ABB general purpose drives Quick installation and start-up guide ACS580-01 drives Frames R1 to R9...
Page 2
List of related manuals in English Drive manuals and guides Code (English) ACS580 standard control program firmware manual 3AXD50000016097 ACS580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware 3AXD50000018826 manual ACS-AP-X assistant control panels user’s manual 3AUA0000085685 Option manuals and guides...
Table of contents 3 Table of contents List of related manuals in English R1…R4 Ratings and fuses I ............... . . 7 II .
Page 4
4 Table of contents Frame R5 R5 Quick installation guide Obey the safety instructions ..........31 Check if capacitors need to be reformed .
Page 5
Providing feedback on ABB Drives manuals ........
Page 6
6 Table of contents [Page intentionally left blank]...
Page 7
R1…R4 Ratings and fuses Type Input Output ratings Maximum Frame ACS580- rating heat size dissipation Nominal use Heavy duty use 3-phase U = 480 V (440…480 V) 02A1-4 0.75 03A0-4 03A5-4 04A8-4 06A0-4 07A6-4 012A-4 014A-4 023A-4 027A-4 034A-4 044A-4 052A-4 065A-4 1024...
Page 8
023A-4 JJS-30 027A-4 JJS-40 034A-4 JJS-50 044A-4 JJS-60 052A-4 JJS-80 065A-4 JJS-90 1) ABB does not require Bussmann brand fuses. Fuses which meet the appropriate UL class type, current rating, and are rated at 600V, 200 kA may be used.
Page 9
ACS580 3-phase U = 480 V (440…480 V) 077A-4 JJS-100 096A-4 JJS-150 1) ABB does not require Bussmann brand fuses. Fuses which meet the appropriate UL class type, current rating, and are rated at 600V, 200 kA may be used.
Page 11
JJS-300 240A-4 JJS-350 260A-4 JJS-400 361A-4 JJS-500 414A-4 JJS-600 1) ABB does not require Bussmann brand fuses. Fuses which meet the appropriate UL class type, current rating, and are rated at 600V, 200 kA may be used. 3AXD50000009286 Rev D...
R1…R4 Quick installation guide 15 R1…R4 Quick installation guide This guide briefly describes how to install the drive. For complete information on installation, see ACS580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000018826 [English]). For start-up instructions, see chapter Quick start-up guide on page 55.
Protective Earth conductor using a measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm (reference value at 25 °C or 77 °F). For the insulation resistance of other motors, see the manufacturer’s instructions.
R1…R4 Quick installation guide 17 Switch off the power and open the cover See figure on page 67. 2. Switch off the power from the drive. 3. Remove the front cover: Loosen the retaining screw, if any, with a screwdriver (3a) and lift the cover from the bottom outwards (3b) and then up (3c).
18 R1…R4 Quick installation guide Ground-to-phase varistor The ground-to-phase varistor is not suitable for use on an IT (ungrounded) system. Disconnect the ground-to-phase varistor before connecting the drive to the supply network. Check the table on page 18. WARNING! Do not install the drive with the ground-to-phase varistor connected on an IT system (an ungrounded power system or a high- resistance-grounded [over 30 ohms] power system), otherwise the varistor circuit can be damaged.
R1…R4 Quick installation guide 19 Disconnect EMC filter or ground-to-phase varistor, if needed To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as follows: 1. Switch off the power from the drive. 2. Open the front cover, if not already opened, see figure on page 67.
20 R1…R4 Quick installation guide Wiring R1...R2 Note: These are instructions for conduit wiring. For cable wiring, see the ACS580 Hardware manual, publication number 3AXD50000018826. Note: In US deliveries, options are already installed at the factory. If installing on site, option slot 1 modules (fieldbus adapter) may be installed by mounting the module on the control board and tightening the mounting screw, which is also the grounding screw.
Page 21
R1…R4 Quick installation guide 21 10. Strip the control cable sheathing and twist the copper screen into a pig-tail. 11. Refer to page 27. Connect the ground screen pig-tail for digital and analog I/O cables. (Ground only at drive end.) 12.
Page 22
22 R1…R4 Quick installation guide R1...R2 Type 12 Analog Inputs and Outputs Option Mounting Digital Inputs Relay Outputs Typical Type 1 Power wiring torque table Frame size lb-ft lb-ft T1/U, T2/V, T3/W 1.2...1.5 1.2...1.5 L1, L2, L3 1.2...1.5 1.2...1.5 R+, R- 1.2...1.5 1.2...1.5 PE Ground...
R1…R4 Quick installation guide 23 Wiring R3 Note: These are instructions for conduit wiring. For cable wiring, see the ACS580 Hardware manual, publication number 3AXD50000018826. Note: In US deliveries, options are already installed at the factory. If installing on site, option slot 1 modules (fieldbus adapter) may be installed by mounting the module on the control board and tightening the mounting screw, which is also the grounding screw.
Page 24
24 R1…R4 Quick installation guide 12. Strip and connect the individual control wires to the drive terminals. Tighten the screws to 0.4 lb-ft (0.5…0.6 N-m). WARNING! To avoid danger or damage to the drive on IT systems and corner grounded TN systems, see section Check the compatibility with IT (ungrounded) and corner-grounded TN systems on page 17.
R1…R4 Quick installation guide 25 Wiring R4 Note: These are instructions for conduit wiring. For cable wiring, see the ACS580 Hardware manual, publication number 3AXD50000018826. Note: In US deliveries, options are already installed at the factory. If installing on site, option slot 1 modules (fieldbus adapter) may be installed by mounting the module on the control board and tightening the mounting screw, which is also the grounding screw.
Page 26
26 R1…R4 Quick installation guide WARNING! To avoid danger or damage to the drive on IT systems and corner grounded TN systems, see section Check the compatibility with IT (ungrounded) and corner-grounded TN systems on page 17. R4 Type 12 Analog Inputs Panel Connector and Outputs...
R1…R4 Quick installation guide 27 Default I/O connections Default I/O connections of the ABB Standard macro are shown below. Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference: 0…10 V 1…10 kohm AGND Analog input circuit common...
28 R1…R4 Quick installation guide Install optional modules, if any See chapter Electrical installation in ACS580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000018826 [English]). Reinstall cover See figure on page 70. 1. Put the tabs on the inside of the cover top in their counterparts on the housing (1a) and then press the cover at the bottom (1b).
R5 Quick installation guide 31 R5 Quick installation guide This guide briefly describes how to install the drive. For complete information on installation, see ACS580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000018826 [English]). For start-up instructions, see chapter Quick start-up guide on page 55.
Protective Earth conductor using a measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm (reference value at 25 °C or 77 °F). For the insulation resistance of other motors, see the manufacturer’s instructions.
R5 Quick installation guide 33 Switch off the power and open the cover See figure on page 71. 2. Switch off the power from the drive. 3. IP21, Remove the module cover: Loosen the retaining screws with a screwdriver (3a) and lift the cover from the bottom outwards (3b) and then up (3c). 4.
Page 34
34 R5 Quick installation guide Check from the table below if you have to disconnect the EMC filter (EMC) or ground- to-phase varistor (VAR). For instructions on how to do this, see page 35. Frame Ground- Symmetrically Corner grounded IT systems sizes filter to-phase...
R5 Quick installation guide 35 Disconnect EMC filter or ground-to-phase varistor, if needed To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as follows: 1. Switch off the power from the drive. 2. Open the front cover, if not already opened, see figure on page 71.
Page 36
36 R5 Quick installation guide See figure on page 37. 1. Install thin-wall conduit clamps for IP21/UL Type 1 or liquid-tight conduit connectors for IP55/UL Type 12 (not supplied). Type 12 has a Pressfit gasket. 2. Connect conduit runs for input power, motor and control cables to the conduit box. Ensure grommets (pointing down) are inserted into all unused holes.
Page 37
R5 Quick installation guide 37 WARNING! To avoid danger or damage to the drive on IT systems and corner grounded TN systems, see section Check the compatibility with IT (ungrounded) and corner-grounded TN systems on page 33. Analog Inputs and Outputs R5 Type 12 Panel Connector Power (Green) and...
38 R5 Quick installation guide Default I/O connections Default I/O connections of the ABB Standard macro are shown below. Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference: 0…10 V 1…10 kohm AGND Analog input circuit common...
R5 Quick installation guide 39 Install optional modules, if any See chapter Electrical installation in ACS580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000018826 [English]). Reinstall cover See figure on page 74. 1. IP21, Reinstall the box cover: Slide the cover upwards (1a) and tighten the retaining screws (1b).
R6…R9 Quick installation guide 43 R6…R9 Quick installation guide This guide briefly describes how to install the drive. For complete information on installation, see ACS580-01 (0.75 to 250 kW) hardware manual (3AXD50000018826 [English]). For start-up instructions, see chapter Quick start-up guide on page 55.
-15 to +50 °C (+5 to +122 °F). No condensation or frost is allowed. For more information on the ambient temperature and derating, see chapter Technical data in ACS580-01 (0.75 to 250 kW) hardware manual (3AXD50000018826 [English]). Protect the drive and input power cable...
Protective Earth conductor using a measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm (reference value at 25 °C or 77 °F). For the insulation resistance of other motors, see the manufacturer’s instructions.
Page 46
46 R6…R9 Quick installation guide WARNING! Do not install the drive with the ground-to-phase varistor connected on an IT system (an ungrounded power system or a high-resistance-grounded [over 30 ohms] power system), otherwise the varistor circuit can be damaged. Check from the table below if you have to disconnect the EMC filter (EMC) or ground- to-phase varistor (VAR).
R6…R9 Quick installation guide 47 Disconnect EMC filter or ground-to-phase varistor, if needed To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as follows: 1. Switch off the power from the drive. 2. Open the front cover, if not already opened, see steps 5, IP21 and 5, IP55 in figure R6…R9 Figures A on page 3.
48 R6…R9 Quick installation guide Wiring R6…R9 Note: These are instructions for conduit wiring. For cable wiring, see the ACS580 Hardware manual, publication number 3AXD50000018826. Note: In US deliveries, options are already installed at the factory. If installing on site, see the appropriate option module manual for specific installation and wiring.
Page 49
R6…R9 Quick installation guide 49 R7 Type 12 Analog Inputs and Outputs Panel Connector Power (Green) and Fault (Red) LEDs Digital Inputs Relay Outputs Shroud Typical Type 1 Note: UDC+ and UDC- terminals are used for external brake chopper units. Power wiring torque table Frame size lb-ft...
50 R6…R9 Quick installation guide Default I/O connections Default I/O connections of the ABB Standard macro are shown below. AI1 U/I Voltage/Current selection for AI1: AI2 U/I Voltage/Current selection for AI2: Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference: 0…10 V...
R6…R9 Quick installation guide 51 Install optional modules, if any See chapter Electrical installation in ACS580-01 (0.75 to 250 kW) hardware manual (3AXD50000018826 [English]). Install side plates and covers See figure R6…R9 Figures E on page 77. IP21 1. Reinstall the side plates of the cable entry box. Tighten the retaining screws with a screwdriver.
Quick start-up guide This guide describes how to start-up the drive using the First start assistant on the assistant control panel. Before you start Ensure that the drive has been installed as described in chapter R1…R4 Quick installation guide on page 15, in chapter R5 Quick installation guide page or in...
Page 56
The First start assistant guides you through the first start-up. The assistant begins automatically. Wait until the control panel enters the view shown on the right. Select the language you want to use by highlighting it (if not already highlighted) and pressing (OK).
Page 57
Refer to the motor nameplate for the following nominal value settings of the motor. Enter the values exactly as shown on the motor nameplate. Example of a nameplate of an induction (asynchronous) motor: ABB Motors motor M2AA 200 MLA 4 IEC 200 M/L 55 Ins.cl.
Page 58
Check that the motor data is correct. Values are predefined on the basis of the drive size but you should verify that they correspond to the motor. Start with the motor type. Motor nominal cosΦ and nominal torque are optional. Press (Next) to continue.
Page 59
The first start is now complete and the drive is ready for use. Press (Done) to enter the Home view. The Home view monitoring the values of the selected signals is shown on the panel. 2 – Additional settings in the Primary settings menu Make any additional adjustments, for example macro, ramps and limits, starting from the Main menu –...
Page 60
2 – Additional settings: Start, stop and reference values If you do not wish to use a macro, define the settings for start, stop and reference: Select Start, stop, reference and press (Select) (or Adjust the parameters according to your needs. Select a parameter and, depending on the parameter type, press (Edit) or press...
Page 61
2 – Additional settings: Limits Select Limits and press (Select) (or Adjust the parameters according to your needs. Select a parameter and press (Edit). After making the adjustments, go back to the Primary settings menu by pressing (Back).
Page 79
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.