Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide First Published: 2018-10-24 Last Modified: 2019-03-28 Americas Headquarters Cisco Systems, Inc. 170 West Tasman Drive San Jose, CA 95134-1706 http://www.cisco.com Tel: 408 526-4000 800 553-NETS (6387) Fax: 408 527-0883...
Page 2
Cisco and the Cisco logo are trademarks or registered trademarks of Cisco and/or its affiliates in the U.S. and other countries. To view a list of Cisco trademarks, go to this URL: https://www.cisco.com/go/trademarks. Third-party trademarks mentioned are the property of their respective owners. The use of the word partner does not imply a partnership relationship between Cisco and any other company.
Minimizing Electromagnetic and Radio Frequency Interference Shock and Vibration Requirements Grounding Requirements Planning for Power Requirements Airflow Requirements Rack and Cabinet Requirements Clearance Requirements C H A P T E R 3 Installing the Switch Chassis Safety Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 4
Replacing an AC Power Supply Replacing a DC Power Supply A P P E N D I X A Rack Specifications Overview of Racks General Requirements for Cabinets and Racks Requirements Specific to Standard Open Racks Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 5
Rack Mount Kit NXK-ACC-KIT-1RU Rack Mount Kit N3K-C3064-ACC-KIT A P P E N D I X E Site Preparation and Maintenance Records Site Preparation Checklist Contact and Site Information Chassis and Module Information Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Braces and a vertical bar within square brackets indicate a required choice within an optional element. Indicates a variable for which you supply values, in context where italics variable cannot be used. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
What's New in Cisco Product Documentation, at: https://www.cisco.com/warp/public/687/Directory/DirTAC.shtml. Subscribe to What's New in Cisco Product Documentation, which lists all new and revised Cisco technical documentation as an RSS feed and delivers content directly to your desktop using a reader application. The RSS feeds are a free service.
Overview, on page 1 Overview The Cisco Nexus 9332C switch (N9K-C9332C) is a 1-RU, fixed-port switch designed for spine-leaf-APIC deployment in data centers. This switch has 32 40/100-Gigabit QSFP28 ports and 2 SFP ports. Ports 25-32 offer hardware support for MACsec encryption.
Page 10
The following figure shows the hardware features seen from the port side of the chassis. Figure 1: Port Side View of the Cisco Nexus 9332C Switch Chassis LEDs (Beacon [BCN], Status [STS], and Environment...
Page 11
Overview Overview Figure 2: Power Supply Side View of the Cisco Nexus 9332C Switch Power supply (2), one is for operations and one USB port is for redundancy. Power supply slot 1 on the left and slot 2 on the right.
Page 12
If the switch has port-side exhaust airflow (blue coloring for fan modules), you must locate the ports in the hot aisle. If you locate the air intake in a hot aisle, the switch can overheat and shut down. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Altitude Requirements Altitude rating is based on power supply installed; see critical components list in the system CB report for altitude rating. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
The wiring is unlikely to emit radio interference if you use a twisted-pair cable with a good distribution of grounding conductors. If you exceed the recommended distances, use a high-quality twisted-pair cable with one ground conductor for each data signal when applicable. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
• Two 1100-W DC power supplies • Two 1100-W HVAC/HVDC power supplies Note Both power supplies must be the same type. Do not mix AC and DC power supplies in the same chassis. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 16
• Ensure that the protective devices are rated not greater than 10A when the switch is powered with HVDC power supplies (rated 240-350VDC). Warning Statement 1033 Connect the unit only to DC power source that complies with the Safety Extra-Low Voltage (SELV) requirements in IEC 60950 based safety standards. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Cisco Technical Assistance Center (TAC) for recommendations: • Use a standard 19-inch (48.3-cm), four-post Electronic Industries Alliance (EIA) cabinet or rack with mounting rails that conform to English universal hole spacing per section 1 of the ANSI/EIA-310-D-1992 standard. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Provide the chassis with adequate clearance to route cables, provide airflow, and maintain the switch. For the clearances required for an installation of this chassis in a four-post rack, see the following figure. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 19
Width of the front clearance area (equal to the width of the chassis with two rack-mount brackets that are attached to it). Note Both the front and rear of the chassis must be open to both aisles for airflow. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 20
Preparing the Site Clearance Requirements Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Starting the Switch, on page 26 Safety Before you install, operate, or service the switch, see the Regulatory, Compliance, and Safety Information for the Cisco Nexus 3000 and 9000 Series for important Safety Information. Warning Statement 1071 Warning Definition IMPORTANT SAFETY INSTRUCTIONS This warning symbol means danger.
You can install the switch using the following rack-mount options: • Rack-mount kit (NXK-ACC-KIT-1RU) which you can order from Cisco. This option offers you easy installation, greater stability, increased weight capacity, added accessibility, and improved removability with front and rear removal.
To prevent loss of input power, ensure the total maximum loads on the circuits supplying power to the switch are within the current ratings for the wiring and breakers. Note For AC input application, please refer to the statement below: Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Check for damage and report any discrepancies or damage to your customer service representative. Have the following information ready: • Invoice number of shipper (see packing slip) • Model and serial number of the damaged unit • Description of damage Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Determine which end of the chassis is to be located in the cold aisle as follows: • If the switch has port-side intake modules (fan modules with burgundy coloring), position the switch so that its ports will be in the cold aisle. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 26
(see the following figure). Tighten 12-24 screws to 30 in-lb (3.39 N·m) of torque and tighten 10-32 screws to 20 in-lb (2.26 N·m) of torque. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 27
Holding the chassis level, insert screws (12-24 or 10-32, depending on the rack type) in each of the two front rack-mount brackets (using a total of six screws) and into the cage nuts or threaded holes in the vertical rack-mounting rails (see the following figure). Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
• Front rack-mount brackets (2) • Rear rack-mount brackets (2) • Slider rails (2) • M4 x 0.7 x 8-mm Phillips countersink screws (12) • The rack is installed and secured to its location. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 29
Four M4 screws used to attach the bracket to the chassis chassis Rear rack-mount guide aligned to the module end of Two M4 screws used to attach the bracket to the the chassis chassis Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 30
Two customer-supplied 12-24 or 10-32 screws used rack to attach each slider rail to the rack c) Repeat Step 3 to attach the other slider rail to the other side of the rack. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 31
Holding the chassis level, insert two screws (12-24 or 10-32, depending on the rack type) in each of the two front rack-mount brackets (using a total of four screws) and into the cage nuts or threaded holes in the vertical rack-mounting rails (see the following figure). Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
This equipment must be grounded. To reduce the risk of electric shock, never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 33
Secure the grounding lug to the chassis grounding pad with two M4 screws, see the previous figure. Tighten the screws to 11 to 15 in-lb (1.24 to 1.69 N·m) of torque. Step 4 Prepare the other end of the grounding wire and connect it to the facility ground. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
3. Place the power cable negative-wire terminal ring on the negative terminal for the power source and secure them with a terminal nut. 4. Place the power cable positive-wire terminal ring on the positive terminal for the power source and secure them with a terminal nut. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 35
A setup utility automatically launches the first time that you access the switch and guides you through the basic configuration. For instructions on how to configure the switch and check module connectivity, see the appropriate Cisco Nexus 9000 Series configuration guide.
Page 36
Installing the Switch Chassis Starting the Switch Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Note To prevent sub-optimal forwarding between endpoints, connect every leaf switch in the fabric to every spine switch in the same fabric. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Cisco equipment. In situations where long parallel cable runs cannot be separated by at least 3.3 feet (1 meter), we recommend that you shield any potential noise sources by housing them in a grounded metallic conduit.
Connecting Leaf Switches to APICs You must downlink one or two (recommended for redundancy) Cisco Nexus 9300 platform ACI-mode leaf switches to each Application Policy Infrastructure Controller (APIC) in your ACI fabric. The type of virtual interface card (VIC) installed on the APIC determines the types of interface cables that you can use to connect the leaf switches to the APICs.
Connect the other end of the interface cable to a downlink port on a leaf switch. • For a Cisco 10GBASE-LR or -SR transceiver and cable, insert the transceiver into a downlink optical port on a leaf switch before connecting the cable to the transceiver.
Page 41
• If there are modular switches in the fabric, their ACI-mode line cards must already be installed. The line cards can be of the following types: • 36-port 40-Gigabit (such as: N9K-X9736PQ) • 32-port 100-Gigabit (such as: N9K-X9732C-EX) (supported by Cisco Nexus 9504 and 9508 modular switches) • 36-port 100-Gigabit (such as: N9K-X9736C-FX) Note You cannot include NX-OS line cards in the same chassis when running in ACI mode.
First-generation Cisco Nexus 9000 Series switches include those switches that do not contain an EX or an FX in the PID (product identification). Second-generation Cisco Nexus 9000 Series switches include those switches that have an EX or an FX in the PID.
Before you begin The console device must support VT100 terminal emulations and asynchronous transmissions. Step 1 Configure the terminal emulator program to match each of the following default port characteristics: • 9600 baud Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
DB-9 connector on the other end of the cable to the serial port on the console device. What to do next You can now perform the initial configuration for the switch (see the Cisco ACI Getting Started Guide). Setting Up an Optional Management Connection You can optionally set up an out-of-band management connection for monitoring and troubleshooting purposes.
Page 45
Use the narrow end of the optics extraction tool to carefully remove the transceiver module (see the following image). Step 4 Place the transceiver module in an antistatic bag or other protective environment. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
• Inspect routinely for dust and damage. If you suspect damage, clean and then inspect fiber ends under a microscope to determine if damage has occurred. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
On the fan module that you are removing, press the two sides of the fan module handle next to where it connects to the fan module and pull on the handles enough to unseat it from its connectors. Step 2 Holding the handle, pull the module out of the chassis. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Replacing an AC Power Supply You can replace an AC power supply during operations so long as the other power supply provides to the switch. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 49
Depending on the outlet receptacle on your power distribution unit, you might need the optional jumper cable to connect the switch to your outlet receptacle. e) Verify that the power supply is operational by making sure that the power supply LED is green. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
(the end with the electrical connections) to the open power supply slot before carefully sliding the power supply all the way into the slot until it clicks into place. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 51
Attach the power connector block end of the power cable to the electrical outlet on the front of the power supply. d) Turn on the circuit breaker for the power source. e) Verify that the power supply is operational by making sure that the power supply LED is green. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 52
Replacing Components Replacing a DC Power Supply Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
• Standard 19-inch (48.3 cm) (two- or four-post EIA cabinet or rack, with mounting rails that conform to English universal hole spacing per section 1 of ANSI/EIA-310-D-1992). For more information, see Requirements Specific to Perforated Cabinets, on page Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
• The roof should be perforated with at least a 20 percent open area. • The cabinet floor should be open or perforated to enhance cooling. The Cisco R Series rack conforms to these requirements. Cable Management Guidelines To help with cable management, you might want to allow additional space in the rack above and below the chassis to make it easier to route all of the fiber optic or copper cables through the rack.
(burgundy) (NXA-PAC-750W-PI) Transceiver and Cable Specifications To determine which transceivers, adapters, and cables are supported by this switch, see https://www.cisco.com/ c/en/us/support/interfaces-modules/transceiver-modules/products-device-support-tables-list.html. To see the transceiver specifications and installation information, see https://www.cisco.com/c/en/us/support/ interfaces-modules/transceiver-modules/products-device-support-tables-list.html. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
115 to 240 VAC nominal (Range: 90 to 264 VAC) Rated input frequency 50 to 60 Hz nominal (Range: 47 to 63 Hz) 1100-W AC Power Supply Specifications These specifications apply to the following power supplies: • NXA-PAC-1100W-PE • NXA-PAC-1100W-PI Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
90 A (cold turn on) Maximum hold-up time 4 ms at 100% load Power supply output voltage 12 V/ 90A Power supply standby voltage 3.3 V/ 3A Efficiency rating @ -48VDC 94% at 50% load Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Saf-D-Grid and SD connectors CAB-HVAC-C14-2M HVAC 6.6-foot (2.0 m) cable with Saf-D-Grid and C14 connector (use for up to 240 V) CAB-HVAC-RT-0.6M HVAC 2-foot (0.6 m) cable with Saf-D-Grid and RT connector Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
The 1100W DC power supply (NXA-PDC-1100W-PE/PI) is shipped with a connector already plugged into the power supply. Regulatory Standards Compliance Specifications The following table lists the regulatory standards compliance for the switch. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 62
• CNS13438 Class A EMC: Immunity • EN55024 • CISPR24 • EN300386 • KN 61000-4 series RoHS The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Temperature exceeds the major alarm threshold. The switch is not receiving power. Green Fans and power supply modules are operational. Amber At least one fan or power supply module is not operating. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Power supply is not receiving power. Green Flashing amber Power supply warning—possibly one of the following conditions: • High voltage • High power • Low voltage • Slow power supply fan Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
• M4 x 8-mm Phillips pan-head screws (2) Not applicable EAC Compliance document Not applicable Hazardous substances list for customers in China The following table lists and illustrates the console cable (CAB-CONSOLE-RJ45) that can be ordered. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Not applicable Hazardous substances list for customers in China The following table lists and illustrates the console cable (CAB-CONSOLE-RJ45) that can be ordered. Illustration Description Quantity Console cable with DB-9F and RJ-45F connectors Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Your completion of each task ensures a successful switch installation. Planning Activity Verification Time and Date Space evaluation: Space and layout Floor covering Impact and vibration Lighting Physical access Maintenance access Environmental evaluation: Ambient temperature Humidity Altitude Atmospheric contamination Airflow Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
(transceivers) EMI evaluation: Distance limitations for signaling Site wiring RFI levels Contact and Site Information Use the following worksheet to record contact and site information for the installation. Contact person Contact phone Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Use the following worksheet to record network-related information. Switch IP address Switch IP netmask Hostname Domain name IP broadcast address Gateway/router address DNS address Use the following worksheet to record information about the modules in the switch. Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...
Page 70
Site Preparation and Maintenance Records Chassis and Module Information Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide...