Mitsubishi Electric RMF-CA100-V1 Installation Instructions Manual
Mitsubishi Electric RMF-CA100-V1 Installation Instructions Manual

Mitsubishi Electric RMF-CA100-V1 Installation Instructions Manual

Thermostat interface
Hide thumbs Also See for RMF-CA100-V1:

Advertisement

Quick Links

RMF-CA100-V1
Thermostat Interface
INSTALLATION / INSTRUCTION MANUAL
Read prior to installing/operating device. Keep this manual for future reference.
Contents
Supplied Parts. ........................................................................... 1
1.
Safety Precautions. .................................................................... 1
2.
Installation ....................................................................................... 1
3.
System Configuration ...................................................................... 3
4.
Operator Instructions .................................................................. 3
5.
. Supplied Parts
1
RMF-CA100-V1 Thermostat Interface (1)
RMF-CA100 Manual (1)
2
Safety Precautions
.
WARNING - INCORRECT HANDLING CAN RESULT IN ELECTRICAL INJURY, DEVICE MALFUNCTION AND DAMAGE
THOROUGHLY READ THE FOLLOWING SAFETY PRECAUTIONS BEFORE EACH USE OF THIS PRODUCT (THE "DEVICE").
Do not expose the device to, or immerse the device in, water. Doing so could lead to electrical shock to a person, device malfunction or
device damage.
Do not install the device in a bathroom, kitchen, or any room where steam could form. Condensation could develop on or around the device and
cause electrical shock to a person, device malfunction and device damage.
Do not install the device in a location where a gas leak could occur.
Do not expose the device to heat or radiation, including direct sunlight, or install the device in a location where the temperature could be greater
than 40°C (104°F) or less than 0°C (32°F). Doing any of these things could result in device deformation or device malfunction.
Always ensure the device is installed in an area without exposure to high frequency noise.
Power generators, inverters, and high-frequency or radio communication equipment may interfere with the operation of this device.
All electrical work should be performed by a qualitied technician and in accordance with applicable laws and the instructions outlined in this
manual.
Use standard wiring with the proper current capacity to avoid current leak, excessive heat, and fire.
Use only specified cables and wiring; securely connect each so that the terminals do not bear any weight.
Include slack in the power supply wiring. Tension in the wiring may cause it to excessively heat up and break, which could result in a fire.
Improperly connected or short-circuited cables or wiring may produce heat and cause device malfunction, device damage, and fire.
Capacity shortage to the power supply circuit or improper installation may result in electrical shock or fire.
Do not modify or alter this device or cable in any manner whatsoever.
3. Installation
Thermostat may be configured for use with a conventional system. For mode settings please refer to
WWW.MITSUBISHITECHINFO.CA website M & P Series Indoor Unit Function Mode Setting chart in Application / Misc section
Make all connections with 18 AWG thermostat wire.
Wire connection terminals support 20-30VAC.
High/medium/low fan signals (G1, G2, G3) are optional, and may not be available on all thermostat models.
Auxiliary heat control is not controlled by the RMF-CA100. Auxiliary heat control remains with Mitsubishi CN24
connector on compatible indoor units.
MODE SELECTION
1.
Select 1 or 2 stage thermostat operation using dipswitch 1-1:
OFF position (default) In the OFF position RMF-CA100 configures for 2 stage heating and cooling thermostats (Y1, Y2 & W1, W2)
1

Advertisement

loading

Summary of Contents for Mitsubishi Electric RMF-CA100-V1

  • Page 1 Installation ..................1 System Configuration ..............3 Operator Instructions ..............3 . Supplied Parts RMF-CA100-V1 Thermostat Interface (1) RMF-CA100 Manual (1) Safety Precautions WARNING - INCORRECT HANDLING CAN RESULT IN ELECTRICAL INJURY, DEVICE MALFUNCTION AND DAMAGE THOROUGHLY READ THE FOLLOWING SAFETY PRECAUTIONS BEFORE EACH USE OF THIS PRODUCT (THE “DEVICE”).
  • Page 2 ON position In ON position product is configured for use with single stage heating / cooling thermostats (Y1, W1) Example 1: Two-Stage Cooling and Heating - Dipswitch 1-1 set to OFF position (default position) RMF-CA100 operates in dual stage heat / cool mode using thermostat signals W1, W2, Y1, Y2, and fan signal (G). G1, G2 and G3 are available but not required.
  • Page 3 The RMF-CA100 relies upon both the dry-contact thermostat and the indoor unit’s thermistors in order to monitor room temperature. The thermostat senses room temperature and establishes set temp. The Mitsubishi Electric indoor unit’s return air thermistor is used for cooling and heating calculation.
  • Page 4 If the state of operation is No Call state: If 1 hour has not elapsed since exit heat mode (thermal off), the MODE display HTG HOLD (heating hold). If G1 thermo input is ON, the LCD display reads MODE: FAN G1 FAN: LOW If G2 thermo input is ON, the LCD display reads MODE: FAN G2 FAN: MED If G3 thermo input is ON, the LCD display reads MODE: FAN G3 FAN: HIGH If G thermo input is ON, and if G1 G2 &...
  • Page 5 Operator Instructions: Screens – Test Settings There are three menu options available in the TEST SETTINGS mode. While in TEST SETTING mode, pressing MENU button returns system to normal operation. After 1 hour in HEAT TEST or COOL TEST mode the system automatically exits test mode and returns to default screen and returns to normal operation.
  • Page 6 MULTI-POSITION AIRHANDLING UNIT KEY MODE SETTING / FUNCTION TABLE Initial Mode Settings Mode (Function) # Setting # Check Setting Disabled Power Failure Auto Restart Enable Indoor Unit Operating Average Indoor Temperature Set By Indoor Unit's remote Controller Detecting Remote Controller's Internal Sensor Not Supported LOSSNAY Supported (indoor unit is not equipped with outdoor air intake)