TABLE OF CONTENTS Unit Nomenclature ..........................................4 LG Air Conditioner Technical Solution (LATS) .................................5-6 LGRED° Four-Way Ceiling-Cassette Product Data ..............................7-41 ......................................8-9 General Data .........................................10-12 Electrical Data ..........................................13 Functions, Controls, and Options ....................................14 Outdoor Unit Dimensions ......................................15-16 Outdoor Unit Center of Gravity / Corner Weights ...............................17 Indoor Unit Dimensions ......................................18-20...
UNIT NOMENCLATURE Single-Zone Indoor Units and Outdoor Units L = LG Frame Type: A: Art Cool™ S: Standard C: Four-Way Ceiling-Cassette D: Ceiling-Concealed Duct (Low Static) H: Ceiling-Concealed Duct (High Static) V: Vertical-Horizontal Air Handling N: Indoor Unit U: Outdoor Unit...
Contact your LG Rep for the best software program for your application. To reduce the risk of designing an improper applied system or one that will not operate correctly, LG requires that LATS software be used on all projects.
Page 6
LATS can generate an Excel GERP report that can imported into the LG SOPS pricing and ordering system.
PRODUCT DATA Mechanical Specifications on page 8 General Data on page 10 Electrical Data on page 13 Functions, Controls, and Options on page 14 Outdoor Unit Dimensions on page 15 Outdoor Unit Center of Gravity / Corner Weights on page 17 Indoor Unit Dimensions on page 18 Acoustic Data on page 21 Refrigerant Flow Diagrams on page 25...
Page 8
Ceiling Cassette System (LC188HHV4). System direction. A guide vane LG single zone four-way ceiling cassette system comprises of a algorithm sequentially single frame outdoor unit connected to a single indoor unit with a changes the predominant single refrigerant circuit.
Page 9
MECHANICAL SPECIFICATIONS Frequency ranges for the 18,000 ~ 48,000 Btu/h outdoor Air Filter - Indoor Figure 4: Four-Way 36,000 to 48,000 Btu/h 3x3 Ceiling Cassette units are: Unit System (LC369HHV, LC429HHV, 18k, 24k Btu/h = 10 to 95 Hz Cooling; 10 to 130 Hz Heating Return air is filtered with a and LC489HHV Models).
GENERAL DATA Pairing Table The following table shows the available outdoor and indoor unit, along with the factory provided controller. Table 1: Four-Way Ceiling Cassette System Pairing Table Outdoor Unit Model Indoor Unit Model Controller LUU180HHV LCN188HV4 PQWRHQ0FDB LUU240HHV LCN249HV AKB75735404 LUU360HHV, LUU420HHV, LUU480HHV LCN369HV...
Page 11
GENERAL DATA Table 2: Single-Zone LGRED Four-Way 2 x 2 Ceiling Cassette System General Data. System (Model) (Indoor Unit / Outdoor Unit) LC188HHV4 (LCN188HV4 / LUU180HHV) Ceiling Grille Model Number (Sold Separately) PT-UQC / PT-QCHW0 Cooling Capacity (Min ~ Rated ~ Max) (Btu/h)
Page 12
GENERAL DATA Table 3: Single-Zone LGRED Four-Way 3 x 3 Ceiling Cassette System General Data. LC249HHV LC369HHV LC429HHV LC489HHV System (Model) (Indoor Unit / Outdoor Unit) (LCN249HV/ (LCN369HV/ (LCN429HV/ (LCN489HV/ LUU240HHV) LUU360HHV) LUU420HHV) LUU480HHV) Ceiling Grille Model Number (Sold Separately) PT-AAGW0 PT-AAGW0 PT-AAGW0...
OUTDOOR UNIT CENTER OF GRAVITY / CORNER WEIGHTS Figure 7: LUU180HHV and LUU240HHV Center of Gravity and Corner Weight Diagram. Table 6: LUU180HHV and LUU240HHV Center of Gravity and Corner Weights. Weight (lb.) Center of Gravity (in.) Leg (in.) Corner Weight (lb.) Model No.
ACOUSTIC DATA Indoor Units Figure 12: Indoor Unit Sound Pressure Level • Measurements taken with no attenuation and units operating at full load normal Measurement Location. operating condition. • Sound level will vary depending on a range of factors such as construction (acoustic absorption coefficient) of particular area in which the equipment is installed.
Page 22
ACOUSTIC DATA Indoor Units Table 9: Four-Way Ceiling Cassette Indoor Unit Sound Power Levels • Data is valid under diffuse field conditions. (dB[A]). • Data is valid under nominal operating conditions. • Sound power level is measured using rated conditions, and tested Model Sound Power Levels (dB[A]) in a reverberation room per ISO 3741 standards.
Page 23
ACOUSTIC DATA Outdoor Units Figure 15: Four-Way Ceiling Cassette Outdoor Unit • Measurements taken with no attenuation and units operating at full load normal Sound Pressure Level Measurement Location. operating condition. • Sound level will vary depending on a range of factors such as construction (acous- tic absorption coefficient) of particular area in which the equipment is installed.
Page 24
ACOUSTIC DATA Outdoor Units • Data is valid under diffuse field conditions. Table 11: Four-Way Ceiling Cassette Outdoor Unit Sound Power Levels (dB[A]). • Data is valid under nominal operating conditions. • Sound power level is measured using rated conditions, and tested Model Sound Power Levels (dB[A]) in a reverberation room per ISO 3741 standards.
REFRIGERANT FLOW DIAGRAMS LCN188HV4 Indoor Units Figure 18: LCN188HV4 Refrigerant Flow Diagram. Gas pipe connection port Heat exchanger (flare connection) Heating Evaporator Outlet Cooling Turbo fan Temperature Thermistor Indoor Air Temperature Thermistor Evaporator Inlet Temperature Thermistor Liquid pipe connection port (flare connection) Table 12: LCN188HV4 Four-Way Ceiling Cassette Indoor Unit Thermistor Details.
Page 26
REFRIGERANT FLOW DIAGRAMS LCN249HV, LCN369HV Indoor Units Figure 20: LCN249HV, LCN369HV Refrigerant Flow Diagram. Gas Pipe Connection Port Heat Exchanger (Flare Connection) Heating Cooling Evaporator Outlet Turbo Fan Temperature Thermistor Suction Air Temperature Thermistor Humidity Sensor Evaporator Inlet Temperature Thermistor Liquid Pipe Connection Port (Flare Connection) Table 16: LCN249HV, LCN369HV Four-Way Ceiling Cassette Indoor Unit Thermistor...
Page 27
REFRIGERANT FLOW DIAGRAMS LCN429HV, LCN489HV Indoor Units Figure 21: LCN429HV, LCN489HV Refrigerant Flow Diagram. : Cooling : Heating (3D Turbo Fan) Table 19: LCN429HV, LCN489HV Four-Way Ceiling Cassette Indoor Unit Thermistor Details. Thermistor Description (Based on Cooling Mode) PCB Connector Indoor Air Temperature Thermistor CN_ROOM Evaporator Inlet Temperature Thermistor...
Page 28
REFRIGERANT FLOW DIAGRAMS LUU180HHV, LUU240HV, LUU360HV Outdoor Units Figure 22: LUU180HHV, LUU240HHV, LUU360HHV Refrigerant Flow Diagram. Condenser Outlet Pipe Temperature Thermistor Condenser Middle Pipe Temperature Thermistor Ø3/8 Inch Liquid Side 36,000 Btu/h Outdoor Piping Units have two (2) fans. High Pressure Sensor Vapor Side Piping...
Page 29
REFRIGERANT FLOW DIAGRAMS LUU420HHV, LUU480HHV Outdoor Units Figure 23: LUU420HHV, LUU480HHV Refrigerant Flow Diagram. Table 23: LUU420HHV, LUU480HHV Four-Way Ceiling Cassette Outdoor Unit Thermistor Details. Description PCB Connector Discharge Pipe Temperature Thermistor CN_DISCHARGE_BK Suction Pipe Temperature Thermistor CN_SUCTION_GR Condenser Outlet Pipe Temperature Thermistor CN_C_PIPE_VI Air Temperature Thermistor CN_AIR_YL...
ELECTRICAL CONNECTIONS General Power Wiring / Communications Cable Guidelines • Follow manufacturer’s circuit diagrams displayed on the inside of the control box cover. • Confirm power source specifications. • Properly ground the outdoor unit and the indoor unit per National Electrical Code (NEC) and local codes. •...
Page 36
Optional controllers (see “Functions, Controls, Options”, or contact an LG representative for more information) can connect to the Four-Way Ceiling Cassette indoor unit in one of two different ways. 1. LG Wired Remote Extension Cable with Molex plug (PZCWRC1; sold separately) that connects to the CN-REMO terminal on the indoor unit PCB.
Page 37
ELECTRICAL CONNECTIONS to black (ground wire) terminals from the remote controller to the indoor unit terminal blocks. Figure 32: PZCWRC1 LG Wired Remote Extension Cable. Verify the connectors are properly inserted. C/BOX Cable (Plug type) To Indoor Unit SPEED CN-REMO...
AIR VELOCITY AND TEMPERATURE DISTRIBUTION Figure 34: LCN188HV4 Air Velocity and Temperature Distribution Charts. Figure 35: LCN249HV Air Velocity and Temperature Distribution Charts. Cooling Heating Discharge angle: Outer - 30°, Inner - 67° Discharge angle: Outer - 36°, Inner - 70° Air velocity [ft/s] Air velocity [ft/s] 8.9 ft...
Page 39
AIR VELOCITY AND TEMPERATURE DISTRIBUTION Figure 36: LCN369HV Air Velocity and Temperature Distribution Charts. Cooling Heating Discharge angle: Outer - 30°, Inner - 67° Discharge angle: Outer - 36°, Inner - 70° Air velocity [ft/s] Air velocity [ft/s] 10.5 ft 10.5 ft 9.8 ft 9.8 ft...
When connected through the indoor unit, user will not be able to record data. This software can be used to both commission new systems and troubleshoot existing systems. LGMV data can be recorded to a “.CSV” file and emailed to an LG representative to assist with diagnostic evaluations. Recommended Minimum PC Configuration: •...
Page 41
SIMs consists of a hardware Wireless Local Area Network (WLAN) module, an interface cable, and a free downloadable application (app) for iOS® or Android™. The user must supply either an Apple® or an Android smart phone; SIMs is not optimized for tablets, and only be used with LG single zone and Multi F systems.
PERFORMANCE DATA Cooling Capacity Data on page 43 Maximum Cooling Capacity Data on page 48 Heating Capacity Data on page 53 Maximum Heating Capacity Data on page 56 Equipment Selection Procedure on page 59...
PERFORMANCE DATA Maximum Cooling Capacity LC188HHV4 Maximum Cooling Capacity Table for LC188HHV4 (LCN188HV4 + LUU180HHV) Table 30: LCN188HV4 / LUU180HHV Maximum Cooling Capacities. Indoor Air Temp. °F DB / °F WB Outdoor Air Temp. 68 / 57 73 / 61...
Page 49
PERFORMANCE DATA Maximum Cooling Capacity LC249HHV Maximum Cooling Capacity Table for LC249HHV (LCN249HV + LUU240HHV) Table 31: LCN249HV / LUU240HHV Maximum Cooling Capacities. Indoor Air Temp. °F DB / °F WB Outdoor Air Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72...
Page 50
PERFORMANCE DATA Maximum Cooling Capacity LC369HHV Maximum Cooling Capacity Table for LC369HHV (LCN369HV + LUU360HHV) Table 32: LCN369HV / LUU360HHV Maximum Cooling Capacities. Indoor Air Temp. °F DB / °F WB Outdoor Air Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72...
Page 51
PERFORMANCE DATA Maximum Cooling Capacity LC429HHV Maximum Cooling Capacity Table for LC429HHV (LCN429HV + LUU420HHV) Table 33: LCN429HV / LUU420HHV Maximum Cooling Capacities. Indoor Air Temp. °F DB / °F WB Outdoor Air Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72...
Page 52
PERFORMANCE DATA Maximum Cooling Capacity LC489HHV Maximum Cooling Capacity Table for LC489HHV (LCN489HV + LUU480HHV) Table 34: LCN489HV / LUU480HHV Maximum Cooling Capacities. Indoor Air Temp. °F DB / °F WB Outdoor Air Temp. 68 / 57 73 / 61 77 / 64 80 / 67 86 / 72...
PERFORMANCE DATA Maximum Heating Capacity LC188HHV4, LC249HHV Maximum Heating Capacity Table for LC188HHV4 (LCN188HV4 + LUU180HHV) Table 40: LCN188HV4 / LUU180HHV Maximum Heating Capacities. Outdoor Air Temp. Indoor Air Temp. °F DB °F DB °F WB -13.4 17.12 3.33 16.74 3.44...
Page 57
PERFORMANCE DATA Maximum Heating Capacity LC369HHV, LC429HHV Maximum Heating Capacity Table for LC369HHV (LCN369HV + LUU360HHV) Table 42: LCN369HV / LUU360HHV Maximum Heating Capacities. Outdoor Air Temp. Indoor Air Temp. °F DB °F DB °F WB -13.4 32.11 5.22 31.40 5.39 30.50 5.57...
Page 58
PERFORMANCE DATA Maximum Heating Capacity LC489HHV Maximum Heating Capacity Table for LC489HHV (LCN489HV + LUU480HHV) Table 44: LCN489HV / LUU480HHV Maximum Heating Capacities. Outdoor Air Temp. Indoor Air Temp. °F DB °F DB °F WB -13.4 38.51 5.68 37.65 5.87 36.57 6.06 35.98...
Page 60
• Use caution when sizing to meet listed capacity specifications for the scheduled manufacturer’s equipment. If further system design assistance is needed, or you have a unique application you would like to discuss, contact your LG sales rep. 60 | PERFORMANCE DATA...
PLACEMENT CONSIDERATIONS Indoor Unit Selecting the Best Location for the Indoor Unit WARNING explosion, and physical injury or death. Figure 40: Indoor Unit Clearance Requirements. Do’s Ceiling Select a location for installing the indoor units that will meet the following conditions: •...
Page 63
PLACEMENT CONSIDERATIONS Indoor Unit • Indoor units (IDUs) should not be placed in an environment where the IDUs will be exposed to harmful volatile organic compounds (VOCs) or in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in the environment where the IDUs are installed, proper air make up or supply and / or adequate ventilation should be provided.
PLACEMENT CONSIDERATIONS Outdoor Unit Selecting the Best Location for the Outdoor Unit DANGER • Do not install the unit in an area where combustible gas will generate, flow, stagnate, or leak. These conditions can cause a fire, resulting in bodily injury or death. •...
Page 65
Model vary based on surrounding ambient conditions and must be calculated and specified by the design (inches) (inches) engineer. LC188HHV4 Insulation thickness (value in parenthesis) = 3/8 inch. LC249HHV, LC369HHV, LC429HHV, Insulation thickness (value in parenthesis) = 1 inch. LC489HHV Insulation thickness (value in parenthesis) = 3/4 inch.
Page 66
PLACEMENT CONSIDERATIONS Outdoor Unit Oceanside Applications Figure 45: Oceanside Placement Using Windbreak. Use of a Windbreak to Shield from Sea Wind Windbreak Ocean winds will cause corrosion, particularly on the condenser and • Avoid installing the outdoor unit where it would be directly Sea wind exposed to ocean winds.
Page 67
PLACEMENT CONSIDERATIONS Outdoor Unit Minimum Allowable Clearance and Service Access Requirements Proper clearance for the outdoor unit coil is critical for proper unit operation. When installing the outdoor unit, consider service, inlet and outlet and minimum allowable space requirements as illustrated in the diagrams below and on the following pages. •...
Page 68
PLACEMENT CONSIDERATIONS Outdoor Unit Outdoor Unit (36,000 to 48,000 Btu/h Capacity) Service Access and Allowable Clearances When installing the outdoor unit, consider service, inlet, and outlet, and minimum allowable space requirements as illustrated in the following diagrams. Minimum 11-13/16 Strong Strong wind wind...
Page 69
PLACEMENT CONSIDERATIONS Outdoor Unit Obstacles above and on the Where there are obstacles on both suction Obstacle just on the and discharge sides (discharge side obstacle air discharge side. air discharge side. is higher than the outdoor unit). Where there are obstacles above, and on both Where there are obstacles on both suction suction and discharge sides (discharge side obstacle and discharge sides (discharge side obstacle...
PLACEMENT CONSIDERATIONS Installing Outdoor Units Indoors Installing Outdoor Units Indoors Single Zone Cassette outdoor units are engineered to be mounted outdoors and include technology designed to minimize the negative effects of winter weather’s freezing rain, sleet, and snow. Some building projects, however, necessitate placing the HVAC outdoor units indoors: •...
Page 71
PLACEMENT CONSIDERATIONS Installing Outdoor Units Indoors Provide a means to drain the condensate generated during heating mode and defrost cycle in addition to rainwater that infiltrates the inlet louver enclosed area. • Install a field-provided drain pan under the outdoor units and provide a path to a nearby floor drain. •...
Page 72
PLACEMENT CONSIDERATIONS Installing Outdoor Units Indoors Open Rate by Louver Radian Figure 50: Open Rate by Louver Radian Formula. ho = h * COS Total Area (A) = H * W Number of Open Spaces (N) = (Number of Louvers - 1) Effective Area (Af) = ho * W * N Louver Open Rate (n) = Af / A Af = A * n...
98.4 feet 98.4 feet Measured in Actual Feet) Additional Refrigerant Needed (oz/ft) 0.43 0.43 Figure 52: Typical LC188HHV4 and LC249HHV System Layout. Figure 53: Typical LC369HHV, LC429HHV, and LC489HHV System Layout. Unit = Feet Unit = Feet Max Length = A...
Page 74
20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics, U.S.A., Inc. Air Conditioning Technologies 4300 North Point Parkway Alpharetta, Georgia 30022 www.lghvac.com New Issue: EM_SZ_LGRED_Cassette_09_20...