Single zone extended piping wall mounted (78 pages)
Summary of Contents for LG LS240HEV2
Page 1
SINGLE ZONE MEGA, STANDARD EFFICIENCY, AND MEGA 115V WALL MOUNTED INSTALLATION MANUAL Single Zone Mega: LS090HEV2, LS120HEV2, LS180HEV2, LS240HEV2 Single Zone Standard Efficiency: LS090HFV3, LS120HFV3, LS180HFV3, LS240HFV3 Single Zone Mega 115V: LS090HXV2, LS120HXV2...
Always follow local codes when selecting and installing copper pipe and piping system components. Approved piping for use with LG Single Zone products will be marked “R410 RATED” along the length of the pipe. Piping wall thickness must meet local code requirements and be approved for a maximum operating pressure of 551 psi. When bending piping, try to keep the number of bends to a minimum, and use the largest radii possible to reduce the equivalent length of installed piping;...
Failure to do so will cause significant performance degradation. Proper leak checks must be performed. Using isolation valves does not automatically void any LG product warranty, however, a limited warranty will be voided in whole or part if any field supplied accessory fail in any way that causes product failure.
Page 33
Pipe Sleeves at Penetrations LG recommends that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the sleeve.
FLARING AND BRAZING PROCEDURES Flaring and Brazing Procedures One of the main causes of refrigerant leaks is a defective connection. For LG HVAC systems, the installer needs to know how perform both flared and brazed connections successfully. • During installation, it is imperative to keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust.
Refer to the table below and on the next page for error codes that are generated from the indoor and outdoor units. These codes are the most common. Your particular system might generate additional codes not listed here. Please contact LG Support if you see these types of errors and a simple power cycle has not corrected the issue.
Communication / connection (power) wiring from the outdoor unit to the indoor unit can be run in the same conduit. Communication type RS-485–BUS type. LG-supplied cable was used; or 22-3 AWG, twisted, stranded, unshielded cable (minimum) was used between the indoor unit and its zone controller. No cables were spliced, and no wire caps are present.
Page 75
20001747 ISO 9001: 2008 LG ELECTRONICS INC. IM_SZ_Wall_Mounted_HEV2_HFV3_HXV2_05_21 LG Electronics, U.S.A., Inc. Supersedes: IM_SZ_Mega_Mega115V_HEV2_HXV2_04_20 Air Conditioning Technologies IM_SZ_Mega_Mega115V_HEV2_HXV2_08_19 4300 North Point Parkway IM_SZ_Mega_Mega115V_HEV2_HXV_06_19 Alpharetta, Georgia 30022 IM_WallMounted_All_11_15 www.lghvac.com IM_WallMounted_All_08_15...