Siemens SITRANS LVL200S Operating Instructions Manual

Siemens SITRANS LVL200S Operating Instructions Manual

Dpdt relay
Hide thumbs Also See for SITRANS LVL200S:

Advertisement

Quick Links

Operating Instructions · April 2008
SITRANS LVL200S

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS LVL200S

  • Page 1 Operating Instructions · April 2008 SITRANS LVL200S...
  • Page 2: Table Of Contents

    Instrument repair ..... . . 23 8 Dismounting Dismounting steps ..... . 24 SITRANS LVL200S l RELAY (DPDT)
  • Page 3 "Product description". Instructions manuals for accessories and replacement parts Tip: To ensure reliable setup and operation of your SITRANS LVL200S, we offer accessories and replacement parts. The associated documents are: 33997 - Electronics module SITRANS LVL200 SITRANS LVL200S l RELAY (DPDT)
  • Page 4: About This Document

    This symbol indicates special instructions for Ex applications. List The dot set in front indicates a list with no implied sequence. à Action This arrow indicates a single action. Sequence Numbers set in front indicate successive steps in a procedure. SITRANS LVL200S l RELAY (DPDT)
  • Page 5: For Your Safety

    During work on and with the device the required personal protection equipment must always be worn. 2.2 Appropriate use SITRANS LVL200S is a sensor for level detection. You can find detailed information on the application range in chapter "Product description".
  • Page 6: Safety Approval Markings And Safety Tips

    The safety approval markings and safety tips on the device must be observed. 2.6 CE conformity SITRANS LVL200S is in CE conformity with EMC (89/336/ EWG), fulfils NAMUR recommendation NE 21 and is in CE conformity with LVD (73/23/EG). Conformity has been judged according to the following...
  • Page 7: Product Description

    - Safety Manual "Functional safety according to IEC 61508 or IEC 61511 (SIL)" - Ex-specific "Safety instructions" (with Ex-versions) - if necessary, further certificates SITRANS LVL200S consists of the following components: Components Housing cover Housing with electronics process fitting with tuning fork Fig.
  • Page 8: Principle Of Operation

    Product description 3.2 Principle of operation SITRANS LVL200S is a point level sensor with tuning fork for Area of application level detection. It is designed for industrial use in all areas of process technology and can be used in liquids.
  • Page 9: Operation

    Unless otherwise indicated, the packages must be stored only under the following conditions: Not in the open Dry and dust free Not exposed to corrosive media Protected against solar radiation Avoiding mechanical shock and vibration SITRANS LVL200S l RELAY (DPDT)
  • Page 10 Product description Storage and transport temperature see "Supplement - Storage and transport temperature Technical data - Ambient conditions" Relative humidity 20 … 85 % SITRANS LVL200S l RELAY (DPDT)
  • Page 11: Mounting

    Mounting 4 Mounting 4.1 General instructions In general, SITRANS LVL200S can be installed in any position. Switching point The instrument simply has be mounted in such a way that the tuning fork is at the height of the desired switching point.
  • Page 12 With flange versions, the fork is directed as follows to the flange holes. Fig. 5: Fork position with flange versions Use the recommended cables (see chapter "Connecting to Moisture power supply") and tighten the cable gland. SITRANS LVL200S l RELAY (DPDT)
  • Page 13 (e.g. by cleaning processes) or on cooled or heated vessels. Fig. 6: Measures against moisture penetration Do not hold SITRANS LVL200S on the tuning fork. Particularly Transport with flange or tube versions, the tuning fork can be damaged just by the weight of the instrument.
  • Page 14: Mounting Instructions

    SITRANS LVL200S is in the same fork position after being screwed in. Remove therefore the supplied seal from the thread of SITRANS LVL200S. This seal is not required when using a welded socket with O-ring in front.
  • Page 15 To minimise flow resistance caused by the tuning fork, Flows SITRANS LVL200S should be mounted in such a way that the surfaces of the blades are parallel to the product movement. SITRANS LVL200S l RELAY (DPDT)
  • Page 16: Connecting To Power Supply

    Take note of the general installation regulations. As a rule, connect SITRANS LVL200S to vessel ground (PA), or in case of plastic vessels, to the next ground potential. On the side of the housing there is a ground terminal between the cable entries.
  • Page 17: Wiring Plan, Single Chamber Housing

    10 Screw the housing cover on The electrical connection is finished. 5.3 Wiring plan, single chamber housing The following illustrations apply to the non-Ex as well as to the EEx-d version. SITRANS LVL200S l RELAY (DPDT)
  • Page 18 DIL switch for mode adjustment DIL switch for switching point adaptation Ground terminal Connection terminals We recommend connecting SITRANS LVL200S in such a way Wiring plan that the switching circuit is open when there is a level signal, line break or failure (safe condition).
  • Page 19: Set Up

    Note: For test purposes, immerse the tuning fork of SITRANS LVL200S always in liquids. Do not test the function of SITRANS LVL200S with the hand. This can damage the sensor. 6.2 Adjustment elements Fig. 10: Oscillator SWE60R - Relay output...
  • Page 20: Functional Chart

    Level Switching status Control lamp Mode A Overflow protection (6) (7) Relay energized Green Mode A Overflow protection (6) (7) Relay deenergized Mode B Dry run protection (6) (7) Relay energized Green SITRANS LVL200S l RELAY (DPDT)
  • Page 21 Set up Level Switching status Control lamp Mode B Dry run protection (6) (7) Relay deenergized Failure of the supply voltage (mode A/B) (6) (7) Relay deenergized off Failure (6) (7) Relay deenergized flashes red SITRANS LVL200S l RELAY (DPDT)
  • Page 22: Maintenance And Fault Rectification

    The first measure to be taken is to check the output signal. In Fault rectification many cases, the causes can be determined this way and the faults rectified. ? SITRANS LVL200S signals "covered" when the vibrating Checking the switching signal element is not submerged (overfill protection) ? SITRANS LVL200S signals "uncovered"...
  • Page 23: Exchange Electronics

    These electronics modules are called SW60E or SW60E1. 7.4 Instrument repair If it is necessary to repair the instrument, please contact Siemens Milltronics Process Instruments Inc. You find the locations on our homepage "www.siemens.com/processauto- mation". SITRANS LVL200S l RELAY (DPDT)
  • Page 24: Dismounting

    Correct disposal avoids negative effects to persons and environment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you cannot dispose of the instrument properly, please contact us about disposal methods or return. SITRANS LVL200S l RELAY (DPDT)
  • Page 25 - Hygienic version (3A) < 0.3 µm (1.18 - Hygienic version (3A) Process fittings - Pipe thread, cylindrical G¾ A, G1 A (ISO 228 T1) ¾ NPT or 1 NPT - American pipe thread, tapered SITRANS LVL200S l RELAY (DPDT)
  • Page 26 Reference conditions and actuating variables according to DIN EN 61298-1 - Ambient temperature +18 … +30 °C (+64 … +86 °F) 45 … 75 % - Relative humidity 860 … 1060 mbar/86 … 106 kPa - Air pressure (12.5 … 15.4 psig) SITRANS LVL200S l RELAY (DPDT)
  • Page 27 Fig. 24: Influence of the process temperature on the switching point Shifting of the switching point in mm (in) Process temperature in °C (°F) Switching point at reference conditions (notch) Tuning fork Influence of the product density on the switching point SITRANS LVL200S l RELAY (DPDT)
  • Page 28 Shifting of the switching point in mm (in) Product density in g/cm³ (lb/in³) Switch position 0.5 g/cm³ (0.018 lb/in³) Switch position 0.7 g/cm³ (0.025 lb/in³) Switching point at reference conditions (notch) Tuning fork Influence of the process pressure to the switching point SITRANS LVL200S l RELAY (DPDT)
  • Page 29 -1 … 64 bar (-14.5 … 928 psig) depending on Process pressure the process fitting, e.g. flange (see following diagrams) SITRANS LVL200S of 316L/Has- -50 … +150 °C (-58 … +302 °F) telloy C4 (2.4610) SITRANS LVL200S l RELAY (DPDT)
  • Page 30 Supplement Process temperature (thread or flange temperature) with temper- ature adapter (option) - SITRANS LVL200S of 316L/ -50 … +250 °C (-58 … +482 °F) Hastelloy C4 70 °C (158 °F) 40 °C (104 °F) 0 °C (32 °F) -50 °C 50 °C...
  • Page 31 1 x plug M12 x 1; 1 x blind stopper M20 x 1.5 for max. wire cross-section 1.5 mm² (AWG 16) Screw terminals Adjustment elements Mode switch Max. detection or overflow/overfill protection Min. detection or dry run protection SITRANS LVL200S l RELAY (DPDT)
  • Page 32 FM (XP) CL I, DIV 1, GP ABCD (DIP) CL II, III, DIV 1, GP EFG Ship approvals Deviating data in Ex applications: see separate safety instructions. Only with Aluminium housing. Only with Aluminium housing. SITRANS LVL200S l RELAY (DPDT)
  • Page 33 ~ 59 mm ~ 116 mm (4 ") ") ø 80 mm ø 84 mm (3 ") ") M20x1,5/ M20x1,5 M20x1,5/ ½ NPT ½ NPT Fig. 30: Housing versions Aluminium housing Stainless steel housing, electropolished SITRANS LVL200S l RELAY (DPDT)
  • Page 34 G 3 / 4 A, 3 / 4 "NPT 32 ( 41 ( G1A, 1"NPT "NPT G1A, 1"NPT ø 33,7 mm ") Fig. 31: SITRANS LVL200S Thread Tri-Clamp Cone DN 25 Bolting DN 40 Flange Gas-tight leadthrough Temperature adapter SITRANS LVL200S l RELAY (DPDT)
  • Page 35 Supplement SITRANS LVL200S l RELAY (DPDT)
  • Page 36 © Siemens Milltronics Process Instruments Inc. 2008 Subject to change without prior notice *7ML19985KR01* Rev. 1.0 33836-EN-080421...