Honeywell QXe Recorder Installation Instruction
Honeywell QXe Recorder Installation Instruction

Honeywell QXe Recorder Installation Instruction

Touch screen assembly

Advertisement

Quick Links

QXe Recorder - Installation Instruction
Touch Screen Assembly
This Installation Instruction sheet is intended as a guide for replacing or installing hardware and for setting up
functionality in the recorder. Refer to the User manual for detailed operational requirements.
The QXe Recorders are designed for ease of assembly with minimal disturbance to the rest of the unit. If unsure, please
return the unit to your supplier for repair or upgrade.
Removing the case and opening the back of the recorder should only be performed under the following circumstances:
When an item of hardware requires individual replacement.
When an item of hardware is to be retrospectively fitted.
In all other instances it is recommended that the complete unit be returned to an authorised agent or service centre.
For Agency Approved recorders the product needs to be upgraded or repaired by an Authorized Repair facility
WARNING
HAZARDOUS VOLTAGES
Disconnect all power to the recorder before removing the case and attempting any maintenance procedures.
SAFETY TESTS
Upon completion of service procedures detailed in this manual two basic safety tests should be performed in order to
ensure continued safe operation of the instrument.
Earth Resistance; 25 VDC applied between case and protective earth, bonding resistance should be < 0.1 Ohm.
Insulation Resistance; 500Vdc applied between the earth terminal, and the live and neutral terminal shorted together,
insulation resistance to be >2.0 MOhm. (Mega Ohm, NOT milli Ohm)
Failure to comply with these instructions could result in death or serious injury
CAUTION
OBSERVE ANTI-STATIC PRECAUTIONS
Refer to BS EN61340-5-1: 2001. Basic specification. Protection of electrostatic sensitive devices.
Full anti-static precautions MUST be observed when in contact with the electronics of your recorder.
SAVE DATA, SETUPS AND LAYOUTS
Removal of PCBs and battery back-up will result in the loss of all non-volatile data.
Ensure all data and set-ups are saved.
Failure to comply with these instructions may result in product damage.
43-TV-33-88 iss.2 GLO Nov 06 UK
QXe Recorder
1

Advertisement

loading

Summary of Contents for Honeywell QXe Recorder

  • Page 1 QXe Recorder - Installation Instruction Touch Screen Assembly QXe Recorder This Installation Instruction sheet is intended as a guide for replacing or installing hardware and for setting up functionality in the recorder. Refer to the User manual for detailed operational requirements.
  • Page 2: Panel Mounting

    Before attempting to repair or upgrade a recorder, it is advisable to clear a sufficient work space so components such as the front panel can be rested on the work surface without getting scratched or damaged. Panel Mounting Before a new Touch Screen assembly can be fitted the recorder must be removed from the panel. Loosen the mounting clamp screws, slide the clamp towards the rear of the recorder and remove the clamps and the recorder.
  • Page 3 Removing the Front Surround Assembly Fig 2 Remove 2 self tapping screws both sides To remove the Front Surround assembly remove the 2 self tapping screws, as shown in Fig 2, on both sides of the recorder. Retain these screws for fitting of the new front surround assembly. When the 4 screws have been removed the complete Front Surround Assembly can be gentle pulled forward to release it from the chassis plates.
  • Page 4 Removing the Front Surround Assembly Fig 4 Front Surround assembly Remove 4 self tapping screws Once the front surround assembly is removed it can be dis-assembled to replace the touch screen assembly. Remove the 4 self tapping screws as shown in Fig 4 above, two at the top of the assembly and one each side at the bottom.
  • Page 5 Take the new touch screen assembly and remove any protective covering from the inside of the touch screen. Take care not do get fingerprints or dirt onto the back of the touch screen. Once assembled it will be impossible to remove any dirt or marks trapped between the display and the touch screen.
  • Page 6: Touch Screen Calibration

    Re-fit the case and back panel assembly Fit the case by carefully sliding it on from the rear of the recorder. Ensure the case is orientated correctly, with the power supply cooling slots on the top of the recorder. Slide the case/back panel fully forward ensuring that no internal cables get trapped between the case and front bezel. The case should sit flat on the back of the front bezel.