(5) Program example
In this program example, when M101 turns ON, data in D250 to D254 of station No.4 (target station) are read out
to D700 to D704 of station No.1 (own station).
(a) System configuration example
CPU module
READ instruction
request source
(Own station)
D700
D701
D702
D703
D704
CPU module
READ instruction
request target
D250
(Target station)
D251
D252
D253
D254
(b) Devices used in the program example
• Link special relay (SB) and link special register (SW)
Device
SB0047
Baton pass status (own station)
Remark
• For details of link special relay (SB):
• For details of link special register (SW):
• Devices used by the user
Device
M100
Control data setting command
M101
Start contact
M105
Completion device
M106
Completion status indication device
Station No.1
CC-Link IE
Controller
Network module
Channel 1
Network No.1
CC-Link IE
Controller
Network module
Station No.4
Description
Page 568, Appendix 1
Page 584, Appendix 2
Description
CHAPTER 9 DEDICATED INSTRUCTIONS
Station No.2
CC-Link IE
CPU module
Controller
Network module
CC-Link IE
CPU module
Controller
Network module
Station No.3
Device
Description
SW00A0.3
Baton pass status of station No.4
Device
Description
D200 to
Control data
D217
D600
Error code storage device
D700 to
Read data storage device (station No.1)
D704
9
341