3. General data
3.6 Electrical data
3.6.1 Considerations
Key words:
• PH: Phase.
• IPT: Total input power.
• STC: Starting current: Less than maximum current.
• RNC: Running current.
• MC: Maximum current.
• CB: Recommended circuit breaker.
• ELB: Earth leakage breaker.
N O T E
• Heating inlet/outlet water temperature condition: 55/65 ºC.
• Outdoor ambient temperature (DB/WB): 7/6 ºC
• Specifications in these tables are subject to change without notice in order that HITACHI may bring the latest
innovations to their customers.
3.6.2 Outdoor unit
Model
Power supply
RAS-4HVRNME-AF
RAS-5HVRNME-AF
1~ 230V 50Hz
RAS-6HVRNME-AF
RAS-4HRNME-AF
RAS-5HRNME-AF
3N~ 400V 50Hz
RAS-6HRNME-AF
3.6.3 Indoor unit
Model
Power supply
RWH-4.0FSVNFE
RWH-5.0FSVNFE
1~ 230V 50Hz
RWH-6.0FSVNFE
RWH-4.0FSNFE
RWH-5.0FSNFE
3N~ 400V 50Hz
RWH-6.0FSNFE
65
TCGB0075 rev.0 - 11/2012
Applicable vol-
Compressor and fan
tage
motors
U max.
U min
STC
IPT
(V)
(V)
(A)
(KW)
2.06
253
207
2.62
3.27
-
2.06
440
360
2.62
3.27
Applicable vol-
Indoor unit system
tage
U max.
U min.
RNC
(V)
(V)
(A)
12.2
253
207
12.5
14.5
6.0
440
360
6.1
7.0
Max.
MC
CB
IPT
(A)
(A)
RNC
(kW)
(A)
9.2
3.94
18.0
20
11.6
5.75
23.0
25
14.5
5.86
23.0
25
3.0
4.72
7.0
15
3.9
6.76
11.0
20
4.8
8.16
13.0
20
Max.
MC
CB
IPT
(A)
(A)
IPT
(kW)
(kW)
2.73
5.41
24.0
32
2.78
6.31
28.0
32
3.23
6.98
31.0
32
2.73
4.80
15.0
15
2.78
4.80
15.0
15
3.23
4.80
15.0
15
3
ELB
(nº poles/A/mA)
2/40/30
4/40/30
ELB
(nº poles/A/mA)
2/40/30
4/40/30