when the demands for reliability of the supply are particularly high. If a component in the redundant supply fails, the power supply for the loads must be fully accommodated by the remaining component.
  • Page 50: Series Connection For Increased Voltage

    Applications 9.3 Series connection for increased voltage Series connection for increased voltage To achieve a higher output voltage, two LOGO!Power power supplies of the same type can be connected in series. In this case, connect the "-" terminal of the first power supply to the "+"...
  • Page 51: Protection Against Short-Time Voltage Dips

    Applications 9.4 Protection against short-time voltage dips Protection against short-time voltage dips During a drop in the primary-side supply voltage, the LOGO!Power power supplies still maintain the output voltage over a short millisecond period (see Section Technical data (Page 27)). LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 52 Applications 9.4 Protection against short-time voltage dips LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 53: Environment

    Environment The device is in conformance with RoHS. As a rule, only non-silicon precipitating materials are used. Disposal guidelines Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse. LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 54 Environment LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629...
  • Page 55: Service And Support

    ● Phone: + 49 (0) 911 895 7222 ● E-Mail (mailto:support.automation@siemens.com) ● Internet: Online support request form (http://www.siemens.de/automation/support-request) Technical documentation on the Internet Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (http://www.siemens.de/sitop/manuals) SITOP power supply homepage General news about our power supplies is available in the Internet at the SITOP homepage: SITOP (http://www.siemens.de/sitop)
  • Page 56 Service and support Contact persons If you have any questions regarding the use of our products, then contact the Siemens contact person in your regional Siemens sales office. You can find these addresses as follows: ● On the Internet (http://www.siemens.de/automation/partner) ●...

Table of Contents