SINGLE ZONE MEGA AND MEGA 115V WALL MOUNTED ENGINEERING MANUAL 3/4, 1, 1-1/2, and 2 Tons 3/4 and 1 Tons Mega Models: LS090HEV2 LS180HEV2 Mega 115V Models: LS120HEV2 LS240HEV2 LS090HXV LS120HXV...
TABLE OF CONTENTS Unit Nomenclature...........................................4 LG Air Conditioner Technical Solution (LATS)................................5-6 Mega and Mega 115V Product Data...................................7-48 Mechanical Specifications......................................8 General Data.........................................9 Electrical Data..........................................12 Functions, Controls, Options......................................13 Outdoor Unit Dimensions......................................14-17 Indoor Unit Dimensions......................................18-20 Acoustic Data ........................................21-26 Refrigerant Flow Diagrams....................................27-28 Wiring Diagrams--Indoor Units....................................29-30 Wiring Diagrams--Outdoor Units....................................31-33...
UNIT NOMENCLATURE Single Zone Wall Mount Indoor and Outdoor Units Family LA= Art Cool Premier / Gallery / Mirror LS= High Efficiency Wall Mount / Standard / Mega Type N = Indoor Wall Mount Unit U = Outdoor Heat Pump Unit Nominal Capacity (Nominal cooling capacity in Btu/h) 090 = 9,000...
Contact your LG Rep for the best software program for your application. To reduce the risk of designing an improper applied system or one that will not operate correctly, LG requires that LATS software be used on all projects.
Page 6
LATS can generate an Excel GERP report that can imported into the LG SOPS pricing and ordering system.
Page 7
PRODUCT DATA Mechanical Specifications on page 8 General Data on page 9 Electrical Data on page 12 Functions, Controls, Options on page 13 Outdoor Unit Dimensions on page 14 Indoor Unit Dimensions on page 18 Acoustic Data on page 21 Refrigerant Flow Diagrams on page 27 Wiring Diagrams—Indoor Units on page 29 Wiring Diagrams—Outdoor Units on page 31...
General mulator, four-way reversing valve, EEV, high and low side charging ports, service valves, LG Single Zone Mega Wall Mounted systems and interconnecting piping. comprise of a single outdoor unit connected to a single indoor unit with a single refriger- ant circuit.
GENERAL DATA Mega Pairing Table The following table shows the available outdoor and indoor unit, along with the factory provided controller. Table 1: Single Zone Mega and Mega 115V Pairing Table Outdoor Unit Model Indoor Unit Model Controller Mega Inverter LSU090HEV2 LSN090HEV2 AKB74955602...
Page 10
GENERAL DATA Table 2: LS090HEV2 LS120HEV2 LS180HEV2 LS240HEV2 System Model Number (IDU/ODU) (LSN090HEV2/ (LSN120HEV2/ (LSN180HEV2/ (LSN240HEV2/ LSU090HEV2) LSU120HEV2) LSU180HEV2) LSU240HEV2) Cooling Capacity (Min/Rated/Max) (Btu/h) 3,070 ~ 9,000 ~10,330 3,070 ~ 12,000 ~ 13,780 3,685 ~ 18,000 ~ 18,493 3,685 ~ 22,000 ~ 24,000 Cooling Power Input (kW) 0.72...
Page 11
GENERAL DATA Table 3: System Model Number (IDU/ODU) LS090HXV (LSN090HXV/LSU090HXV) LS120HXV (LSN120HXV/LSU120HXV) Cooling Capacity (Min/Rated/Max) (Btu/h) 1,023 ~ 8,500 ~ 13,785 1,023 ~ 12,000 ~ 13,785 Cooling Power Input (kW) 0.71 1.14 Heating Capacity (Min/Rated/Max) (Btu/h) 1,023 ~ 10,900 ~ 22,178 1,023 ~ 13,000 ~ 22,178 Heating Power Input (kW)
ELECTRICAL DATA Electrical Data Table 4: 208-230V, 60Hz, 1-Phase Single-Zone Mega System Electrical Data Table. Compressor Motor Outdoor Fan Motor Indoor Fan Motor Nominal Unit Model Voltage Range Compressor Hertz Voltage Tons (Min. to Max.) Quantity Cooling Heating LS090HEV2 10.0 LS120HEV2 10.0 208 - 230...
Dry contact Central control (LGAP) PI 485 Zone control CTIE Electro thermostat Wi-Fi Module (Option) Water level sensor connection (for optional AG-9300-LG) Wind baffle kit Mode Lock Cooling Only or Heating Only Temperature Control Thermistor Smart Inverter Monitoring System (SIMS) Primary washable filters.
Page 16
OUTDOOR UNIT CORNER WEIGHT AND CENTER OF GRAVITY DIMENSIONS Figure 3: LSU090-120-180-240HEV2 Outdoor Unit Corner Weight and Center of Gravity Dimensions. Table 7: LSU090-120-180-240HEV2 Outdoor Unit Corner Weight and Center of Gravity Dimensions. Weight (lb.) Center of Gravity (Inch) Leg (Inch) Corner Weight (lb.) Model No.
Page 20
INDOOR UNIT DIMENSIONS LSN090HXV, LSN120HXV 8-5/16 34-7/8 15/16 Return Air Grille 2-5/16 for piping and cable 6-5/16 Place a level on raised tab Unit Outline 17-7/16 17-7/16 Ø 2-13/16 Ø2-13/16 Installation Plate Left rear Right rear piping piping 3-3/4 5-1/4 6-15/16 8-9/16 Unit: Inch...
ACOUSTIC DATA Indoor Unit Sound Pressure Measurement / Sound Pressure Levels • Measurements are taken 3.3 ft away from the front of the unit. Figure 4: Mega Indoor Unit Sound Level Measurement. • Sound pressure levels are measured in dB(A) with a tolerance of ±1.
Page 22
ACOUSTIC DATA LSN120HEV2 and LSN180HEV2 Sound Pressure Levels Figure 6: Sound Pressure Levels for Mega LSN120HEV2 Indoor Units. LSN120HEV2 Cooling Heating High High Middle Middle NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25...
Page 23
ACOUSTIC DATA LSN240HEV2 Sound Pressure Levels Figure 8: Sound Pressure Levels for Mega LSN180HEV2 Indoor Units. LSN240HEV2 Cooling Heating High High Middle Middle NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 Approximate Approximate...
Page 24
ACOUSTIC DATA Outdoor Unit Sound Pressure Measurement / Sound Pressure Levels Figure 10: Outdoor Unit Sound Levels • Measurements are taken 3.3 ft away from the front of the unit. • Sound pressure levels are measured in dB(A) with a tolerance of ±1.
Page 25
ACOUSTIC DATA LSU120HEV2 and LSU180HEV2 Sound Pressure Levels Figure 12: Sound Pressure Levels for Mega LSU120HEV2 Outdoor Units. LSU120HEV2 Cooling Heating Front Front Back Back NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25...
ELECTRICAL CONNECTIONS General Power Wiring / Communications Cable Guidelines • Follow manufacturer’s circuit diagrams displayed on the inside of the control box cover. • Have a separate power supply for the indoor units. • Provide a circuit breaker switch between the power source and the indoor unit. •...
Page 35
ELECTRICAL CONNECTIONS Figure 16: LS090HEV2 and LS120HEV2 General Power / Communica- Figure 17: LS180HEV2 and LS240HEV2 General Power / Communica- tions System Schematic. tions System Schematic. Power Supply Power Supply Circuit Breaker Circuit Breaker Indoor Unit Indoor Unit Ground Wiring Ground Wiring Outdoor Unit Outdoor Unit...
Page 36
Buttons on the AKB73456121 will (Model Nos. AKB74955602 [Mega] and AKB73456121 [Mega 115V]). Optional LG-suppled wired control- differ. lers are available for the Mega 115V units. See “Functions, Controls, Options”, or contact an LG repre- sentative for more information. Wireless Handheld Remote Controller features: Display •...
Page 37
ELECTRICAL CONNECTIONS Figure 24: PZCWRC1 LG Wired Remote Extension Cable for Use with the Mega 115V. Verify the connectors are properly inserted. C/BOX Cable (Plug type) To Indoor Unit SPEED CN-REMO TEMP OPER MODE Terminal Extension cable Figure 25: Wired Controller Connection on the Mega 115V Indoor Unit Terminal Block.
Page 38
AIR FLOW, STATIC PRESSURE, AND TEMPERATURE DISTRIBUTION Table 14: Mega and Mega 115V Outdoor Unit Air Flow Rate and Static Pressure. Model No. Air Flow Rate (CFM) Static Pressure (in. WG) LSU090HEV2, LSU120HEV2 0.0284 LSU180HEV2, LSU240HEV2 1,730 0.0387 LSU090HXV, LSU120HXV 0.0384 LSN090HEV2 Cooling...
Page 39
AIR FLOW AND TEMPERATURE DISTRIBUTION LSN090HEV2, continued. Heating Air Velocity [m/s (ft./s)] ( )] 28(82) 22(72) 26(79) 2(6.6) 0.3(1) 24(75) 0.5(1.6) 1(3.3) 32.8 26.2 19.7 13.1 32.8 26.2 19.7 13.1 Side View Discharge Vertical Louver : Center Air Velocity [m/s (ft./s)] Air Velocity [m/s (ft./s)] 16.4 16.4...
Page 40
AIR FLOW AND TEMPERATURE DISTRIBUTION LSN120HEV2 Cooling Air Velocity [m/s (ft./s)] 22(72) 24(75) 2(6.6) 26(79) 0.3(1) 28(82) 0.5(1.6) 1(3.3) 32.8 26.2 19.7 13.1 32.8 26.2 19.7 13.1 Side View Discharge Vertical Louver : Center Air Velocity [m/s (ft./s)] Air Velocity [m/s (ft./s)] 16.4 16.4 0.3(1)
When connected through the indoor unit, user will not be able to record data. This software can be used to both commission new systems and troubleshoot existing systems. LGMV data can be recorded to a “.CSV” file and emailed to an LG representative to assist with diagnostic evaluations. Recommended Minimum PC Configuration: •...
Page 48
SIMs consists of a hardware Wireless Local Area Network (WLAN) module, an interface cable, and a free downloadable application (app) for iOS® or Android™. The user must supply either an Apple® or an Android smart phone; SIMs is not optimized for tablets, and only be used with LG single zone and Multi F systems.
PERFORMANCE DATA Cooling Capacity Data on page 50 Heating Capacity Data on page 53 Maximum Heating Capacity Data on page 55 Equipment Selection Procedure on page 57...
EQUIPMENT SELECTION PROCEDURE Cooling / Heating Correction Factors For Single Zone Mega Wall Mounted systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, determine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correc- tion factors as shown below.
Page 58
• Use caution when sizing to meet listed capacity specifications for the scheduled manufacturer’s equipment. If further system design assistance is needed, or you have a unique application you would like to discuss, contact your LG sales rep. 58 | PERFORMANCE DATA...
Page 59
APPLICATION GUIDELINES Placement Considerations on page 60 Installing Outdoor Units Indoors on page 65 Design Guideline Summary on page 68...
PLACEMENT CONSIDERATIONS Selecting the Best Location for the Indoor Unit Figure 28: Mega Indoor Unit Clearance Requirements. Follow recommended best practices when choosing an indoor location for the Unit: Inch (mm) single zone indoor unit. >8 (200) • Follow the table at right for minimum clearance of indoor unit from the top of the unit to the ceiling.
Page 61
PLACEMENT CONSIDERATIONS Selecting the Best Location for the Outdoor Unit DANGER • Do not install the unit in an area where combustible gas will generate, flow, stagnate, or leak. These conditions can cause a fire, result- ing in bodily injury or death. •...
Page 62
PLACEMENT CONSIDERATIONS Planning for Snow and Ice, continued. When deciding on a location to place the outdoor unit, be sure to choose an area where run-off from defrost will not accumulate and freeze on sidewalks or driveways, which will create unsafe conditions. Properly install and insulate any drain hoses to prevent the hose from freezing, cracking, leaking, and causing unsafe conditions from frozen condensate.
Page 63
PLACEMENT CONSIDERATIONS Oceanside Applications Figure 32: Oceanside Placement Using Windbreak. Use of a Windbreak to Shield from Sea Wind Windbreak Ocean winds will cause corrosion, particularly on the condenser and • Avoid installing the outdoor unit where it would be directly Sea wind exposed to ocean winds.
Page 64
PLACEMENT CONSIDERATIONS Minimum Allowable Clearance and Service Access Requirements Proper clearance for the outdoor unit coil is critical for proper operation. When installing the outdoor unit, consider service, inlet and outlet, and minimum allowable space requirements as illustrated in the diagrams below. •...
PLACEMENT CONSIDERATIONS Installing Outdoor Units Indoors Single Zone Mega and Mega 115V Wall Mount outdoor units are engineered to be mounted outdoors and include technology designed to minimize the negative effects of winter weather’s freezing rain, sleet, and snow. Some building projects, however, necessitate placing the HVAC outdoor units indoors: •...
Page 66
PLACEMENT CONSIDERATIONS Provide a means to drain the condensate generated during heating mode and defrost cycle in addition to rainwater that infiltrates the inlet louver enclosed area. • Install a field-provided drain pan under the outdoor units and provide a path to a nearby floor drain. •...
Page 67
PLACEMENT CONSIDERATIONS Open Rate by Louver Radian Figure 37: Open Rate by Louver Radian Formula. ho = h * COS Total Area (A) = H * W Number of Open Spaces (N) = (Number of Louvers - 1) Effective Area (Af) = ho * W * N Louver Open Rate (n) = Af / A Af = A * n Side View...
REFRIGERANT PIPING DESIGN Device Connection Limitations Figure 39: Mega and Mega 115V System Layout. Max Length = A Single-zone systems consist of one outdoor unit and one indoor unit. One of Unit = Feet Max Elevation = B the most critical elements of a single zone system is the refrigerant piping. The table below lists pipe length limits that must be followed in the design of a Single Zone Mega or Mega 115V refrigerant pipe system.
Page 69
20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics, U.S.A., Inc. Commercial Air Conditioning Division EM-SZ_Mega_Mega115V_HEV2_HXV__05_19 4300 North Point Parkway Supersedes: EM-SZ_Mega_Mega115V-3-16 EM- Alpharetta, Georgia 30022 SZ_Mega_Mega115V-4-15 www.lghvac.com EM-SZ_Mega_Mega115V-10-14...