Adding Refrigerant

After finishing vacuuming, exchange the vacuum pump with a refrigerant cylinder and start additional charging of refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without additional refrigerant.
Heat pump type
Additional re frigerant
charge amount at local site
Table 1
Liquid pipe dia. (mm)
Additional refrigerant amount/1m liquid pipe (kg/m)
Table 2
Standard type
High Efficiency type
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and gas sides, operate the
air conditioner in COOL mode, and then charge refrigerant into service port at the gas side.
In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
Outdoor unit type
Charging amount (kg)
= Real length of liquid pipe ×
Combined HP
(HP)
8
8HP
10
10HP
12
12HP
14
14HP
16
16HP
18
10HP
20
10HP
22
12HP
24
12HP
26
16HP
28
16HP
30
16HP
32
16HP
34
12HP
36
12HP
38
16HP
40
16HP
42
16HP
44
16HP
46
16HP
48
16HP
16
8HP
24
8HP
26
10HP
28
10HP
30
10HP
32
8HP
34
10HP
36
10HP
38
10HP
40
10HP
42
12HP
44
12HP
46
12HP
48
12HP
MAP080
MAP100
Additional refrigerant charge
amount per 1 m liquid pipe
(Table 1)
6.4
9.5
0.025
0.055
Combined outdoor units
(HP)
8HP
10HP
10HP
12HP
10HP
12HP
14HP
16HP
12HP
10HP
12HP
12HP
12HP
10HP
12HP
12HP
14HP
12HP
16HP
12HP
16HP
14HP
16HP
16HP
8HP
8HP
8HP
8HP
8HP
10HP
8HP
10HP
10HP
8HP
8HP
8HP
8HP
10HP
8HP
10HP
10HP
10HP
10HP
10HP
10HP
12HP
10HP
12HP
12HP
12HP
12HP
MAP120
MAP140
11.5
Corrective amount of refrigerant depending
+
on HP of cooperating outdoor units
(Table 2)
12.7
15.9
19.1
0.105
0.160
0.250
C (Corrective amount
of refrigerant) (kg)
10.5
11.5
12.5
10.0
12.0
14.0
8HP
8HP
8HP
8HP
10HP
10HP
10HP
10HP
12HP
MAP160
22.2
0.350
1.5
2.5
3.5
8.5
0.0
3.0
5.0
7.5
8.5
9.5
3.0
4.0
6.0
7.0
8.0
0.0
-4.0
-4.0
-2.0
0.0
-6.0
-6.0
-6.0
-6.0
-5.0
-4.0
-2.0
0.0
2.0