Valve Positioner
Brief Operating Instructions for TZID-C With Software Rev. 1.1 and Lower
Commissioning
1. Turn on the air supply to the positioner.
2. Apply the 4...20 mA analog input signal to the positioner.
3. Check for proper mounting: refer to instruction manual if needed.
• Open front dust cover from positioner to access the local control keys.
• Press and hold MODE.
• Additionally briefly press
• Release MODE.
• Press
or
to move the actuator to its mechanical limit stops in both directions, and note the values.
The angle of rotation on the display is indicated in degrees. Recommended positions of limit stops:
> -28° and < +28° for linear actuators
> -57° and < +57° for rotary actuators
• Adjust the mounting position of the positioner in relation to the actuator if required.
Configuration
4. Switch to the configuration level:
• Press and hold
• Additionally briefly press ENTER.
• Wait until the countdown from 3 to 0 is completed.
• Release
or
The device will automatically go to program level "P1.0"
5. Select the actuator type "ROTARY" or "LINEAR" using
Note: This Step must be done prior to Autoadjust (Step 6)
Copyright 2004 ABB. All Rights Reserved [February, 2004]
or
until mode 1.3 MAN_SENS is displayed.
or
simultaneously.
.
QUICK-START
or
.
PN25087

Advertisement

loading

Summary of Contents for ABB TZID-C

  • Page 1 QUICK-START TZID-C Valve Positioner Brief Operating Instructions for TZID-C With Software Rev. 1.1 and Lower Commissioning 1. Turn on the air supply to the positioner. 2. Apply the 4...20 mA analog input signal to the positioner. 3. Check for proper mounting: refer to instruction manual if needed.
  • Page 2 QUICK-START 6. Start Autoadjust: • Press and hold MODE • In Addition briefly press until "P1.1" is indicated. • Release MODE. • Press ENTER and keep it pressed until the countdown from 3 to 0 is finished. • Release ENTER Autoadjust is now activated; the complete process will take a few minutes. •...
  • Page 3 “Adaptive Control” to the “Fixed Control” mode once the TZID-C was optimized as explained above. The TZID-C also allows the user to access the control parameters manually via the front push buttons on the TZID- C or via the ABB Smart Vision software tool to perform custom optimization that may be required in some extreme cases when the standard AUTOSTROKE or Adaptive Control was not able to optimize the application.