Parameterization
9.4 Parameters
P09
Designation on
Qn,
ATC display
n=1...2
P09.n.19 INTERNAL SRC
CONTROL
P09.n.20 CHANNEL NO.
OFF = The voltage measurement in the OFF mode is disabled.
1)
ON = The voltage measurement in the OFF mode is enabled.
2)
OFF+GLOB = The voltage measurement in the OFF mode is disabled but the relay programmed for the global alarm
3)
function is either tripped or not, depending on whether the source is present or missing.
ON+GLOB = The voltage measurement in the OFF mode is enabled and the relay programmed for the global alarm
4)
function is either tripped or not, depending on whether the source is present or missing.
176
Description
Enable control of the source
- With this parameter it is possible to set whether the source is
only regarded as OK subject to a condition.
OFF = The source can be connected normally.
Every other setting = The source can only be used if the variable
is active.
Function index (x)
- Index that is possibly assigned to the function programmed in
the previous parameter.
Example:
Source 1 should only be controllable if the input 4 has been ena-
bled:
P08.1.19 = INPx
P08.1.20 = 4
Unit
De-
Range
fault
OFF OFF
INPx
OUTx
LIMx
REMx
Ax
Uax
TIMx
OFF OFF / 1-
99
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01